background image

F-PRO

Feeder Protection Relay

Model 5100

User Manual

Version 4.0 Rev 0

Summary of Contents for F-PRO 5100

Page 1: ...F PRO Feeder Protection Relay Model 5100 User Manual Version 4 0 Rev 0...

Page 2: ......

Page 3: ...rect or consequential damages arising from the use of this documentation While all information presented is believed to be reliable and in accordance with accepted engineering practices ERLPhase makes...

Page 4: ......

Page 5: ...2 5 Setting the Baud Rate 2 7 Accessing the Relay s SCADA Services 2 8 Communication Port Details 2 9 Maintenance Menu 2 12 Firmware Update 2 13 3 Using the IED Getting Started 3 1 Start up Sequence...

Page 6: ...Element Operating Time Curves at Nominal Frequency A 4 Frequency Element Operating Time Curves A 5 Appendix B IED Settings and Ranges B 1 Appendix C Hardware Description C 1 Appendix D Event Messages...

Page 7: ...tions to denote special information Example Describes Start Settings Control Panel Choose the Control Panel submenu in the Set tings submenu on the Start menu Right click Click the right mouse button...

Page 8: ......

Page 9: ...and edit older setting file versions Minor releases designated with a letter suffix e g v3 1a maintain the same compatibility as their base version For example F PRO firmware v3 1c and Offliner Settin...

Page 10: ......

Page 11: ...Offline Mode Settings Software Online Mode Terminal Mode F PRO Feeder Protection Model 5100 Port 1 Date Time View Readings View Logs Prev Next Target Clear Target 1999 JUN 07 Relay Functional IRIG B...

Page 12: ...to address special protection needs Ten ProLogic statements are provided Breaker Logic Group Logic Demand Metering Analog Inputs 4 Analog Voltages 1 Three phase Input 1 Single phase Input 6 Analog Cu...

Page 13: ...217 218 219 220 221 222 223 224 226 227 228 229 230 225 External Inputs 100 101 102 103 104 105 106 107 108 109 110 112 111 113 114 115 116 117 234 235 Port 4 Unused Port 3 SCADA IRIG B 1 2 3 4 5 6 9...

Page 14: ...The F PRO relay has 12 output relay contacts Each contact is programmable and has breaker tripping capability All output contacts are isolated from each other The output contacts are closed for a mini...

Page 15: ...ou must connect the relay to the station ground using the rear grounding terminal on the relay Ground the relay even when testing Do not rely on the rack mounting screws to provide case grounding IRIG...

Page 16: ...Communications Equipment DCE devices with female DB9 connec tors This allows them to be connected directly to a PC serial port with a stan dard straight through male to female serial cable for pin ou...

Page 17: ...n the relay and your computer using an external modem Connect the serial port on the external modem to the Port 2 on the relay s back panel Both devices are configured as RS 232 DCE devices with femal...

Page 18: ...nternal modem is installed The factory defaults are M0S0 0 B1 for an external modem and M0S0 0 for an internal modem Network Link PC with TCP IP Port 5 RJ 45 Network 10BaseT TCP IP Network F PRO Feede...

Page 19: ...ws VT 100 terminal program on your PC for use with the relay The computer must be connected to the relay by one of its serial modem or Ethernet communication ports for details see Communicating with t...

Page 20: ...t of the PC Ending a User Interface Session Use the Quit function in the relay s user menu to end a session This will close the interface and require the next user to log in to the relay The relay aut...

Page 21: ...ge New communications settings loaded will appear The new baud rate will be used on that port the next time you log in to it To change the baud rate on your computer s serial port 1 From within HyperT...

Page 22: ...nd in the Appendices Modbus RTU Communication Protocol in Appendix E and DNP3 Communication Protocol in Appendix F respectively Protocol Selection To select the desired SCADA protocol login to the rel...

Page 23: ...ional ERLPhase Modem Adapter converts this port to a Data Termi nal Equipment DTE to simplify connection to an external modem Default Setting 9 600 baud 8 data bits no parity 1 stop bit Port 2 is disa...

Page 24: ...No connection 9 2 Setup and Communications 2 10 F PRO 5100 User Manual D02416R04 00 Notes Relay is DCE PC is DTE Pins 1 and 6 are tied together internal to the relay Male DB 9 Cable End for Relay Por...

Page 25: ...m Adapter DCD 1 RxD 2 TxD 3 DTR 4 Common 5 DSR 6 RTS 7 CTS 8 No connection 9 2 Setup and Communications D02416R04 00 F PRO 5100 User Manual 2 11 Notes Relay with modem adapter is DTE modem is DCE Pins...

Page 26: ...t serial or modem connection 1 Use the terminal program to connect to the serial port either through direct serial link or modem 2 Select Enter the relay responds with a login prompt Figure 2 5 Login...

Page 27: ...up View network statistics View IP TCP and UDP statistics when equipped with inter nal 10BaseT Ethernet card Monitor SCADA Shows real time display of SCADA data Enable disable Modem Enables or disable...

Page 28: ......

Page 29: ...following initialization sequence takes place Test Mode red LED on 2 seconds after power applied Relay Functional green LED on 5 seconds after power applied Front Display on 30 seconds after power ap...

Page 30: ...e contact changes to an open and the protective functions become functional IRIG B Functional Indicates the presence of a valid IRIG B time signal Service Required Indicates the relay needs service Th...

Page 31: ...ils see Display on page 3 4 Previous Next Scroll through the menu by pressing Previous and Next Clear Target When a fault takes place the red target light appears You can select a setting option to re...

Page 32: ...ngs View Logs Pri V 0 0 KV ph ph I 0 0 A line 2000Jun28 19 34 31 331 50LS 1 Main ABC Trip Figure 3 2 Line Display Examples Line Display Messages PRI V I P Q Va Ia magnitude and angle Vb Ib magnitude a...

Page 33: ...l mode program appears on your screen the following prompt should appear If it doesn t appear press Enter 4 If login is successful the Main Menu appears as follows for view change or service login for...

Page 34: ...Authorized functions view view lowest View settings on line readings and logs and to list and upload records At this level you cannot affect the operation of the controller change change middle Do all...

Page 35: ...vel through the Access menu minimizing the chance that a password is changed casually and provides a means of resolving situations where a password has been forgotten The following rules are applied w...

Page 36: ...previous menu level The menu tree consists of a series of sub menus for details see Figure 3 3 Terminal Mode Menus for view change and service login on page 3 9 The Enter key allows you to toggle thro...

Page 37: ...1 50LS 50BF 25 27 59 Sync Check 79 Output Matrix 2 50 51 50N 51N 46 50 46 51 Output Matrix 3 32 27 59 60 81 THD Aux Fail Output Matrix 4 External Inputs Output Matrix 5 ProLogic Output Matrix 6 BkrLog...

Page 38: ...3 Using the IED Getting Started 3 10 F PRO 5100 User Manual D02416R04 00 Figure 3 4 Terminal Mode Menu for Breaker login Figure 3 5 Terminal Mode Menus for secadmin login...

Page 39: ...unctions When these settings are made or changed you can load them into the relay Allows input of all settings information Settings submenus Identification F PRO System Parameters Setting Group 1 to 8...

Page 40: ...erial number into the F PRO Serial No box in the Identification tab display area of Offlin er Settings Alternately you may check the Ignore Serial Number check box to bypass serial number supervision...

Page 41: ...by Hyper Terminal if the record already exists in the downloads folder When using HyperTerminal use Z modem no crash recovery files are received and auto incremented Delete Records from the Relay To d...

Page 42: ...ciated relay functions Requires service access level Control Virtual Inputs set re set and pulse virtual inputs Pulse width is 1 second Latched virtual inputs reset after pulse command has executed R...

Page 43: ...ker Log Metering Reset Quit Breaker Log The breaker log provides a log of breaker monitoring events Metering The metering quantities provided are breaker logic and I I t For an explana tion of those q...

Page 44: ...isabled UDP UDP protocol is used for communication with Syslog server IP Address parameter defines Syslog server IP Address Port parameter defines Syslog server IP port for receiving Syslog messages H...

Page 45: ...L voltage positive sequence line current real and reactive power positive sequence voltage frequency THD power factor and 3IO current All values are in primary quantities These are also available from...

Page 46: ...ip states of all the relay elements Logic ProLogic Displays the status of all ProLogic Logic Setting Groups Displays the current active setting group as well as the current state of all the group logi...

Page 47: ...inputs are applied to the relay from ring bus breakers this current is summated to represent the total line current and is used with this overcurrent function You can set directional control of 50 51...

Page 48: ...00 to 99 99 non directional 51 Enable disable Directional Forward reverse non directional Pickup 0 25 to 50 00 5 A 0 05 to 10 00 1 A Curve Type For details see IEC and IEEE Curves on page 4 1 TMS 0 0...

Page 49: ...he characteristic of the overcurrent function can be rescaled by clicking on the characteristics using the right mouse key and by making a box around the area of interest The characteristic can be pri...

Page 50: ...kup For I2 pickup T I2 TMS B A I2 Pickup p 1 T I2 TMS TR I2 Pickup 2 1 46 50 46 51N Negative Sequence Overcurrent 46 50 Enable disable Directional Forward reverse non directional Pickup 0 25 to 50 0 5...

Page 51: ...to 0 0 for a instantaneous trip Auxiliary definite time delay functions are available to monitor main and aux iliary CT currents 50 IMainA 50 IMainB 50 IMainC T O 100 50LS 1 Main 101 50 IMainA 50 IMa...

Page 52: ...ip coil or the next level of breakers such as bus breakers The breaker failure protection logic diagram is shown below Phase current supervision is fixed at 4 of I nominal and is shown for a 5 A relay...

Page 53: ...ation voltage signals Figure 4 5 Effect of the Ring Filter on page 4 7 and Ipos is the positive sequence line current Ring Filter Va Va_polarization Ring Filter Vb Vb_polarization Ring Filter Vc Vc_po...

Page 54: ...o to zero directional control are maintained because the positive sequence volt age does not go to zero 25 27 59 Sync Check The relay can bring in voltages from both line and bus PTs The Sync Check fu...

Page 55: ...t until the feeder returns to normal by manual op eration i e The feeder has been on with a load greater than the low set setting for a certain amount of time 79Main and 79Aux are identical except the...

Page 56: ...04 00 59 Overvoltage The F PRO has a definite time delay main overvoltage function This function looks at all three phase to neutral voltages to determine an overvoltage condi tion The logic gate can...

Page 57: ...ntaneous trip 27 Va Main 27 Vb Main 27 Vc Main T O OR Gate Switch Setting AND Figure 4 9 27 Undervoltage 27 Undervoltage 27 1 Enable disable Gate Switch AND or OR Pickup 1 0 to 120 0 volts Pickup Dela...

Page 58: ...vel T O df dt Hz s Figure 4 12 Frequency Rate of Change 81 Over Under Frequency 81 1 Disabled Fixed Level Rate of Change Pickup 50 000 to 59 995 or 60 005 to 70 000 fixed level 10 0 to 0 1 or 0 1 to 1...

Page 59: ...1P Phase Distance The relay has two mho phase distance elements Each element includes a for ward reach and delta current supervisor setting The element output is only available as a ProLogic 21 Phase...

Page 60: ...l statement The possible gates are AND NAND OR NOR XOR NXOR and LATCH The control can be time delay pickup and or time delay dropout and can drive the front panel target LED Ten ProLogic control state...

Page 61: ...reset all associated breaker monitoring values from the terminal SCADA interfaces Breaker Logic The Breaker Logic function is similar to a ProLogic function but includes some additional features spec...

Page 62: ...t I2 t function will only be available in the event log the output is not available in the output matrix or in the Pro Logic input list The terminal UI and SCADA interfaces will show the accumulated v...

Page 63: ...Hz THD in You can select from three calculation types integrating rolling and thermal They are described in detail below Figure 4 16 Integrating Demand Meter Integrating demand meter is a linear avera...

Page 64: ...called sliding window is a process by which intervals are divided into a fixed number of subintervals Instead of calculating demand only at the end of each interval the calculation is performed at th...

Page 65: ...when the elapsed time is equal to the Demand Interval 5 minutes for this example The thermal demand will reach 99 of the input when the time is twice of the demand interval as shown in the table belo...

Page 66: ...our accumulated energy quantities They are 3 Phase real energy OUT MWh 3 Phase real energy IN MWh 3 Phase reactive energy OUT MVARh 3 Phase reactive energy IN MVARh The accumulated energy quantities a...

Page 67: ...s with Boolean statements one latch state and one pickup delay timer The active setting group ASG is viewed from the Terminal Mode the front panel or from a re cord stored by the relay the active sett...

Page 68: ...group To view a snapshot of the group logic data select F2 prior to making any modifi cation to the Active Setting Group input The following is the flow of events that can occur in the Active Group S...

Page 69: ...n the Editing Settings Screen Edit Settings Access Level Change or Service View F3 Quit Enter view System opens Copy SG Screen Exit CR or Space System updates Copy SG x to SG y and waits for User I P...

Page 70: ...that can occur in the Load Settings Screen Load Settings Access Level Change or Service View System opens Load Setting Screen Confirm Setting Load Yes Yes No System Saves all Changes SG to Activate Y...

Page 71: ...ged to show completion of the request There is some lag time during the load request and the completion of the re quest where the interface processor associates ancillary functions with the pre vious...

Page 72: ...P Q Ener gy V I Freq and THD of the feeder with an adjustable sample period from 5 to 60 minutes per sample This same global trend sampling rate is applied to all the trend quantities The relay store...

Page 73: ...bled an event record is created approximately every 230 events A recording can also be initiated manually through the terminal user interface The command Initiate Event Recording is available under th...

Page 74: ...elay Logging Functions Event Log The F PRO maintains a log of events in a 250 entry circular log Each entry contains the time of the event plus an event description Logged events include trips alarms...

Page 75: ...ovides an easy way to view and manipulate settings PC System Requirements Hardware The minimum hardware requirements are 1 GHz processor 2 GB RAM 20 GB available hard disk space USB port Serial commun...

Page 76: ...ti spyware Software If an anti virus anti spyware software on your local system identifies any of the ERLPhase applications as a potential threat it will be necessary to con figure your anti virus ant...

Page 77: ...a small box around the graph area When you release the mouse the trace assumes a new Zoom position determined by the area of the zoom coordinates To undo the zoom on the graph click the Refresh button...

Page 78: ...the new setting file When the conversion is complete Offliner Settings dis plays the new file Figure 5 3 Converting Setting Files Sending a New Setting File to the Relay 1 Make sure the settings versi...

Page 79: ...liner Settings 2 Open a sample file of the desired version Use File Save As to save the sam ple file to a new file name Then edit the setting file and the serial number save it and load it into the re...

Page 80: ...A Figure 5 5 Identification Identification Settings Version Indicates the settings version number fixed Ignore Serial Number Bypass serial number check if enabled Serial Number Available at back of e...

Page 81: ...ter you can choose to ignore the serial number enforcement in the identification screen The relay only checks for proper relay type and setting version if the ignore serial number has been chosen requ...

Page 82: ...External Inputs screen allows you to define meaningful names for nine ex ternal inputs External Input Names 1 to 9 User defined Output Contacts Figure 5 8 Output Contacts The Output Contact Names scre...

Page 83: ...nputs are individually controlled and include a set reset and pulse function The latch state is retained during setting changes and relay power down conditions The 30 virtual inputs conform to DNP3 st...

Page 84: ...e 5 10 F PRO 5100 User Manual D02416R04 00 Setting Groups Figure 5 10 Setting Groups The Setting Group Names screen allows you to define meaningful names to the 8 setting groups Setting Groups Setting...

Page 85: ...ACB CT Turns Ratio Ring Bus Configuration Aux CT Line Input Enable disable Main CT Turns Ratio 1 0 to 10000 0 Aux CT Turns Ratio 1 0 to 10000 0 PT Turns Ratio Main PT Turns Ratio 1 0 to 10000 0 Sync...

Page 86: ...elay If en abled the currents from the two sets of CTs are added to the relay to form the line current F PRO uses ac volts from the main PTs for its protections and for the metering functions A single...

Page 87: ...ith the following exceptions the sole function is to activate one of the eight setting groups and the processing is in a slower half second cycle Group Logic inputs statements can be driven from ProLo...

Page 88: ...criptions of the protection functions see Protection Functions and Specifications on page 4 1 Demand Trend Metering Figure 5 15 Demand Trend Metering Demand Trend Metering Demand Trend Metering Enable...

Page 89: ...igure 5 16 I I t I I t Main Enable disable External Input or ProLogic for Trip Disable or External Input or ProLogic I I t Limit 0 1 to 99999 0 KA 2 s Aux Enable disable External Input or ProLogic for...

Page 90: ...input A by selecting any of the relay functions using the list for up to 5 possible inputs Put these inputs into AND OR NAND NOR and exclusive logics and latches by clicking on the gate In vert the in...

Page 91: ...initiating condition does not last at least 0 5 seconds Figure 5 19 Group Logic Output Matrix Figure 5 20 Output Matrix 1 The output contact matrix determines which function initiates which output re...

Page 92: ...nt the entire output matrix by selecting File Print Summary This printout is produced on two pages Settings Summary Figure 5 21 Settings Summary Select Settings Summary to view and print the relay set...

Page 93: ...ill automatically launch F PRO Offliner to display the settings in summary form If the record contains Setting Groups the Offliner displays all Setting Groups in the summary Bold text in the tree view...

Page 94: ......

Page 95: ...en it leaves the factory but if component changes are made within the relay you may need to do a re calibration Establish the accuracy of equipment used to calibrate the relay be fore a new calibratio...

Page 96: ...ty by your relay Therefore if it is absent there is not a locked valid relationship among all of the analog quanti ties Testing the External Inputs To test the external inputs the relay is connected t...

Page 97: ...tic Drawing in Appendix I and DC Schematic Drawing in Appendix J Communication Wiring EIA 232 All of the relay s serial ports Ports 1 2 and 3 are configured as EIA RS 232 Data Communications Equipment...

Page 98: ......

Page 99: ...acters Password may contain Lower case letters a z Upper case letters A Z Numeric characters 0 9 Special characters as follows Table 8 1 Special Characters Character ASCII Decimal Description 033 Excl...

Page 100: ...7 un successful login attempts Lock out of one Access Level does not affect avail ability of the others Authorization by Access Level Each Access Level is assigned a set of functions authorized for i...

Page 101: ...ivities Table 8 2 Cyber Security Activity Types Activity Message ID Description Access to IED resources ACCS Access to the configuration settings records files and control data Authentication AUTH Use...

Page 102: ...e data 8 optional description Message priority Message priority defines message relative importance The lower the priority value the more important critical is the message The list of message priori t...

Page 103: ...vailable in the Syslog Configu ration menu Figure 8 1 Figure 8 2 and Figure 8 3 below illustrate relationship between Syslog Configuration menu selection and Host Name field Figure 8 1 Unit IP Address...

Page 104: ...trol TimeSettings 46483 1 ACCS IED Time Settings change Calibration 46483 1 ACCS IED Calibration Settings change SysArchive 46483 1 ACCS Access to IED System Archive Event 46483 1 SYST IED System Even...

Page 105: ...face access 20000 Enabled disabled TCP UDP DNP3 DNP3 communication Port number is configurable Port is disabled if DNP3 SCADA communication over Ethernet is disabled 514 Enabled disabled UDP Syslog Sy...

Page 106: ...functions Exception 5 1 6 a View data Comply 5 1 6 b View configuration settings Comply 5 1 6 c Force values Comply 5 1 6 d Configuration change Comply 5 1 6 e Firmware change Comply 5 1 6 f ID passwo...

Page 107: ...s and Alarms is available via Syslog protocol in compli ance with RFC 5424 and RFC 5426 standards 5 3 2 Events Comply 5 3 3 Alarms Exception 5 3 3 a Unsuccessful login attempt Comply 5 3 3 b Reboot Co...

Page 108: ...t supported 5 4 3 Cryptographic techniques Exception Not supported 5 4 4 Encrypting serial communications Exception Not supported 5 4 5 Protocol specific security features Comply 5 5 IED configuration...

Page 109: ...put channels Capacity up to 15 x 2 second records Records up to the 25th harmonic Viewing software provides waveform symmetrical components and harmonic analysis Trend MW In and Out MVAR In and Out I...

Page 110: ...or Ethernet or Modbus RS 232 Rear port Time Sync IRIG B BNC connector Modulated or unmodulated auto detect Self Checking Relay Inoperative 1 contact Closed when relay inoperative Terminal User Interfa...

Page 111: ...5 of inputs from 0 1 to 1 0 x nominal current In 1 0 of inputs from 1 0 to 20 0 x nominal current In Voltage 1 0 of inputs from 0 01 to 2 00 x nominal voltage Vn Impedance 5 0 of set value from 0 05...

Page 112: ...t operate time Faults were applied at a location representing a percentage of the Zone 1 relay reach setting Tests were performed for source impedance ratios SIR of 0 1 1 0 10 0 and 30 0 No pre trigge...

Page 113: ...change settings The diagrams show operating times at each test point including output contact operate time Operating times are the same for both 50 Hz and 60 Hz Time Delay Error 0 2s 0 15 30 45 60 75...

Page 114: ...90 105 120 135 150 165 180 195 0 1 2 3 4 5 6 7 8 9 10 11 Multiple of Hz s Pickup Time Delay Error ms 0 1 Hz s 1 Hz s Appendix A IED Specifications Appendix A 6 F PRO 5100 User Manual D02416R04 00 Figu...

Page 115: ...mmary provides a list of all the current and voltage analog input quantity names used for line protection and used for recording External Inputs and Output contact names are also identified on this su...

Page 116: ...re 3 Output 4 Spare 4 Output 5 Spare 5 Output 6 Spare 6 Output 7 Spare 7 Output 8 Spare 8 Output 9 Spare 9 Output 10 Spare 10 Output 11 Spare 11 Output 12 Spare 12 Virtual Input Names VI 1 Virtual Inp...

Page 117: ...Setting Group 1 Setting Group 1 Setting Group 2 Setting Group 2 Setting Group 3 Setting Group 3 Setting Group 4 Setting Group 4 Setting Group 5 Setting Group 5 Setting Group 6 Setting Group 6 Setting...

Page 118: ...0 Zero Sequence Angle 70 0 degrees 25 0 to 89 0 Protection Functions 50LS 1 Main Enabled 50LS 1 Aux Enabled 50LS 2 Main Enabled 50LS 2 Aux Enabled 50BF Main Enabled 50BF Aux Disabled 50 Enabled 51 Ena...

Page 119: ...0 seconds 0 00 to 99 99 50LS 2 Aux Enabled Gate Switch OR Pickup 10 0 amperes 0 1 to 50 0 Pickup Delay 0 00 seconds 0 00 to 99 99 50BF Breaker Failure 50BF Main Enabled Pickup Delay 1 0 50 seconds 0 0...

Page 120: ...d Directional Control forward Pickup 10 00 amperes 0 25 to 50 00 Curve Type IEC very inverse TMS 0 50 0 01 to 10 00 A 13 5 B 0 0 p 1 0 TR 21 60 Initiate Fault Location Enabled ProLogic Control Disable...

Page 121: ...eclose T4 20 00 seconds 1 00 to 99 99 Close Time Tp 0 20 seconds 0 01 to 1 00 Lockout Reset Td 25 00 seconds 0 00 to 99 99 Initiate Reset TDI 1 00 seconds 0 00 to 99 99 Block Reset TDB 0 50 seconds 0...

Page 122: ...ntial Alarm 60 Enabled 81 Over Under Frequency 81 1 Disabled Pickup 60 005 Hz 50 000 59 995 or 60 005 70 000 Pickup Delay 2 00 seconds 0 05 to 99 99 81 2 Disabled Pickup 60 005 Hz 50 000 59 995 or 60...

Page 123: ...0 to 100 0 Demand Metering Demand Metering Disabled Demand Interval 5 minutes 5 to 60 Demand Meter Type Integrating I I t I I t Main Disabled External Input or ProLogic for Trip disabled I I t Limit...

Page 124: ...rator 5 Input E Unused 0 PL 3 ProLogic 3 ProLogic 3 Disabled Target Enabled Pickup Delay 0 00 seconds 0 00 to 999 00 Dropout Delay 0 00 seconds 0 00 to 999 00 Operator 1 Input A Unused 0 Operator 2 In...

Page 125: ...0 00 to 999 00 Operator 1 Input A Unused 0 Operator 2 Input B Unused 0 Operator 3 Input C Unused 0 Operator 4 Input D Unused 0 Operator 5 Input E Unused 0 PL 6 ProLogic 6 ProLogic 6 Disabled Target E...

Page 126: ...E Unused 0 PL 8 ProLogic 8 ProLogic 8 Disabled Target Enabled Pickup Delay 0 00 seconds 0 00 to 999 00 Dropout Delay 0 00 seconds 0 00 to 999 00 Operator 1 Input A Unused 0 Operator 2 Input B Unused 0...

Page 127: ...perator 5 Input E Unused 0 Breaker Logic 1 BkrLogic 1 BkrLogic 1 Disabled Alarm LED Enabled Message Parameter none Count Limit 0 0 to 99999 Pickup Delay T1 0 00 seconds 0 00 to 999 00 Drop Out Delay T...

Page 128: ...seconds 0 00 to 999 00 Pickup Delay T3 0 00 seconds 0 00 to 999 00 Drop Out Delay T3 0 00 seconds 0 00 to 999 00 Pickup Delay T4 0 00 seconds 0 00 to 999 00 Drop Out Delay T4 0 00 seconds 0 00 to 999...

Page 129: ...gic 4 BkrLogic 4 BkrLogic 4 Disabled Alarm LED Enabled Message Parameter none Count Limit 0 0 to 99999 Pickup Delay T1 0 00 seconds 0 00 to 999 00 Drop Out Delay T1 0 00 seconds 0 00 to 999 00 Pickup...

Page 130: ...0 00 to 999 00 Operator 1 Input A Unused 0 Operator 2 Input B Unused 0 Operator 3 Input C Unused 0 Operator 4 Input D Unused 0 Operator 5 Input E Unused 0 Breaker Logic 6 BkrLogic 6 BkrLogic 6 Disabl...

Page 131: ...to 999 00 Drop Out Delay T2 0 00 seconds 0 00 to 999 00 Pickup Delay T3 0 00 seconds 0 00 to 999 00 Drop Out Delay T3 0 00 seconds 0 00 to 999 00 Pickup Delay T4 0 00 seconds 0 00 to 999 00 Drop Out D...

Page 132: ...5 Input E Unused 0 Breaker Logic 9 BkrLogic 9 BkrLogic 9 Disabled Alarm LED Enabled Message Parameter none Count Limit 0 0 to 99999 Pickup Delay T1 0 00 seconds 0 00 to 999 00 Drop Out Delay T1 0 00 s...

Page 133: ...99 00 Drop Out Delay T3 0 00 seconds 0 00 to 999 00 Pickup Delay T4 0 00 seconds 0 00 to 999 00 Drop Out Delay T4 0 00 seconds 0 00 to 999 00 Operator 1 Input A Unused 0 Operator 2 Input B Unused 0 Op...

Page 134: ...up Logic 3 Group Logic 3 Group Logic 3 Disabled Setting Group to Activate none Pickup Delay 0 00 seconds 0 00 to 999 00 Operator 1 Input A Unused 0 Operator 2 Input B Unused 0 Operator 3 Input C Unuse...

Page 135: ...rator 4 Input D Unused 0 Operator 5 Input E Unused 0 Group Logic 6 Group Logic 6 Group Logic 6 Disabled Setting Group to Activate none Pickup Delay 0 00 seconds 0 00 to 999 00 Operator 1 Input A Unuse...

Page 136: ...r 1 Input A Unused 0 Operator 2 Input B Unused 0 Operator 3 Input C Unused 0 Operator 4 Input D Unused 0 Operator 5 Input E Unused 0 Group Logic 9 Group Logic 9 Group Logic 9 Disabled Setting Group to...

Page 137: ...11 Disabled Setting Group to Activate none Pickup Delay 0 00 seconds 0 00 to 999 00 Operator 1 Input A Unused 0 Operator 2 Input B Unused 0 Operator 3 Input C Unused 0 Operator 4 Input D Unused 0 Oper...

Page 138: ...tor 5 Input E Unused 0 Group Logic 14 Group Logic 14 Group Logic 14 Disabled Setting Group to Activate none Pickup Delay 0 00 seconds 0 00 to 999 00 Operator 1 Input A Unused 0 Operator 2 Input B Unus...

Page 139: ...Group Logic 16 Group Logic 16 Group Logic 16 Disabled Setting Group to Activate none Pickup Delay 0 00 seconds 0 00 to 999 00 Operator 1 Input A Unused 0 Operator 2 Input B Unused 0 Operator 3 Input...

Page 140: ......

Page 141: ...nput Board The AC Analog Input Board has 6 current transformer inputs and 4 potential transformer inputs On board anti aliasing filters provide accurate and secure digitization of the ac input signals...

Page 142: ...h disk on the CPU board provides the operat ing software for the 486 and stores the relay s recordings Front Panel Board The Front Panel Board provides visual indication of the status of the relay an...

Page 143: ...34 5km Trip 51 ABC 1234 5km Trip 51N 1234 5km Alarm Fault Location will be included if enabled 50N 1234 5km Trip 51N 1234 5km Trip 46 51 1234 5km Alarm 46 50 1234 5km Trip 46 51 1234 5km Trip 252759 S...

Page 144: ...ames are user assigned Where msgParam count limit Where n 1 10 BkrLogic Name Input Reset msgParam BLn I I t Main Limit 99999 0 I I t Aux Limit 99999 0 MWh IN Count Rollover Reset 9800 MWh OUT Count Ro...

Page 145: ...Y INOPERATIVE on the rear panel closes to activate a remote alarm The watch dog repeatedly attempts to re start the DSP for diagnostic purposes The green light stays off and the relays remain de energ...

Page 146: ......

Page 147: ...6 0 Contact Open inactive 1 Contact Closed active Output Contact 5 517 0 Contact Open inactive 1 Contact Closed active Output Contact 6 518 0 Contact Open inactive 1 Contact Closed active Output Conta...

Page 148: ...796 0 Off inactive 1 On active 81 2 Trip 797 0 Off inactive 1 On active 81 3 Trip 798 0 Off inactive 1 On active 81 4 Trip 799 0 Off inactive 1 On active THD Alarm 800 0 Off inactive 1 On active Auxil...

Page 149: ...e Group Logic 7 833 0 Off inactive 1 On active Group Logic 8 834 0 Off inactive 1 On active Group Logic 9 835 0 Off inactive 1 On active Group Logic 10 836 0 Off inactive 1 On active Group Logic 11 83...

Page 150: ...10521 0 Off inactive 1 On active Virtual Input 10 10522 0 Off inactive 1 On active Virtual Input 11 10523 0 Off inactive 1 On active Virtual Input 12 10524 0 Off inactive 1 On active Virtual Input 13...

Page 151: ...1 Years since 1900 40013 90 137 1 Sync d to IRIG B 40014 0 No 1 Yes 1 Milliseconds Now 40015 2 s complement half hours North America is negative 1 Channel Address Units Scale Main Va Magnitude 40257...

Page 152: ...and Real Power Out 40290 MW 10 Demand Real Power In 40291 MW 10 Demand Reactive Power In 40292 MVAR 10 Demand Reactive Power Out 40293 MVAR 10 Demand A Phase Voltage 40294 kV 10 Demand B Phase Voltage...

Page 153: ...nual Appendix E 7 BkrLogic 7 Count 40312 1 BkrLogic 8 Count 40313 1 BkrLogic 9 Count 40314 1 BkrLogic 10 Count 40315 1 I2t Main Accumulated 40316 1 I2 t Main for last operation 40317 10 I2t Aux Accumu...

Page 154: ...s active Energy Reset 257 Reset Breaker Logic 1 258 Reset Breaker Logic 2 259 Reset Breaker Logic 3 260 Reset Breaker Logic 4 261 Reset Breaker Logic 5 262 Reset Breaker Logic 6 263 Reset Breaker Logi...

Page 155: ...s includes fault location information The following controls are available Refresh Event List Function Code 6 address 40513 Fetches the latest events from the F PRO s event log and makes them availabl...

Page 156: ...igh Byte Low Byte 40516 0x00 0x1B Event text size 27 0x1B hex 40517 0x46 0x4C FL Fault locator event 40518 0x32 0x30 2 0 40519 0x30 0x30 0 0 40520 0x53 0x65 S e 40521 0x70 0x32 p 2 40522 0x31 0x20 1 4...

Page 157: ...__Always __Sometimes __Configurable SELECT OPERATE __Never x Always __Sometimes __Configurable DIRECT OPERATE __Never x Always __Sometimes __Configurable DIRECT OPERATE No ACK __Never x Always __Somet...

Page 158: ...tatus default 1 read 0x00 0x01 0x06 0x07 0x08 0x17 0x28 129 response 0x00 12 1 Control Relay Output Block 3 select 4 operate 5 direct op 6 direct op no ack 0x00 0x01 0x07 0x08 0x17 0x18 129 response e...

Page 159: ...e scanned with 1 ms resolution Change Event Buffer Size 100 Name Point Index Change Event Class External Input 1 0 1 External Input 2 1 1 External Input 3 2 1 External Input 4 3 1 External Input 5 4 1...

Page 160: ...F PRO 5100 User Manual D02416R04 00 Object Group 10 12 Object Variation 2 Binary Output Status default 1 Control Relay Output Block Class 0 Not Applicable Note Binary outputs are scanned with 500 ms r...

Page 161: ...Output Contact 10 9 N A Output Contact 11 10 N A Output Contact 12 11 N A 50LS 1 Main Trip 12 N A 50LS 2 Main Trip 13 N A 50LS 1 Aux Trip 14 N A 50LS 2 Aux Trip 15 N A 50BF 1 Main Trip 16 N A 50BF 2 M...

Page 162: ...gic 6 50 N A ProLogic 7 51 N A ProLogic 8 52 N A ProLogic 9 53 N A ProLogic 10 54 N A Breaker Logic 1 55 N A Breaker Logic 2 56 N A Breaker Logic 3 57 N A Breaker Logic 4 58 N A Breaker Logic 5 59 N A...

Page 163: ...0 12 Virtual Input 4 89 N A 10 12 Virtual Input 5 90 N A 10 12 Virtual Input 6 91 N A 10 12 Virtual Input 7 92 N A 10 12 Virtual Input 8 93 N A 10 12 Virtual Input 9 94 N A 10 12 Virtual Input 10 95 N...

Page 164: ...12 Reset Breaker Logic 9 127 N A 10 12 Reset Breaker Logic 10 128 N A 10 12 Demand Reset 129 N A 10 12 Peak Demand Reset 130 N A 12 Analog Inputs Obj 30 31 Static Points Change Event Points Object Gr...

Page 165: ...a Ang 13 degrees 10 2 0 5 degrees Aux Ib Mag 14 A 1 2 2 nominal Aux Ib Ang 15 degrees 10 2 0 5 degrees Aux Ic Mag 16 A 1 2 2 nominal Aux Ic Ang 17 degrees 10 2 0 5 degrees Line Ia Mag 18 A 1 2 2 nomin...

Page 166: ...6 0x44 hex Demand Reactive Power In 36 MVAR 10 2 0 5 Demand A phase Voltage 37 kV 10 2 2 nominal Demand B phase Voltage 38 kV 10 2 2 nominal Demand C phase Voltage 39 kV 10 2 2 nominal Demand A phase...

Page 167: ...her of the octet string objects DNP Example Event Message FL2000Sep21 20 16 16 966 50 1 Trip AB 1 0km DNP Octet string object contents 0x46 0x4C 0x32 0x30 0x30 0x30 0x53 0x65 0x70 0x32 0x31 0x20 0x32...

Page 168: ......

Page 169: ...W LOGS VIEW PREVIOUS NEXT TARGET TARGET CLEAR 12 12 Side View 19 00 Top View RELAY FUNCTIONAL IRIG B FUNCTIONAL SERVICE REQUIRED TEST MODE ALARM PORT 1 4 75 0 25 18 31 0 34 17 17 5 25 11 37 5 15 Panel...

Page 170: ...17 19 18 31 5 17 4 75 0 20 Cut Out Template 9 16 9 16 C L Appendix G Mechanical Drawings Appendix G 2 F PRO 5100 User Manual D02416R04 00 Figure G 5 Cut out Template...

Page 171: ...18 100 101 102 103 104 105 106 107 108 109 110 111 112 113 114 115 116 117 125VDC 125VDC 125VDC 125VDC 125VDC 125VDC 125VDC 125VDC 125VDC Case Gnd PORT 2 PORT 3 IRIG B PORT 5 PORT 4 SCADA Unused Direc...

Page 172: ......

Page 173: ...tage input used for sync check main AC voltage inputs used for line protection Line CTs Line Breaker 52 1 IA 1 300 IA 1 301 IB 1 302 IB 1 303 IC 1 304 IC 1 305 IA 2 306 IA 2 307 IB 2 308 IB 2 309 IC 2...

Page 174: ......

Page 175: ...07 209 202 204 206 208 Out10 221 220 Out7 Out6 Out5 213 211 215 Out8 Out9 217 219 Output Relay Contacts 210 212 214 216 218 Out11 Out12 223 225 222 224 Alarm Relay Inoperative 201 200 NC Notes 1 IRIG...

Page 176: ......

Page 177: ...D02416R04 00 F PRO 5100 User Manual Appendix K 1 Appendix K Function Logic Diagram Available on www erlphase com the product CD and in plastic sleeves of printed manuals...

Page 178: ......

Page 179: ...The relay resets all the events that are currently high and reports states of all the events that remain high after a setting change Viewing Active Setting Group To view the active setting group and...

Page 180: ...ge includes the actual clearing time Timer 1 accumulated run time When the final output goes high the run time associated with all the timers is available and can be record ed in the event log The mes...

Page 181: ...t Timer T2 drop out delay is set to one second for creating the desired Alarm pulse width The message parameter setting is used to define the event log message The Alarm LED Enabled setting is used to...

Page 182: ...red Alarm pulse width The message parameter setting is used to define the event log mes sage this example you do not need any additional information to be included with the event message therefore the...

Page 183: ...group one and group two If you wanted to switch through all setting groups group logic two would switch to setting group three and so forth If the contact input to switch setting groups becomes welded...

Page 184: ...t and an external input as qualifiers see example Using ProLogic to Qualify Group Logic Statements on page Appendix L 11 Figure L 17 Group Logic 1 Setting Group 2 Logic Statements When setting group t...

Page 185: ...ee External Inputs to Toggle Setting Group Three external inputs connected to an eight position selector switch The out put contact is used to build a truth table to toggle between eight setting group...

Page 186: ...pecific time delay pickup setting You can also provide two additional logic inputs in each statement to be used to provide qualifiers before switching setting groups We are using a ProLogic statement...

Page 187: ...F PRO 5100 User Manual Appendix L 9 EI 1 low EI 2 high and EI 3 low Figure L 23 Group Logic 14 EI 1 high EI 2 high and EI 3 low Figure L 24 Group Logic 13 EI 1 low EI 2 low and EI 3 high Figure L 25 G...

Page 188: ...PRO 5100 User Manual D02416R04 00 EI 1 high EI 2 low and EI 3 high Figure L 26 Group Logic 11 EI 1 low EI 2 high and EI 3 high Figure L 27 Group Logic 10 EI 1 high EI 2 high and EI 3 high Figure L 28...

Page 189: ...ic inputs to make specific blocking logic to be used as a qualifier for any group logic decisions In this example we use either the 50 or 50N elements to drive the Block Group Logic statement There is...

Page 190: ......

Page 191: ...e 5 4 creating a setting file from an older version 5 5 CT turns ratio 5 12 D date time 3 3 demand 3 10 demand trend metering 5 14 diagnostics 3 12 E erase 3 12 event log 3 11 4 28 external inputs 3 9...

Page 192: ...SCADA 3 12 sending a new setting file 5 4 service 3 13 service required 3 2 setting groups 3 9 3 11 5 10 5 13 L 5 Settings 5 18 settings 3 9 settings summary 5 18 setup 3 12 start up 3 1 system param...

Reviews: