Operating instruction 

Temperature Controls Series TS1 

 

 

 

Emerson Climate Technologies GmbH  

www.emersonclimate.eu

 

Am Borsigturm 31 I 13507 Berlin I Germany 

Date: 21.06.2016 

TS1_OI_ML_R08_0715182.docx 

For application in refrigeration systems and heat 
pumps.

 

Technical data: 

 

Protection class:   IP44 (IEC 529/EN 60529) 
 

 

IP30 with Off-Switch 

 

Ambient temperature (housing): 

  -50 .. +70°C 

 

Storage / transportation temperature:    -50 .. +70°C 

 

Temperature sensing range:  

  -55 .. +180°C 

 

Max. bulb temperature: 

see product label

 

 

Vibration resistance: 4g (10...1000 Hz) 

 

Electrical rating 
 

Heating load (AC1): 

    24A / 230V AC 

 

Inductive load (AC15):      10A / 230V AC 

 

Inductive load (DC13):      0.1A / 230V DC 

 

 

 

 

    3A / 24V DC 

 

Start-up (AC3): 

 

144A / 230V AC 

 

Motor rating (FLA): 

24A / 120/240V AC 

 

Locked rotor (LRA):  144A / 120/240V AC 

 

Dimensions 

width x height x depth (mm) 

  TS1-A/B/C/D/E/F/R 

86 x 75 x 44 

  TS1-G/H (flush mounting) see fig. 2b: 
   

cut-out: 

85 x 39 x 73 

   

front cover (mm): 

 106 x 44 

 

all dimensions without reset button,  adjustment  

  spindles, off-switch and temperature sensors 
 

Type code: 
 

TS1 - 

 

 

 

e.g. TS1-A 4 F

 

 

 

Function 

 

A =  Wall mounting, top adjustment 

 

B = 

as A

 plus off-switch 

 

C =  Frost monitor, auto reset 

 

D =  Frost monitor, manual reset 

 

E =  Wall mounting, front adjustment 

 

F =  

as E

  plus off-switch 

 

G =  flush mounting 

 

H = 

as H  

plus off-switch 

 

R =  Wall mounting, top adjustmnet, manual reset 

 

NOTE: Function types D, R   with Temperature  

 

Ranges 0…4 have a manual reset for falling 

 

 

temperature, with Ranges 5 – 9 for rising temp. 

 

 

 

Temperature range

 

 

ranges 0 … 9 

 

refer to product label or catalogue data 

 

 

Temperature sensor type 

 

A =  Vapour charge, 2 m, capillary 

 

E =  Vapour charge, 0 m, coil 

 

F =  Adsorption charge, 2 m, bulb 

 

P =  Vapour charge, 2 m capillary 

 

 

(frost monitors 

Function C/D:

 6 m) 

 

  

Safety instructions:

 

 

 

Read installation instructions thoroughly. 
Failure to comply can result in device failure, 
system damage or personal injury. 

 

It is intended for use by persons having the 
appropriate knowledge and skill.  

 

Ensure supply voltage and current of electric 
device match rating on TS1 name plate. 
Disconnect supply voltage from system and TS1 
before installation or service.

 

 

Do not exceed max. bulb temperature. 

 

Keep temperatures within nominal limits.  

 

Function/Type of switch (Fig. 1): 

  Fig. 1a: Automatic reset function 
  Fig. 1b: Manual reset function for low temp. reset 
  Fig. 1c: Manual reset function for high temp. reset 
  Fig. 1d: Bellows heater 82 k

, 230V AC/DC 

    on devices with temperature sensor type A, E 
  Fig. 1e: Off-switch, function types B, F, H 

 

TS1 temperature switches are equipped with a SPDT 
snap action contact switching from 1-2 to 1-4 on 
rising and from 1-4 to 1-2 on falling temperature. 
Reaching the preset switch point on rising 
temperature, contact 1-2 breaks while contact 1-4 
makes and vice versa on falling temperature. 

 

TS1 with manual reset: 

Reaching the preset switching point contact 1-4 
breaks (low temp. switch) or contact 1-2 makes 
(high temp. switch) and locks in this position. After 
the temperature has risen or dropped by a fixed 
differential,

 

the switch can be reset by pushing the 

reset button. 

 

TS1 with manual reset are “trip-free”. 

Mounting (Fig. 2a; all models except TS1-
G/H): 

 

TS1 controls may be installed by using a mounting 
plate or as a wall-mounted device against a flat 
surface. 

 

For wall-mounted devices, the insulating console 
supplied with controls with sensor type “E” 
must be installed between wall and control to 
ensure proper operation. 

 

For devices with vapour charges “A” and “P” an 
insulating console or other  insulating material 
must be used if the wall temperature is close to 
the application temperature to be sensed. 

 

Use universal thread M4 or UNC8-32 mounting 
holes for installation via mounting plate. 

 

Use the standard mounting holes at the backside for 
wall mounting. 

 

Use mounting screws supplied with control. 

 

Mounting screws must not penetrate control 
backside by more than 8 mm to ensure proper 
operation. 

 

In order to achieve protection class IP44, the 
following instructions must be observed: 

 

Cover must be closed and cover screw fastened. 

 

Control must be mounted against a flat surface 
so that all openings on the housing backside are 
fully covered. 

Mounting direction: 

Any direction except upside 

down. 

Mounting (Fig. 2b models TS1-G/H): 

 

Prepare cut out section for 85 x 39 mm 

 

Prepare holes for M4 screws 

 

Insert control into slot and tighten screws  

Temperature sensors (Fig. 3):

  

 

Avoid sharp bends or kinks in capillaries. 

 

Do not allow capillary to rub and abrade against 
any moving surface. Avoid work hardening effects. 

 

A capillary loop of ca. 8 cm diameter should be 
provided in capillary type sensors (A, C, P) below 
the control. 

Vapour charges (Sensor types A, E, P): 

 

These sensing elements always sense from the 
coldest point on the capillary, coil, bulb or power 
element head. 

 

Ensure that the control body and the portion of the 
capillary which is not at the sensing location is 
warmer than the sensing location by at least 2 K. 

 

Surfaces mounted controls should use an insulating 
console in order to ensure that control is not 
affected by the temperature of the mounting 
surface. 

 

At least 30 cm of sensor type “P” should be located 
at the sensing point for proper control. 

Adsorption charge (Sensor type “F”): 

 

This sensing element always responds to the bulb 
temp.  

 

The entire bulb must be in contact with the sensed 
temp. 

 

This charge is slower in response than a vapour 
charge. 

Electrical connection (Fig. 4): 

 

Note: Comply with local electrical regulations 
when conducting electrical wiring. Wire size 
must match the electrical load connected to the 
switch contacts. 

 

Feed cables through rubber grommet at switch 
bottom. 

 

Optionally, replace rubber grommet by a standard 
PG 13.5 cable gland. 

 

Connect wires to terminals 1, 2 and 4 by taking into 
account switch functions as shown in Fig. 1a to 1e. 

 

Fasten terminal screws with torque 1.2 Nm. 

 

For electronic applications with low electrical loads 
(voltage  <24 V and  current <50 mA) gold plated 
contacts are recommended. 

Setpoint adjustment (Fig. 4, Fig. 5): 

 

TS1 pressure switches come with individually 
adjustable range and differential depending on the 
exact model. 

 

Manual reset switches always have a fixed 
differential. 

 

Use the adjustment knob, a flat screw driver or a ¼” 
refrigeration (square) wrench to adjust setpoints as 
described below. 

 

Adjust upper setpoint using the range spindle. 

 

Adjust lower setpoint by turning the differential 
spindle: 

Upper setpoint – Differential = Lower setpoint 

 

A separate thermometer must be used for exact 
adjustment of the setpoints. The integrated display 
scale can only be used for obtaining approximate 
settings. 

 

Refer to the ALCO catalogue for standard factory 
settings. 

 

Minimum differential setting at the end of range do 
differ slightly from the nominal differentials. 

Manual reset (Fig. 6) 

 

Manual reset: press the reset button. 

 

Note that the reset is ‘trip-free’, i.e. reset is only 
possible if the temperature has reached its reset 
treshold. 

Off-switch (Fig. 1e) 

 

TS1-B/F/H have an off-switch which cuts off the 
line to terminal 1 when in Position “STOP”.

 

Check-out lever (Fig. 4) 

 

Use the check-out lever to manually override the 
electrical contact position for testing out the system. 

Standards 

 

Low Voltage Directive 73/23/EWG; 93/68/EWG; 
EN 60947-1; EN 60947-5-1; EN 60730-2-9 

 

UL/CSA: all models except front operated 

 

Marking:  

 

 
 

!

Summary of Contents for TS1-G

Page 1: ...mperature to be sensed Use universal thread M4 or UNC8 32 mounting holes for installation via mounting plate Use the standard mounting holes at the backside for wall mounting Use mounting screws supplied with control Mounting screws must not penetrate control backside by more than 8 mm to ensure proper operation In order to achieve protection class IP44 the following instructions must be observed ...

Page 2: ...der sonstiges Isoliermaterial verwenden wenn die Wandtemperatur nahe der zu messenden Temperatur ist Zur Montage mit Montageplatte die auf der Geräterückseite vorhandenen Bohrungen mit kombiniertem M4 UNC8 32 Gewinde verwenden Für Wandmontage sind zusätzliche Bohrungen vorhanden Befestigungsschrauben nicht tiefer als 8 mm in das Gerät eindringen lassen ansonsten ist die ordnungsgemäße Funktion des...

Page 3: ...garantir un fonctionnement correct Avec les modèles à charge vapeur charge A et P une console ou matière isolante doit être utilisée si la température du mur est proche de celle à contrôler Utiliser les trous taraudés polyvalents M4 ou UNC 8 32 pour la fixation sur un support Utiliser les trous standards à l arrière du boîtier pour le montage mural Utiliser les vis de montage livrées avec l appare...

Page 4: ...ratos con cargas de vapor A y P un aislante de cónsola o cualquier otro material aislante debe colocarse ante la pared si la temperatura de ésta es cercana a la de que se mida en la aplicación Usar tornillos M4 o UNC8 32 de tipo universal para los agujeros en instalación mediante placa de fijación Usar los orificios estandarizados del fondo trasero para la fijación en pared Usar los tornillos sumi...

Page 5: ...r montage middels de montageplaat de in de TS1 aangebrachte gecombineerde M4 UNC8 32 gaten Voor montage direct tegen een wand zijn separate boringen aangebracht Gebruik voor montage de meegeleverde schroeven De bevestigingsschroeven niet verder dan 8 mm in de behuizing draaien daar anders de juiste werking van de thermostaat niet meer gegeven is De TS1 kan in elke willekeurige positie gemonteerd w...

Page 6: ...než 8 mm Pro zachování krytí IP 44 je nutno Vnější kryt musí být pečlivě nasazen a šrouby dotaženy Přístroj musí být namontován na rovný povrch který kompletně překryje všechny otvory v zadní stěně termostatu Montážní poloha TS1 lze montovat v libovolné poloze vyjma vzhůru nohama Montáž Fig 2b modely TS1 G H zhotovit otvor v panelu 85x 39 mm připravit otvory pro šrouby M4 vložit přístroj do otvoru...

Page 7: ...ажную планку используйте универсальные отверстия с резьбой M4 или UNC8 32 Для настенной установки используйте стандартные монтажные отверстия на обратной стороне прибора Используйте монтажные винты поставляемые в комплекте с реле Для гарантирования нормальной работы реле монтажные винты не должны углубляться в него с обратной стороны больше чем на 8 мм Для обеспечения класса защиты IP44 необходимо...

Page 8: ...utzleiteranschluss Vis de masse Conductor de tierra Aardschroef Заземление Fig 5a 4 Effect of turning range spindle Fig 5b 6 Effect of turning differential spindle 1 Oberer Schaltpunkt Point de consigne haut Valor más alto Bovenste schakelpunt horní nastavení Верхняя уставка 2 Unterer Schaltpunkt Point de consigne bas Valor más bajo Onderste schakelpunt spodní hodnota teploty Нижняя уставка 3 Diff...

Reviews: