Overview

The Response Analog IO Gateway supports analog input of external contact closures and/or analog 0-10V 
sources and relay outputs. Using these analog inputs and outputs, you can communicate with and control 
different equipment in your lighting network.

The Analog IO Gateway can be mounted to a standard 35mm DIN rail or can be mounted in a standard 19” 
rack with the optional rack mounting kit. The gateway provides 12 analog inputs and 12 relay outputs for 
your integration options. Power can be provided by either 24VDC or Power over Ethernet (PoE).

Electrical Specifications

• Rated Input Voltage: 12-24VDC, 1A Max, Class 2, Polarity Independent
• Analog Inputs: 24VDC Max, can sense between 0-10V (10V, 100mA utility supply provided)
• Relay Outputs: 30VDC Max, 0.5A Max per contact resistive or contactor load

LED Indicators

• Power: solid blue indicates that power is supplied
• Ethernet: solid green indicates network connection and blinking indicates network activity

Navigation Buttons

• Up, Down, Back, Check Mark/Enter - The check mark allows you to advance to the next available 

menu or commit a modified selection. The back arrow allows you to return to the previous menu or 
option, and the up and down arrows navigate between lines in a menu.

• Reset - The reset button provides a physical reset button.

Installation

You can install the Response Analog Gateway on a DIN rail in a wall- or rack-mounted enclosure.

Summary of Contents for Response Analog IO Gateway

Page 1: ...unted to a standard 35mm DIN rail or can be mounted in a standard 19 rack with the optional rack mounting kit The gateway provides 12 analog inputs and 12 relay outputs for your integration options Power can be provided by either 24VDC or Power over Ethernet PoE Electrical Specifications Rated Input Voltage 12 24VDC 1A Max Class 2 Polarity Independent Analog Inputs 24VDC Max can sense between 0 10...

Page 2: ...s on the top of the gateway and push the screwdriver down to open the clips Insert the screwdriver into the bottom retaining clips and push up to fully release the gateway from the DIN rail Rack Mounted Enclosure If you are installing your Response Analog IO Gateway in a rack refer to the DIN Rail Rack Mount Kit Installation Guide that is shipped with your DIN Rail Rack Mount Kit 4267A1015 Wiring ...

Page 3: ...rformed using the Net3 Concert application available from etcconnect com View Device Information To view information specific to your gateway select the About menu from the home screen From the About menu you can select one of the following three options Version Provides the version of software running on the device Analog Provides information for each of your 12 analog inputs including level sACN...

Page 4: ...he software directly from the gateway If you do choose to update directly from the gateway the bootloader runs and the latest software is downloaded from the server indicated by the IP address on the Update Software screen If you need to modify this IP address you can configure it in the Net3 Concert application using the Update Server property Connect to the Eos Family Console You can configure y...

Reviews: