background image

LB1448

20.07.2005

Multicalor 300.1 PR/MD
Multicalor 400.1 PR/MD

Light oil / Natural gas 40÷300 mbar
Light oil / LPG 75÷300 mbar

MODELS

A

BRUCIATORI MISTI GAS + GASOLIO

B

GAS/LIGHT-OIL DUAL BURNERS

Summary of Contents for Multicalor 300.1 PR

Page 1: ...LB1448 20 07 2005 Multicalor 300 1 PR MD Multicalor 400 1 PR MD Light oil Natural gas 40 300 mbar Light oil LPG 75 300 mbar MODELS A BRUCIATORI MISTI GAS GASOLIO B GAS LIGHT OIL DUAL BURNERS...

Page 2: ...atural Gas L C V 8 570 kcal Nm3 LPG L C V 22 260 kcal Nm3 Light oil L C V 10 200 kcal kg max visc 1 5 E at 20 C OVERALL DIMENSIONS Burner output Backpressure in combustion chamber I M L E D D1 F C B A...

Page 3: ...the air servocontrol in approximately 30 seconds time When the servocontrol is fully open a signal to the electronic control unit starts the 66 seconds pre purge cycle At the end of the prepurging tim...

Page 4: ...ation probe which cuts in and sets the burner shutdown within the safety time In case of gas lack or a major pressure drop the minimum air pressure switch shuts down the burner Ref Description t1 Dura...

Page 5: ...STING THE MAXIMUM CAPACITY OF THE GAS Position the selector situated on the control panel on position 1 and proceed as follows Adjusting the maximum gas flow rate see figure on solenoid valve adjustme...

Page 6: ...p cover M ADJUSTMENT OF THE AIR PRESSURE SWITCH Unscrew screws A and B and remove cover C Set the pressure switch to the mini mum by turning regulator D to position 1 Start the burner and keep in low...

Page 7: ...st be suitable for burner The connection of boiler s thermostats and all the safeties The motor rotation direction The correct calibration of the motor s thermal protection When all the above mentione...

Page 8: ...button on the control box If after a successful pump priming the burner locks out after the prepurging due to a fuel pressure drop in the pump rearm the burner s lock out to restart the burner Do neve...

Page 9: ...p 5 Selector 0 Loking of devoices for operating at intermediate outputs Operation at max output Operation at min output AUTO Automatic operation 6 Main switch I O 7 Selector 0 Light oil Gas 8 Lockout...

Page 10: ...ses are blown out The control box is faulty THE BURNER RUNS THE PREPURGING AND SWITCHES TO LOCKOUT AT THE END OF CYCLE Check the fan and the air pressure Check the air pressure switch Control box faul...

Page 11: ...LOSE 1st Stage Increase power OPEN 2nd Stage Two stage operation Description of display and keys on the RWF 40 microprocessor regulator The figure shows the normal display indicating the actual value...

Page 12: ...to access the parameters level To move from one parameter to the next press PGM PGM When HYS1 is displayed burner ignition differential stage II increase or decrease the value using the and keys Conf...

Page 13: ...1 Connection for probe QAE2 passive probe Water probe Configuration code C111 9XXX Connection for probe FT TP passive probe Degusa probe Configuration code C111 5XXX Connection for probe QBE620 P act...

Page 14: ...faulty the regulator will not indicate the real value Situation The number 1999 blinks in the display as the actual value with SP E showing in the set point field Cause The external set point value i...

Page 15: ...e relative opening in the electrical panel A Insert the fixing anchors and screws into the slots and secure the unit to the panel B To open the regulator squeeze the cover from the ends as shown and l...

Page 16: ...ive probe QBE620 P QAE22 FT TP 1000 P4 P10 P16 P25 P40 Analog input 1 2 and 3 setpoint changeover shift C111 9030 5030 G000 G000 G000 G000 G000 Limit comparator controller type setpoint 1 locking C112...

Page 17: ...A UV 19 03 1998 Q N BEM43167 3 MULTICALOR 300 1 400 1 500 1 PR PR LANDIS SQM 50 481A2 LANDIS LFL 1 622 VPS 504 UV 11 03 2005 FMP 95 96 KMV R S T NO FMV MV U V W FMP MP U V W S R T KMP R S T NO SAMA 1...

Page 18: ...TV MV MP KA FU Z Q SWITCH OIL GAS COMMUTATORE GASOLIO GAS INTERRUPTEUR MAZOUT GAS CONMUTADOR GASOLEO GAS THERMOSTAT GRANDE PETIRE ALLURE HIGH LOW FLAME THERMOSTAT TERMOSTATO DI ALTA BASSA FIAMMA COMM...

Page 19: ...2005 FMP 95 96 KMP R S T NO KMV R S T NO MP U V W MV U V W Q HLB FMV FMP S R 10 11 8 5 6 7 9 T N FMV 95 96 SAgG 1 2 3 0 SAMA 1 2 3 0 FMV 97 98 HLBT GAS 2 GASOLIO 1 COMMUTATORE ALTA BASSA FIAMMA SWITC...

Page 20: ...LIO GAS INTERRUPTEUR MAZOUT GAS CONMUTADOR GASOLEO GAS TERMOSTATO DE SEGURIDAD COMMUTATORE MANUALE AUTOMATICO SWITCH MANUAL AUTOMATIC INTERRUPTEUR MANUEL AUTOMATIQUE CONMUTADOR MANUAL AUTOMATICO THERM...

Page 21: ...1 33 LFL 1 622 VPS 504 UV 22 06 2005 FMP 95 96 KMV R S T NO FMV MV U V W FMP MP U V W S R T KMP R S T NO SAMA 1 2 3 0 HLBT FMV 97 98 SAgG 1 2 3 0 GAS 2 GASOLIO 1 T P STC 50 Hz 400V HLB STAB T P STS R...

Page 22: ...MP KA FU Z Q SWITCH OIL GAS COMMUTATORE GASOLIO GAS INTERRUPTEUR MAZOUT GAS CONMUTADOR GASOLEO GAS THERMOSTAT GRANDE PETIRE ALLURE HIGH LOW FLAME THERMOSTAT TERMOSTATO DI ALTA BASSA FIAMMA COMMUTATOR...

Page 23: ...6 Q N BEM43188 1 MULTICALOR 300 1 400 1 500 1 PR PR LANDIS SQM 50 481A2 LANDIS LFL 1 333 LFL 1 622 PREDISPOSTO UV 03 11 2005 FMP 95 96 KMV R S T NO FMV MV U V W FMP MP U V W S R T KMP R S T NO SAMA 1...

Page 24: ...TATORE GASOLIO GAS INTERRUPTEUR MAZOUT GAS CONMUTADOR GASOLEO GAS THERMOSTAT GRANDE PETIRE ALLURE HIGH LOW FLAME THERMOSTAT TERMOSTATO DI ALTA BASSA FIAMMA COMMUTATORE MANUALE AUTOMATICO SWITCH MANUAL...

Page 25: ...400 1 PR AB Multicalor 300 1 PR MD Multicalor 400 1 PR MD 7 8 36 11 14 4 6 5 3 9 10 39 26 31 29 30 27 34 32 33 52 35 28 2 37 20 13 12 25 24 22 23 19 21 17 16 15 18 1 41 50 51 44 43 47 53 38 49 42 46 4...

Page 26: ...802 2 24 REL BASE Finder 5532 R905 R905 Finder 5534 R906 R906 25 REL Finder 5532 R711 R711 Finder 5534 R712 R712 26 UV CELL LANDIS QRA 2 A205 A205 27 IGNITION CABLE TC BFE01403 2 BFE01403 2 TL BFE0140...

Page 27: ...right to make without any prior notice all those modifications which it deems usefull and or necessary in order to improve the quality of its products without affecting their main features CEcoflam S...

Reviews: