background image

COMFORT DUO RF

 

    

 

COMFORT DOU RF-RV Wireless Thermostat 
Installation Guide 

COMFORT DOU RF is a surface-mounted 
transmitter unit and COMFORT DOU RF-RV, a 
receiver unit, it is designed to control the 
heating and cooling systems efficiently with 
precise control.

 

 

1) Features: 

 

Easy operation and settings with touch key function 
displayed on LCD. 

 TPI Function. 

  Temperature Differential adjustable. 

 Easy Installation: Separate Base plate to aid 

installation. 

 Daily Program period can be changed subject to 

personal activities or commercial applications. 

 Informative Display. 

Both Set & Room Temperature Displayed. 

Anti-freeze protection in standby mode. 

 Lock or unlock keys to prevent unauthorized 

changes. 

  Temperature reading calibration(offset). 

  Daily programming status indicator. 

  Battery low indicator. 

  Vacation setting to program a setback temperature 

to save energy. 

 

Comfort Override mode maintains the room 
temperature on the desired setpoint during a set 
period of time from 1~9 hours. 

 Manual override. 

  User settings can be retained when the thermostat 

is power off. 

2)Technical data: 

Temperature control range : 5 ~ 35°C 

Comfort setpoint adjustment range: 5 ~ 35°C 

Temperature adjustment scale : 0.5°C 

Temperature offset calibration range: ±3,5°C 

Temperature reading calibration increments: 0.5°C 

Antifreeze protection: 5.0°C (Standby mode Only) 

Switching differential (Hysteresis) : 0.5°C /1 °C /1.5 °C 
/2°C Default 0.5°C 

Temperature sensor : 10K Ohm NTC 

Temperature accuracy: ±0.5°C (@21°C) 

Temperature display resolution: 0.1°C 

Sampling resolution: 1 minute interval 

Material : Non flammable plastics 

Storage temperature : -10°C ~ 60°C 

Dimensions: 120W x 112 H x 27 D mm 

3) Installation 

 

 Please force the upper edge of the cover to open 

it and insert batteries (AA Alkaline Batteries x 2). 

4) Design and function 

(1) 

 Switch on/off    (2) 

 Run Prog. Select. 

(3) (6)

 Function key 

(4) 

 Heat / Cool / Auto mode select. 

(5) 

: Fan mode select. 

 :  

Confirm 

 :  Cancel 

:  NEXT ITEM, jump to next function setting 

Summary of Contents for COMFORT DUO RF

Page 1: ...fort Override mode maintains the room temperature on the desired setpoint during a set period of time from 1 9 hours Manual override User settings can be retained when the thermostat is power off 2 Technical data Temperature control range 5 35 C Comfort setpoint adjustment range 5 35 C Temperature adjustment scale 0 5 C Temperature offset calibration range 3 5 C Temperature reading calibration inc...

Page 2: ...e P2 8 00 29ºC 14 ºC Return P5 18 00 25ºC 21 ºC Sleep P6 22 00 27ºC 16 ºC PROG 2 period per day Program Time Cool Heat Wake P1 6 00 25ºC 21 ºC Sleep P2 22 00 29ºC 16 ºC 4 2 LCD Display Descriptions Key lock Frost Protection Heating on Battery Low Standby Mode Run Prog Wake Run Prog Leave Run Prog Occupied Run Prog Unoccupied Run Prog Return Run Prog Sleep Setting Mode DAY MoTuWeThFrSaSu MON TUE WE...

Page 3: ...G Press the key to start programming Press to enter the program setting for day of the week SET PROG Press to enter PROG COPY function Press to return to Run PROG mode 4 1 Set PROG A Press to enter the program setting You will see Mo and P1 temperature reading is flashing Each day of the week can be individually programmed B Press the key to set desired temperature for P1 program period C Press th...

Page 4: ... for copy are completed The display returns to start PROG setting mode 5 Set Differential Press the key to select the settings for Operating mode Press to change between TPI and ANALOGE operationg mode and press to select the desired one 5 1 Analoge operating mode Once selected the Analoge operating mode press key to change value 0 5 1 1 5 2 the default value is 0 5 Press to save the changed value...

Page 5: ...oom code of your device Press to enter RF Room code setting In order to pair with RV receiver please set a code from 0 15 Attention After setting the room code please remember to set the dip switch on RV receiver For dip switch setting please refer the form below Press key to save the setting 10 Test RF signal strength of location 1 To test your devices location are good or not 2 When the ventilat...

Page 6: ...NUAL override will expire Press key to cancel the MANUAL override mode and return to Run PROG mode 3 COMFORT override COMFORT override allows you to change the temperature for a specific number of hours from one to nine without altering the thermostat s program The thermostat will use the new temperature setting for the specified amount of time then the thermostat will return to run the programmed...

Page 7: ...mostat keeps monitoring the room temperature and calls for heating should there be a risk of frost damage 1 Activate Standby function by pressing key power icon and frost protection icon will appear on LCD 2 Press the key to deactivate the Standby function and return to Run PROG mode Power icon and frost protection icon will disappear from LCD 7 Key Lock function This function allows you to lock t...

Page 8: ...ds of blue cover by screw driver and make the electrical connections according to the following scheme N Neutral 230 V C Cooling L Phase 230 V F Fans fancoils H Heating COM Common Operating Instruction RF code ID setting 1 Check RF code to match with the transmitter s RF code Initial code setting is 0000 All pins are downward 2 RF LED indicator on the right next to reset A The LED will keep lighti...

Reviews: