1 sAFetY

1.1 Please read and keep in a safe place

 Please read through these instructions carefully before 

installing or operating. Following the installation, pass the instructions 
on to the operator. This unit must be installed and commissioned 
in accordance with the regulations and standards in force. These 
instructions can also be found at www.docuthek.com. 

1.2 explanation of symbols

 = Action 

= Instruction

1.3 Liability

We will not be held liable for damage resulting from non-observance 
of the instructions and non-compliant use.

1.4 safety instructions

Information that is relevant for safety is indicated in the instructions
as follows:

 DAnGeR

Indicates potentially fatal situations.

 WARnInG

Indicates possible danger to life and limb.

 CAUtIon

Indicates possible material damage.

All interventions may only be carried out by qualified gas techni-
cians. Electrical interventions may only be carried out by qualified 
electricians.

1.5 Conversion, spare parts

All technical changes are prohibited. Only use OEM spare parts.

1.6 Instructions provided by the company

Instructions provided by the company or individual responsible for the 
manufacture and/or overall installation of a complete system incor-
porating MAXON burners take precedence over the installation and 
operating instructions provided by MAXON. If any of the instructions 
provided by MAXON are in conflict with local codes or regulations, 
please contact MAXON before initial start-up of equipment.

EN – www

.docuthek.com

VALUPAK-II, 

low temperature burners

1 Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1

2 Checking the usage . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
3 Application requirements  . . . . . . . . . . . . . . . . . . . . . . . . 2

4 Installation  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

5 Start . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
6 Stop. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3

7 Commissioning. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3

8 VALUPAK package and back pressure  . . . . . . . . . . . . .4
9 Maintenance  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5

10 Technical data  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
11 Logistics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
12 Certification. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
13 Disposal  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8

oPeRAtInG InstRUCtIons

· Edition 11.22 · 32-00270 · EN

Summary of Contents for Maxon VALUPAK-II

Page 1: ...rventions may only be carried out by qualified gas techni cians Electrical interventions may only be carried out by qualified electricians 1 5 Conversion spare parts All technical changes are prohibited Only use OEM spare parts 1 6 Instructions provided by the company Instructions provided by the company or individual responsible for the manufacture and or overall installation of a complete system...

Page 2: ...ditional loads will be created on the burner 3 4 Burner mounting flange loads Check burner weight and reinforce burner mounting flange or combustion chamber furnace back wall if necessary to take the complete burner weight 4 INSTALLATION 4 1 Handling of VALUPAK II burners VALUPAK II burners are shipped as complete units Handle burn ers with care using proper equipment during unpacking transport li...

Page 3: ...r 4 6 1 Spark ignitor orientation The spark igniter can be mounted in 4 different positions on the burner housing seen from the back of the burner left standard position right up blower side and bottom if the air inlet is on top VP II 60 has only 3 different positions There s no up connection to the blower side only left right and bottom down All spark ignitor arrangements 1 2 NPT connection D R L...

Page 4: ...ance or approval agency having jurisdiction and depends on the total amount of fresh air and the volume of combustion space A 5 fold refresh rate should be minimum At the end of the purge time of the burner flame safeguard programming relay ignition is energized and the main gas valve will be energized shortly after Because main gas cock is closed the programmer will lock out requiring manual rese...

Page 5: ...n equip ment according to the installation s manual are an integral part of its safety Inspection activities and frequencies shall be carried out as spec ified in the installation s manual Perform the following activities at least annually as part of a rec ommended preventative maintenance routine 1 Inspect burner internal parts for wear and oxidation paying spe cial attention to the refractory of...

Page 6: ...lease kW HHV 6 10 12 6 15 15 15 15 Pilot capacity typical kW HHV 28 35 51 44 50 49 59 Turndown1 58 1 43 1 50 1 45 1 51 1 71 1 85 1 Q gas max m3 h st 33 7 41 8 61 3 64 8 73 6 102 6 123 1 Q gas min m3 h st 0 6 1 0 1 2 1 5 1 5 1 5 1 5 Q air max m3 h st 388 482 706 747 848 1133 1418 Q air min m3 h st 64 82 117 148 209 230 276 Excess air at max n 1 2 1 2 1 2 1 2 1 2 1 15 1 2 Excess air at min n 11 4 8 ...

Page 7: ...se kW HHV 6 10 12 6 15 15 15 15 Pilot capacity typical kW HHV 23 29 51 37 42 41 49 Turndown1 48 1 36 1 50 1 37 1 42 1 59 1 71 1 Q gas max m3 h st 28 1 34 8 61 3 54 0 61 4 85 2 102 6 Q gas min m3 h st 0 6 1 0 1 2 1 5 1 5 1 5 1 5 Q air max m3 h st 323 401 706 622 707 981 1133 Q air min m3 h st 55 72 117 144 174 205 230 Excess air at max n 1 2 1 2 1 2 1 2 1 2 1 2 1 15 Excess air at min n 9 9 7 8 10 1...

Page 8: ...all be stored dry inside Burner blocks have been cured carefully before shipment and shall be kept dry Wetting of the blocks could result in premature failures Packaging Do not discard packing material until loose items are accounted for The packaging material is to be disposed of in accordance with local regulations 12 CERTIFICATION 12 1 Eurasian Customs Union The products VALUPAK II meet the tec...