background image

Guangzhou Video-star Electronics Industrial Co., Ltd

www.video-star.com.cn

[email protected]

Tel.

:(

8620

39338986

Fax.

:(

8620

39338465

K-BUS

R

Thermostat

User manual-Ver. 1

CHTC-86/01.1.21

CHTC-86/01.1.22

CHTC-86/01.1.24

KNX/EIB Intelligent Installation Systems

Summary of Contents for CHTC-86/01.1.21

Page 1: ...cs Industrial Co Ltd www video star com cn marketing video star com cn Tel 8620 39338986 Fax 8620 39338465 K BUS R Thermostat User manual Ver 1 CHTC 86 01 1 21 CHTC 86 01 1 22 CHTC 86 01 1 24 KNX EIB Intelligent Installation Systems ...

Page 2: ...unction 13 3 9 binary input and temperature sensor input 13 4 Parameter setting description in the ETS 13 4 1 overview 13 4 2 parameter Settings window General 13 4 3 parameter setting interface Measurement Settings 18 4 4 Parameter setting interface Heating Cooling setpoint 23 4 5 Parameter setting interface Heating Cooling Control 34 4 6 Parameter setting interface Additional heating cooling 42 ...

Page 3: ...on Object 75 5 3 Threshold value communication object 82 5 4 Logic Communication Object 83 5 5 Timer Page 1 2 communication object 84 5 6 Pushbutton Interface Communication Object 85 5 6 1 Switch Communication Object 85 5 6 2 Dimming Communication Object 86 5 6 3 Shutter Communication Object 86 5 6 4 Scene Communication object 87 5 6 5 Temperature limiter underfloor heating Communication Object 88...

Page 4: ... other humidity related industries User can adjust the indoor temperature according to their needs by capacitive touch buttons LCD screen displays the status of the current temperature control This user manual provides specific technical information including installation and programming details and explains how to use the binary input by the application examples 1 1 Product and function instructi...

Page 5: ...e Structure chart and Wire Map Temperature control panel use standard 86 wall mounted installation through the bus terminal connected to EIB KNX system 2 1 Technical Parameter Power supply EIB KNX voltage 21 30V DC EIB KNX current consumption Max 12mA EIB KNX power consumption Max 360mW Auxiliary power supply voltage 20 30V DC power consumption 2W Input three input channels Can be Individually con...

Page 6: ...torage 25 C 55 C transportation 25 C 70 C Environmental conditions humidity 80 No dewing Installation standard 86 wall mounted installation Size 86 86 42 6mm Weight 0 3KG Temperature Measuring range 5 70 Resolution 0 1 Accuracy 0 5 Humidity Measuring range 0 100 RH Resolution 0 01 Accuracy 3 RH 2 2 Size Structure Picture Figure2 2 1 Thermostat Size picture ...

Page 7: ...ostat coupler size picture Figure2 2 2Thermostat connect picture KNX EIB Auxiliary power supply KNX EIB BUS NTC temperature Three binary inputs To ensure the accuracy and stability of the measurement Thermostat please note the following items 1 Keep away from air conditioners refrigerators stoves and other areas sensitive to changes in ...

Page 8: ...ing in extreme conditions and chemical vapors otherwise it will cause inaccurate readings of Thermostat 2 3 Button operation instruction LCD display the current temperature setting temperature the heating and cooling working mode wind speed weeks time timing marks relative humidity Button on the circuit board from left to right mode key increasing key reducing key wind speed key timing button and ...

Page 9: ...0 5 when adjust the time the reduction is 1 Wind speed key the key is used to adjust the fan speed The icon indicates the wind speed which is divided into four gears automatic transmission 1 2 and 3 transmission which can also switch the wind speed Timed key the key is mainly used for timing and modifying the regular time Before entering the timing Settings short press it can implement the timing ...

Page 10: ...m external NTC thermistors 3 3 Basic heating cooling and additional heating cooling control functions Thermostat has the basic heating refrigeration output control function according to the temperature set by the user in addition to basic heating refrigeration control function there is additional heating refrigeration control function as a supplement to the temperature control When the actual temp...

Page 11: ... actuator can maintain at a low level Continuous control can also control the rise and fall valve of the fan coil or KNX valve actuator PWM control PWM pulse width modulation control s values is calculated according to the actual temperature and set temperature and then calculate the on and off time of the switch valve to control it to achieve a comfortable room temperature state Switch valve only...

Page 12: ...ides two logic functions each has three inputs each input can be arbitrarily set it can be the message 1bit sent by the temperature threshold or the message 1bit sent by the humidity threshold or the message received from the bus also it can be obtained by getting the opposite message to participate in the logic operation the message 1 bit 1 byte will be output according to the result triggering t...

Page 13: ...ut Thermostat offers binary input and three roads which is used to switch dimming curtains and scene controls One way is externally connected to temperature sensor input which can be a NTC thermistor as an external temperature sensor or as a floor heating temperature limiter stops heating when floor heating is higher than the limited temperature heating 4 Parameter setting description in the ETS 4...

Page 14: ...t the Thermostat cycle and send a message 1 or 0 to the bus which shows that the panel is working well If fail it will stop sending the message 1 or 0 Options for No do not send Options for the value 0 cyclically send or send the value 1 cyclically Thermostat will send a message 0 or 1 according to the set period of time so the object in operation and Transmission period of in operation object par...

Page 15: ...n day Parameter Backlight in operation in day Parameter Backlight in no operation in night Parameter Backlight in operation in night Options 0 100 This parameter is mainly used to set up the LCD panel backlight brightness in the daytime or at night under the condition of operation and non operation The user can set the day or night through the bus also can identify the day or night by time points ...

Page 16: ...hat LCD backlight brightness of the backlight switch to daylight For example once setting to 6 00 that means LCD backlight brightness automatically switched to day mode when the time is 6 00 Parameter Time mode Options 24H AM PM This parameter set show the mode of time display 24H indicates the time on the Thermostat display system for 24 hours AM PM means the time display system in Thermostat for...

Page 17: ... fan coil actuator air condition means home air conditioning system adjusting household air temperature by controlling the infrared device Parameter Temperature control system Options Cooling Heating Heating and Cooling Basic and additional cooling Basic and additional heating Basic and additional Heating and Cooling This parameter is used to set the temperature control feature you can select the ...

Page 18: ...e when the screen being turned off Parameters Heating and cooling share object Options yes no This parameter is visible when choosing Heating and Cooling or Basic and additional Heating and Cooling in temperature control function this parameter is used to select whether the heating and cooling control value share a communication object to accommodate two or four control system controls 4 3 paramet...

Page 19: ...internal sensor and external sensor the local sensor and external temperature sensor will be used simultaneously this sets suit for a large area to temperature control such as a lobby where using many sensors at the same time temperature sensors B get the temperature from sensor A then get the proportion of the sum itself and then it will control the temperature based on the results of summation o...

Page 20: ...e Actual temperature This is the proportion summing process Parameters Send temperature at variation of Options Do not send 0 1 0 2 3 This parameter define Actual temperature can send the current temperature to the bus when a certain amount of temperature change If the option is Do not send the temperature only be sent to the bus through the Actual temperature because the temperature measurement v...

Page 21: ...rement by Thermostat to control The monitoring time will be re timed when the thermostat panel receives each packet send from the external temperature sensor Note The monitoring time from Thermostat for external temperature sensor should be at least 2 times for the time that the external temperature sensor sending messages for preventing packets missing Parameters Period of sending temperature Opt...

Page 22: ...ual humidity For example setting correction value to 1 if the humidity measured by the sensor is 40 then the corrected humidity is 40 1 41 Parameters Send rel Humidity at variation of Options Do not send 1 2 20 This parameter defines to change when humidity change a certain amount the communication object rel Humidity can send current humidity to the bus If choosing do not send humidity measuremen...

Page 23: ...the bus through its communication objects rel humidity 4 4 Parameter setting interface Heating Cooling setpoint In the setting of Temperature control system parameter s setting content will be different in this page according to your choice from Cooling Heating or Heating and Cooling Temperature can be set here under any work patterns including relative mode and absolute mode Figure 4 4 1 Paramete...

Page 24: ...GVS K BUS R KNX EIB Thermostat www video star com cn marketing video star com cn Tel 8620 39338986 Fax 8620 39338465 24 Figure 4 4 2 Parameter setting interface of Cooling setpoint ...

Page 25: ... programming There are 4 work patterns in temperature controller including comfort mode standby mode night mode and Frost Heating protecting mode Every mode has its corresponding temperature setting Comfort mode is applied to the daytime when someone at home Standby mode is applied to the daytime when no one at home for saving the energy Night mode is applied for the night time when someone at hom...

Page 26: ...are as follows Frost heating protection Comfort night standby forcing switchover Window status Presence object 1bit switching Work pattern to be activated Comfort Standby Night Frost heating protection 01 x x x x x x Comfort 02 x x x x x x Standby 03 x x x x x x Night 04 x x x x x x Frost heating protection 00 1 x x x x x Frost heating protection 00 0 1 x x x x Comfort 00 0 0 1 0 0 0 Comfort 00 0 ...

Page 27: ...change and cyclically In the Parameter of Send setpoint the ways of sending the temperature setpoint can be set When choosing do not send the temperature setpoint won t be sent It only can be sent to the bus after reading by setpoint temperature When choosing on change the temperature setpoint will be sent to the bus after the changing of temperature setpoint When choosing cyclically the temperatu...

Page 28: ...f the current temperature is lower than the temperature setpoint under heating comfort mode When Choosing switching heating cooling automatically in the parameter of Switchover between heating and cooling the object of Heating cooling switchover will send the current status of heating cooling to the fan coil controller or any other corresponding controllers to warm cool Under the condition of rela...

Page 29: ...ter of Cyclic transmission of heating cooling switchover in min can be found if you choose the automate switchover by dead zone from the Switchover between heating and cooling This parameter is use for setting the sending time period of heating cooling status Parameter control option after reset Options cooling heating control option before reset The parameter control option after reset can be fou...

Page 30: ...justment absolute adjustment Parameter of Setpoint adjustment is use for setting the adjusting way of the temperature setpoint For the option of relative adjustment the temperature setpoint is referred to definite comfortable temperature setpoint in every mode except the comfort mode For the option of absolute adjustment the temperature setpoint of comfort mode stand by mode night mode protecting ...

Page 31: ... option 0 100 The parameter is use for setting the reduction that decides the night mode s temperature setpoint which is changed with the comfort temperature setpoint under the circumstance of heating function For example if setting the deduction of 2 when the comfort temperature setpoint is 23 the stand by mode s temperature setpoint will be 21 Parameter of Setpoint frost protection at heating in...

Page 32: ...des the night mode s temperature setpoint which is changed with the comfort temperature setpoint under the circumstance of cooling function For example if setting the deduction of 2 when the comfort temperature setpoint is 23 the night mode s temperature setpoint will be 25 Parameter setpoint heat protection at cooling in 0 1Celsius Options 0 500 This parameter is used to set the temperature setpo...

Page 33: ...rature setpoint is set independently and is not affected by the comfort mode Parameter Setpoint frost protection at heating 0 1Celsius Options 0 255 Here it sets the temperature setpoint of heating function under frost protection mode This temperature setpoint is set independently and is not affected by the comfort mode Parameters Cooling comfort setpoint in 0 1Celsius Options 0 500 Here it sets t...

Page 34: ...cted Heating comfort setpoint is set to 21 C and cooling comfort setpoint is set to 25 C The dead zone between heating and cooling is 3 C If the heating setpoint is moved up the dead zone is also moved up If heating comfort setpoint is adjusted up to 23 C cooling comfort setpoint will be also adjusted up to 26 C to ensure that there is always a minimum distance of 3 C between heating and cooling I...

Page 35: ...alve 100 to open the valve if it is between 0 and 100 the actuator will adjust the controlling output according to the duty cycle of control target value For example assuming the cycle is 10mins set in the switch actuator the controlling value is 60 then the valve will be opened for 6mins closed for 4mins all cycles in this way Thermostat according to temperature conditions ratio range and integra...

Page 36: ...prevent that the small decline or rise of temperature causes the frequent switching on off of actuator and results in the frequent switching on off of the valve The delay interval is symmetrically disposed above and below the set temperature e g in the cooling mode if the set temperature is 21 the delay interval is 2 then the controlled object will send an on or 100 telegram at 22 and open the val...

Page 37: ... 8620 39338986 Fax 8620 39338465 37 Switching PI control Two position control fan coil control Parameter control parameter of heating system Options Hot water heating 5K 150min Floor heating 5K 240 min Electric heating 4K 100min Split unit 4K 90min PI auto tuning User defined parameter ...

Page 38: ...ers got from PI auto tuning may not be optimal During the process of PI auto tuning please do not adjust temperature setpoint or convert heating and refrigeration to prevent interference of PI auto tuning In the option of user defined parameter PI parameter values can be set through the following two parameters and application of Thermostat will calculate the control value basing on the given para...

Page 39: ... value will send normal control values If you select yes control object Heating Cooling control value will send negative control value If control value is off or 0 negative control value will be on or 100 If control value is on or 100 negative control is off or 0 If control value is 60 then negative control value is 40 Parameters minimum control value in Options 0 30 This parameter is used to set ...

Page 40: ...er sets time interval of control value cyclically send control value to the bus 0 means not using this parameter Each time it sends a control value to the bus cyclical sending time will be re timing Note the cycle time here should corresponds to the monitoring time of temperature control actuator therefore the time of cyclical sending telegram should be half or less of the monitoring time of tempe...

Page 41: ...uent switching on off of actuator and results in the frequent switching on off of the valve If the delay interval is set to be too large it will reduce the number of actuator s action and extend actuator s life but it will reduce control accuracy For example in the mode of heating if temperature setpoint is 20 the delay interval is 2 then the control object will send an on telegram at 19 open the ...

Page 42: ... between basic and additional heating cooling in 1C is used to set the setpoint temperature of the additional heating cooling if select additional heating the setpoint of additional heating basis comfort temperature at heating value of the parameter setting if select additional cooling the setpoint of additional cooling basis comfort temperature at cooling value of the parameter setting 4 7 Parame...

Page 43: ...ON OFF object Manual ON OFF This parameter is used to set the automatic and manual switchover of wind speed When you select object Automatic ON OFF and switch to automatic wind speed mode communication object 21 sends 1 When you switch to manual wind speed mode communication object 21 sends 0 and communication object 22 sends the control value of corresponding wind When choosing object Manual ON O...

Page 44: ... the wind speed reaches the time to return to the automatic mode the communication object 21 sends packets to return to automatic speed mode Parameter Threshold value in for fan speed 1 at heating Parameter Threshold value in for fan speed 2 at heating Parameter Threshold value in for fan speed 3 at heating Options 0 100 Threshold value in for fan speed 1 at heating to set packet value that commun...

Page 45: ... corresponding wind speed When switching to a working mode the communication object sends the control value the corresponding wind speed is entered Each switching to an operation mode timing mark start timing in speed return mode time will return to automatic speed mode 4 9 Parameter window Threshold value Parameter window Threshold value is shown in Figure 4 9 here is to set the threshold values ...

Page 46: ...GVS K BUS R KNX EIB Thermostat www video star com cn marketing video star com cn Tel 8620 39338986 Fax 8620 39338465 46 Figure 4 9 Parameter window Threshold value Setpoints of threshold values ...

Page 47: ...e new value when the power of the BUS is off Parameter Negative hysteresis temperature 0 1 Options 5 50 This parameter is used to set the hysteresis value of the low threshold value to high threshold value Assuming the hysteresis value is 3 then the lower threshold high threshold value 3 When the high threshold changes the low threshold changes accordingly Parameter If temperature is lower than th...

Page 48: ...t temperature is below the low threshold and above the high threshold After a bus reset or programming if the current temperature is between the low threshold and the high threshold the object does not send telegram to the bus Parameter Cycle time for temperature threshold value min if used Options 1 255 This parameter is used to set the object 1bit 1byte output temperature cycle time on the bus t...

Page 49: ...ng the lock Options Do not send Update This parameter sets the action when the threshold value is started again Select do not send when the object temperature threshold value1 2 block receives the telegram 0 if the threshold value changes 1bit 1byte output temperature value will be sent immediately but not vice versa If the current temperature is between high and low thresholds no telegram will be...

Page 50: ...eshold value1 2 and once changing in the bus will save the new value when the power of the BUS is off Parameter Negative hysteresis humidity Options 1 10 This parameter is used to set the hysteresis value of the low threshold value to high threshold value Assuming the hysteresis value is 5 then the lower threshold high threshold value 5 When the high threshold changes the low threshold changes acc...

Page 51: ...byte telegram value Options Logic 1bit 0 1 1byte 0 255 This parameter is used to specify the telegram value that object 1bit 1byte output humidity sends when the current humidity is below the low threshold and above the high threshold After a bus reset or programming if the current humidity is between the low threshold and the high threshold the object does not send telegram to the bus Parameter C...

Page 52: ... of the humidity threshold output if User selects yes Parameter Behaviour when releasing the lock Options Do not send Update This parameter sets the action when the threshold value is started again Select do not send when the object humidity threshold value1 2 block receives the telegram 0 if the threshold value changes 1bit 1byte output humidity value will be sent immediately but not vice versa I...

Page 53: ...t or humidity threshold 1bit or from the bus these telegrams can also be inverted then participate in logic operations Figure 4 10 1 Parameter window Logic Parameter Active logic function Options enable disable Here is to set whether to enable logic functions Parameter logic1 Parameter logic 2 Options enable disable This parameter sets whether to enable logic 1 and logic 2 If select enable it mean...

Page 54: ...n logic operation and the operation result is then runs logical operation with Input3 at last the final logical result is obtained according to the final results two different types of data transmission can be achieved When the final logic result is 1 user can specify the values of two different types of transmission on the bus when the final result is 0 user may further specify two different type...

Page 55: ...put5 If one of the logic input isn t used the logic input and its logic operations should be ignored If in a certain threshold state no telegrams are sent then in this case logic input is not involved in the logic operation equivalent do not use and if the threshold function is disabled and in this case logic input is also equivalent to do not use If the object value of the threshold value is in a...

Page 56: ... telegram cyclically sending time can be set in the following parameter cycle time for humidity threshold value min in the settings you can send two object types the value of the object is set in the following parameters logic1bit 1byte telegram value Parameter logic 1 bit 1byte telegram value Options 1bit 0 1 1byte 0 255 Here is to set the value of the logic object sends when the logic results ar...

Page 57: ...egram 1 Parameter Behaviour when releasing the lock Options Do not send Update This parameter sets the action when the logic is started again Select do not send when the object humidity threshold value1 2 block receives the telegram 0 if the threshold value changes 1bit 1byte output humidity value will be sent immediately but not vice versa If selecting update when logic 1 2 bock receives telegram...

Page 58: ...enable disable This parameter is used to activate a timing time After the timing is enabled timing mode switching and manually adjust the timing time can be achieved If the 16 timers has overlap time thermostat will send the front timer mode and data to the bus When regular time enabled users can long press the timer button to modify the regular time Parameter Week Options Monday Tuesday Wednesday...

Page 59: ...ons 0 23 This parameter is used to set time in hours Parameter Minute Options 0 59 This parameter is used to set time in minutes Parameter operating mode Options comfort mode standby mode night mode frost heat protection unchanged This parameter sets the room control mode when the set timing time reaches Parameter Reaction at regular time Options No reaction 1bit value 0 1 2bit value 0 3 4bit valu...

Page 60: ...puts and a temperature sensor input three binary inputs can be set to switch dimming curtains and other functions Temperature sensor inputs can be connected an external NTC thermistor as an external temperature sensor of thermostat panel or as a temperature limiter of underfloor heating to stop heating when the heating temperature is higher than the limit Figure 4 12 1 Parameter window Push button...

Page 61: ...sets the number of telegrams can be sent in a maximum of 17 seconds Bus voltage is restored the device initialization is complete the timer starts and starts counting telegrams once the maximum allowed number of telegrams sent once reached then no telegrams will be sent to the bus until the end of 17 seconds After the end of the 17 seconds the timer re starts and the telegram restarts to count Par...

Page 62: ...eration If selecting no action no actions will be performed If selecting toggle it will perform the inverse operation namely inverse the last value and send again such as before executing the On to operate inverted perform the Off operation Parameter Send object value after voltage recovery if yes not equal toggle Options yes No Here to set whether to send the current switch value of Switch X to t...

Page 63: ...t switch value of Switch X to the bus Parameter option Always is selected regardless of the object Switch X in the current switch value is 0 or 1 the switch will send cyclically the current value to the bus Parameter option is set as If switch off or If switch on Only when the current value is the same as the option the value will be cyclically sent Parameter Interval of Tele Cyclic send Base Fact...

Page 64: ...he connecting time of input contacts is longer that the set time the operation is considered as long operation Parameter Reaction on short operation Options no action off on toggle Through this parameter user can set the operation after Switch X is triggered namely the switching operations when the contact input is short operation Parameter Reaction on long operation Options brighter darker bright...

Page 65: ...ess range percentage of cyclically sending dimming telegrams Parameter Transmission dimming stop telegram Options yes no It sets whether to send stop dimming telegram when the dimming stops Parameter Cyclical transmission of dimming telegrams Options disable enable It sets whether to cyclically send dimming telegram Parameter Time between two dimming telegrams in 0 1s Options 3 250 If selecting en...

Page 66: ...0 1s Options 3 250 This parameter defines the contact input s effective time for a long operation If the connecting time of input contacts is longer that the set time the operation is considered as long operation Parameter Function switchover blinds roller shutter Options Shutter Roller shutter Set action performed when contact input is operated Note that if the parameter reaction on operation sel...

Page 67: ...p This parameter can only be set if 1 byte has been set as object type which can be used to set the position percent values that a connected blind shall be lowered or raised to Options 0 100 the value 0 means travel up completely the value 100 means travel down completely Parameter value for stats position down value for stats position up This parameter can only be set if 1 byte has been set as ob...

Page 68: ...The setting scene number 1 64 corresponding to the telegram value 0 63 Parameter storage function light scenes Options enable disable Here is to set whether to enable scene saving If select enable long press the switch will save the scene short press the switch will recall scene the calling and saving of the scene are controlled by the same 1byte communication object Parameter Long operation after...

Page 69: ...gure 4 12 6 parameter window Input 4 Parameter Function of input 4 Options No function external temperature sensor for RTC temperature limiter underfloor heating If temperature sensor inputs is used as an external temperature sensor of thermostat panel it should be connected an external NTC thermistor but also selects external sensor or internal sensor and external sensor for Temperature sensor in...

Page 70: ...used to send the current floor temperature Floor temperature sending variation refers to parameter Send temperature at variation of the floor temperature cyclically sending refers to parameter period of sending temperature The following parameter is visible if selecting temperature limiter underfloor heating in the Function of input 4 Parameter Limit temperature in 1Celsius Options 1 50 This param...

Page 71: ...jects corresponds to a different commands If 1byte type is selected control command sent by 1byte object different 1 byte value corresponds to a different commands These control commands similar to the air conditioning on the remote control commands Users can learn the air conditioner remote control commands to the infrared transmitter module configure the Thermostat with corresponding parameters ...

Page 72: ...Options 5 64 10s 2h This option sets the time period of cyclically send the parameter Send setpoint is visible when selecting the cyclically or on change and cyclically Parameter Object type for controlling air condition Options 1bit 1byte This option is set to format of sending command 1bit means that using different 1bit communication objects to control different commands the specific informatio...

Page 73: ...for fan speed low Parameter Command for fan speed auto stop Options 1 64 These parameters are used to set the command value of switching speed velocity When parameter Object type for controlling air condition is selected 1byte it is visible Parameter Command for setpoint 16 31Celsius Options 1 64 These parameters are to adjust the command value of set temperature When parameter Object type for con...

Page 74: ...eans enabling communication functions W means the value of communication objects can be modified through the bus R means the value of communication objects can be read through the bus T means the communication object has a transmission function U means the value of the communication objects can be updated 5 1 General Setting Communication Object Figure 5 1 General Communication Object Number Objec...

Page 75: ...Figure 5 2 Temperature control communication object No Object name Functions Data Types Flags DPT 2 Input external temperature Temperature 2 byte C R W 9 001 DPT_Value_Temp This communication object is for receiving temperature the external temperature sensor sends on the bus 3 Actual temperature Temperature 2 byte C R T 9 001 DPT_Value_Temp The communication object is used to send the current tem...

Page 76: ...ject receives a telegram 2 the thermostat panel will control the actuator according to the standby mode setting 6 Window status Setpoint temperature 1 bit C R W 1 019 DPT_Window_Door This communication object is used to connect a window contact Receive telegram 1 the windows open Receive telegram 0 the windows closed 7 Presence object Setpoint temperature 1 bit C R W 1 001 DPT_Switch This communic...

Page 77: ... used to activate the frost heat protection mode Receiving telegram 1 will activate the frost heat protection mode receiving telegram 0 will not activate the frost heat protection mode Receive telegram 1 activate the frost heat protection mode Receive telegram 0 not activate the frost heat protection mode 12 Temperature operating mode switchover Setpoint temperature 1 byte C R W 20 102 DPT_HVACMod...

Page 78: ...ating setpoint of the current operating mode on the bus sending way depends on the parameter send setpoint in 4 4 The communication object is used to modify the heating setpoint of the current operating mode Note that due to the relative adjustment of setpoint temperature the setpoint temperature in standby mode night mode and frost heat protection mode can only be increased to the maximum setpoin...

Page 79: ... no effect on the temperature control 18 Output RHCC status Temperature control 2 byte C R T 22 101 DPT_StatusRHCC RHCC Status Report Bit no 0 error 1 alarm 0 normal 8 heating or cooling 0 cooling 1 heating 12 Dewpoint alarm 1 alarm 0 normal 13 frost alarm 1 alarm 0 normal 14 over heat cold alarm 1 alarm 0 normal Over heat the current temperature exceed 35 Over cooling the current temperature belo...

Page 80: ...sable enable temperature control including disable enable basic heating cooling control and additional heating cooling control When receiving telegram 1 the object Basic heating cooling control value and object additional heating cooling control value stop sending control telegrams when receiving telegram 0 they update control value immediately Receive telegram 1 disable temperature control Receiv...

Page 81: ... Setpoint adjustment Selects absolute adjustment it is used to modify the night mode temperature at heating 87 Setpoint frost protection Setpoint temperature 2byte C R W 9 001 DPT_Value_Temp This communication object would display when parameter Setpoint adjustment Selects absolute adjustment it is used to modify the frost protection mode temperature at heating 88 Cooling comfort setpoint Setpoint...

Page 82: ...witch When the temperature is higher than the current high threshold or below the low threshold 1bit telegram can be sent via this object to the bus specific telegrams can be set by the parameter logic 1bit telegram value 0 1 29 33 1 byte output temperature Temperature threshold value 1 2 1byte C R T 5 010 DPT_Value_1_Ucount When the temperature is higher than the current high threshold or below t...

Page 83: ...h threshold or below the low threshold 1bit telegram can be sent via this object to the bus specific telegrams can be set by the parameter 1byte telegram value 0 255 38 42 Humidity threshold value 1 2 block Humidity threshold value 1 2 1bit C R W 1 001 DPT_Switch This communication object is used to disable or enable the function of the humidity threshold value Disabled and enabled actions can be ...

Page 84: ...0 Logic 1 2 block Logic 1 2 1bit C R W 1 001 DPT_Switch This communication object is used to disable or enable the logic function Disabled and enabled actions can be set by the parameter Receive telegram 1 disable the logic function Receive telegram 0 enable the logic function 5 5 Timer Page 1 2 communication object Figure 5 5 Timer communication object Number Object name Functions Data Types Flag...

Page 85: ...the timer time reaches this communication object sends the appropriate data values to the bus the user can select the appropriate data type and value in the parameter Reaction at regular time and the parameter Output value as required for transmission 5 6 Pushbutton Interface Communication Object 5 6 1 Switch Communication Object 5 6 1 Switch Communication Object Number Object name Functions Data ...

Page 86: ...mmunications objects with channel function are Disable the operations performed are the same 5 6 2 Dimming Communication Object 5 6 2 Dimming Communication Object Number Communication object name Functions Data Types Flags DPT 53 56 59 Switch CH A Switch 1bit C W T 1 001 DPT_Switch When CH A Switch is enabled this communication object is visible through short push according to the parameters setti...

Page 87: ...ue set by the user 54 57 60 Stop lamella adj CH A B C Blind 1bit 1byte C T 1 007 DPT_Step 5 001 DPT_Scaling The communication objects by sending commands to the bus stop adjust curtains The communication object can send 1bit or 1bytecommands by Function of switchover blinds roller shutter choose curtain type by Object type select the telegram type When the communication object is 1bit send 1 to st...

Page 88: ...ene number 0 63 E g in parameter Number of scene scene number is 1 and the communication object Number of light scene sends scene number 0 55 58 61 Disable input 1 2 3 CH A B C Disable 1 bit C W 1 001 DPT_Switch As above 5 6 5 Temperature limiter underfloor heating Communication Object Figure 5 6 5 NTC communication object Number Object name Functions Data types Flags DPT 54 Floor temperature Exte...

Page 89: ... is ON sending 1 when OFF sending 0 65 Mode heating cooling Temperature control 1 bit C T 1 001 DPT_Switch In Air condition the object is visible when selecting 1 bit in Object type for controlling air condition When heating sending 1 when cooling sending 0 66 Switch to high medium speed Temperature control 1 bit C T 1 001 DPT_Switch In Air condition the object is visible when selecting 1 bit in O...

Reviews: