CHLORIDE 

User's Guide and Reference

 

 

 

 

 

ManageUPS

®

 

NET ADAPTER

 P-Series

 

ManageUPS

®

 

NET ADAPTER

 VP

 

 

Network Adapter for UPS Management 

 

 

 

 

 

Licenses and Trademarks 

ManageUPS and MopUPS are registered trademarks of ONEAC Corporation, A 
Chloride Power Protection Company. All other trademarks, product and corporate 
names are the property of their respective owners.  

Entire contents copyright ©2008 ONEAC Corporation. All rights reserved. 
Reproduction in whole or in part without permission is prohibited.

 

 

Controlled Document Number: 913-623 @Rev A    10 April 2008 

Summary of Contents for ManageUPS

Page 1: ...UPS are registered trademarks of ONEAC Corporation A Chloride Power Protection Company All other trademarks product and corporate names are the property of their respective owners Entire contents copyright 2008 ONEAC Corporation All rights reserved Reproduction in whole or in part without permission is prohibited Controlled Document Number 913 623 Rev A 10 April 2008 ...

Page 2: ......

Page 3: ...1 I 2 I 4 I 5 Section II Network Setup Understand Your Network Setting Network Parameters DHCP Client and Network Settings II 1 II 3 II 5 Section III Setting Service Options Overview of Services Logging Services Network Time Reference 4 Event Messaging E Mail and SNMP configuration Network Shutdown Controller III 1 III 2 III 5 III 9 Section IV Administrative Settings About ManageUPS Net Adapter P ...

Page 4: ...oting VII 1 VII 2 VII 3 VII 4 VII 5 VII 6 VII 7 Section VII Configuring the Environment Sensor P Series Only Hardware Specifications Hardware Installation Browser Interface Sensor Configuration Environment Sensor Settings 5 Input Device Settings 6 Output Relay Settings 7 Chloride Environment Sensor MIB Object List VIII 1 VIII 2 VIII 3 VIII 4 VIII 8 Appendices Appendix A Methods for ManageUPS Confi...

Page 5: ......

Page 6: ...e communications expansion slots will use the internal adapter card Other UPS models will use the adapter card with external chassis power supply and communications cables ManageUPS Net Adapter VP P Series cards with Legacy Adapter are compatible with external chassis and can be used to update services and features in existing installations Simplified Description of Services Message Send a message...

Page 7: ...ftware element or program that requests information or actions from other software elements known as servers Server A program that provides some service to other client programs The connection between client and server is normally by means of message passing often over a network and uses some protocol to encode the client s requests and the server s responses Agent An Agent is a server that thinks...

Page 8: ...ation S FTP TFTP Network Update C DHCP Auto Net Configuration S CONSOLE Dial in and Local RS232 Terminal access to Configuration and Status menus S TELNET Network access to Console BASE HARDWARE S HTTP Network Browser access P Series Only S Modbus JBus Serial Communications RS232 RS422 RS485Half Full Duplex TCP IP 1 The specific services available on your ManageUPS adapter may depend on model and ...

Page 9: ...ental Installation Note for your UPS Installation notes are included on the ManageUPS documentation CD and are also available from http connectivity chloridepower com Some UPS models do not report all information needed by ManageUPS to represent the UPS accurately ManageUPS will request missing information when the UPS Status WEB page is first accessed Review Section V Device Settings in the User ...

Page 10: ...IP address is entered in the Management URL control in the node description form offered by the NMS This makes it easy for the administrator to navigate to the ManageUPS WEB page to learn more about the UPS status ManageUPS embedded WEB server offers all UPS MIB measures and controls Network administrators at a central operations center use an SNMP management system to monitor and manage IT networ...

Page 11: ...an restart any batch jobs interrupted by power fail conditions When UPS alarm conditions occur ManageUPS will initiate e mail to identified e mail recipients The long form email intended for desktop e mail clients includes a URL link back to the ManageUPS WEB server to make it convenient to research the conditions that may be causing the alarm Short form e mail options are offered for routing to p...

Page 12: ... and other UPS module events that may affect redundancy or overall availability and calls the manager s pager At Campus C SUBNET a backup server is supported by a UPS shared with the campus PABX router switch e mail server and other infrastructure devices located in the campus communications center Some of the backup server s clients are in Department 2 The backup repository is the SAN Storage Are...

Page 13: ...UPS NSC is configured to connect to the first group and call OS shutdown five minutes after an AC failure has been reported by the UPS As this group finishes its shutdown and power off sequence the UPS load on the battery is reduced by about 1 3 increasing the autonomy available to the remaining groups Shutdown is called on the second group after 15 minutes on battery have elapsed The third group ...

Page 14: ...rise WAN Or only within a local subnet or LAN side of a Router Does your network manage network address registration automatically What is your network administrator s policy or procedure for assignment of static IP addresses and entry of server host names in DNS tables Does you network operate a local Network Time NTP Server Does your network operate an SMTP server Basic Network Parameters If you...

Page 15: ...sary See page II 5 for more information Q What happens if there is no DHCP server available or if there is no dynamic IP address available from the DHCP pool A If ManageUPS is not able to obtain an IP address from a DHCP it will negotiate an unused IP address from the reserved link local IP range 169 254 xxx yyy See DHCP client on page II 5 for more information Q Can I turn off the DHCP client Can...

Page 16: ... need to know the default username password combination Default username admin Default password admin The three options for configuring Network Settings manually via network connection are described below Configuration using ManageUPS DCU ManageUPS DCU Discovery and Configuration Utility is a software program that will help simplify initial configuration and ongoing management of ManageUPS adapter...

Page 17: ...with the adapter using its new IP address You may want to configure Service Administrative or Device settings before rebooting Configuration via CONSOLE Menu For Telnet and Serial Configuration methods The CONSOLE utility is a text menu interface that is available via Telnet or via serial port The lower section of the MAIN menu right provides navigation to other menus If IP address is set to STATI...

Page 18: ...necessary Generally it is considered good practice to assign a static IP address to server class devices but many network policies use dynamic address provisioning and automated network registration to simplify network administration Generous lease periods allow a device that obtains a specific IP from a lease pool to continue to use the same IP unless the DHCP server s MAC table becomes corrupted...

Page 19: ...nted here If the DHCP session does not include assignment of DNS Host Name the entry will be the default value shown Changing the host name entry in ManageUPS TCP IP settings will not affect the entry in the DNS server s directory NOTE Handling of hostname via DHCP under DDNS When the adapter boots with DHCP enabled then the adapter will provide it s hostname in the DHCP request By default this na...

Page 20: ...TATIC IP SETTINGS IP Address Fixed IP address assigned to this adapter Subnet Mask Subnet Mask of the network that the UPS unit is on Default Gateway The local default gateway IP address of the router DNS Settings Primary DNS Server IP address of the primary DNS server Secondary DNS Server IP address of the secondary DNS server ...

Page 21: ...Network Setup 913 623 Rev A User Guide ManageUPSnet Section II page 8 ...

Page 22: ...rify the IP address of a local NTP server in the Date Time Settings menu Event Messaging Service Pages 5 8 The messaging service sends messages on UPS status events via SNMP Trap e mail or both For e mail alerts set e mail recipients and the address of the SMTP server on your network that will deliver these e mails Set up to ten destinations to receive SNMP traps If you plan to use the full SNMP a...

Page 23: ...ubleshooting the cause of the problem ManageUPS accumulates various measures reported by the UPS between log intervals and summarizes this information for each entry The following explains each of the fields contained in the data log Date and Time the log entry was made is presented according to your time zone preference The calendar and clock are synchronized to the network time server See NETWOR...

Page 24: ...ed reflects a temperature reading within the UPS cabinet typically either in the inverter power electronics region or in the battery compartment Log Controls Changing the LOG INTERVAL will change the amount of time ManageUPS waits before making entries in the data log file Extending the duration between log entries allows ManageUPS to archive a longer history of data measures The default data log ...

Page 25: ...ts clock and calendar reference at Midnight 1 January 2000 GMT If this occurs ManageUPS will retry to access the NTP server once every 5 minutes until a connection is established unless NTP is disabled in the FREQUENCY control Frequency How often ManageUPS will synchronize with the NTP Server Time Zone Log entries are stored using GMT Select the time zone to be used for displaying data log entries...

Page 26: ...ies in their form within the page Press APPLIES to save changes before configuring email destinations Email Destinations Enter the NAME and EMAIL ADDRESS of message recipients and determine which severity level should trigger email messages to this destination See Appendix B Alarm Detail for more information on alarm interpretation For regular email recipients use the LONG message type Use SHORT o...

Page 27: ... the following condition Module Utility Power Fail ManageUPSnet Information Model ACTIVE Serial Number 0412 cf00 Host Name none Contact Your ContactName Location YourLocation Attached Devices URL http 192 168 1 2 Short Message Type From ManageUPS27 Yournet com Sent 5 April 2004 To TestR1 yournet com Subject Utility Power Fail Module Utility Power Fail Short Message Type No Subject From ManageUPS27...

Page 28: ... of the trap receiver Community The name authentication string of the SNMP trap receiver community About SNMP UPS Traps There are four traps defined in the standard UPS MIB RFC1628 Trap1 upsTrapOnBattery DESCRIPTION The UPS is operating on battery power This trap is persistent and is resent at one minute intervals until the UPS either turns off or is no longer running on battery Trap2 upsTrapTestC...

Page 29: ...these additional alarm entries change the setting in the SNMP trap control dialog Suppress Non RFC1628 Alarms NOTE For a complete list of UPS alarms reported by ManageUPS including SNMP MIB OID email severity code and probable cause see Appendix B Alarm Detail SNMP Communities SNMP Communities is an authentication scheme that enables an intelligent network device to validate SNMP requests Name The...

Page 30: ...st group is executed before shutting the UPS off Network Shutdown Controller Settings Cancel UPS Shutdown if Utility Power Returns After Execution of Last Group Available Only on UPS s with Shutdown Capabilities If this option is checked the UPS shutdown will be cancelled if power returns after the last group is executed but before the UPS is turned off A restart message will then be sent to all I...

Page 31: ...omputer in a range to receive Remote Shutdown signals Formatted as XXX XXX XXX XXX IP Address To The fourth octet of the last computer in the range to receive Remote Shutdown messages Must be a number greater than the fourth octet of the corresponding IP Address From and must be less than 255 Port for Shutdown Sequence The TCP IP port each of the computers in this range is listening on for Remote ...

Page 32: ...Setting Service Options 913 623 Rev A Section III page 11 ...

Page 33: ...ins menus and utilities for setting identity information network parameters covered in Section II security and firmware maintenance About ManageUPS The Product Identification area contains information that is useful when contacting your vendor for technical support Ratings and Identity contains standard variables required in most SNMP applications ...

Page 34: ...odel Number Adapter Model Number Part Number Serial Number Adapter Serial Number is a 4 digit date code followed by the last 4 digits of the MAC ID MAC Address Adapter MAC Address RATINGS AND IDENTITY Contact The system Contact name for this UPS This value is returned as the sysContact object in SNMP MIB II Location Location of the UPS This value is returned as the sysLocation object in SNMP MIB I...

Page 35: ...GS Controls the duration authentication lasts when there is no session activity and determines what can be viewed or changed by non authenticated users accessing the adapter via WEB Browser AUTO LOGOUT This security feature will automatically log a user off of HTTP Telnet or FTP when the session is idle for the specified amount of minutes HTTP WEB AUTHORIZATION OPTIONS The following options are av...

Page 36: ...for a specific protocol If an arbitrary port is used between 5000 and 65535 you can effectively hide the server on the network This provides an additional level of security since the port must be known by the user when attempting to connect to the server with client software NOTE If you change the port setting in a server you will also need to use the new port setting when accessing the server wit...

Page 37: ...s required to cause system changes such as a change to the IP Address to take effect See also Hardware Reset below REBOOT RESET UTILITIES Reset the Adapter This will cause all settings on the adapter to be reset to their factory default values Note that this will reset all passwords and other user specific settings If you want to save some settings download and save the configuration files before ...

Page 38: ... anywhere from three to ten seconds the USERNAME and PASSWORD revert back to the factory default 3 If the RESET switch is depressed for more than ten seconds it reverts back to the factory defaults The RESET Switch can be reached through the access hole by using a paperclip or similar object Note Resetting the adapter with the RESET switch will clear all volatile object values in the SNMP agent Th...

Page 39: ...tivity support web site you will be notified by email if an update for either of these files is available for download The cfg type files store the results of user specific settings entered during the configuration steps covered in sections II and III To simplify configuration of multiple adapters on your network After you have configured the first adapter download the mopups and or snmp configura...

Page 40: ...he directory that contains the file you want to upload Open an FTP session by typing ftp manageupsDNSname or manageupsIPaddress You will be prompted for the username and password Default is admin admin If the file to be uploaded is a type cfg or type merge simply enter ftp put mopups cfg or put mopups merge If the file to be uploaded is an agent or system update then enter the word bin at the FTP ...

Page 41: ...Administrative Settings 913 623 Rev A Section IV page 9 ...

Page 42: ... be reported as string voltage or cell voltage depending on the UPS model This value is returned as the upsBatteryVoltage object in the UPS MIB RFC1628 Internal Temperature The internal temperature reported by the UPS This value is returned as the upsBatteryTemperature object in the UPS MIB RFC1628 Est Battery Life Sometimes referred to as Estimated Autonomy This is an estimate of the amount of ti...

Page 43: ...ted as Battery or Bypass Percent Load The percentage of the UPS capacity currently being supplied by the UPS Output Watts The measured UPS output power in Watts Input Line Disruptions The number of times the UPS has been on inverter due to input voltage being out of tolerance Input Frequency The frequency measured on the UPS AC input Input Voltage The voltage measured at UPS AC input Min Input Vol...

Page 44: ...bove are described below Battery Impedance Test The Impedance test performs a qualitative analysis of the condition of the battery This test runs at regular intervals The impedance test returns one of three results Passed Battery is significantly degraded or The battery is defective and must be replaced as soon as possible Deep Battery Autonomy Calibration This test performs a deep battery dischar...

Page 45: ... Mute the Audible Alarm This action mutes the audible alarm for the duration of the current event It does not disable the alarm If you want to silence the audible alarm for future events navigate to the UPS Configuration menu The control for the audible alarm is in the General Settings dialog area Reboot the UPS This action causes the UPS output to immediately turn off and then restart after the t...

Page 46: ...ed to the UPS Setting the transfer points closer together will cause the UPS to provide a more tightly controlled voltage but may also cause the UPS to switch to battery power more frequently depending on the quality of your AC line power The factory default values are sufficient for most applications Battery Replacement Date The date on which the UPS was first commissioned or when the battery was...

Page 47: ...ceived from monitoring software If Whole UPS is selected the UPS output and internal electronics are turned off In this state the UPS will not be able to communicate with monitoring software until the UPS is restarted If Output Only is selected the UPS output is turned off but the UPS internal electronics remain Auto Restart This setting controls the conditions under which UPS output is restarted ...

Page 48: ...d ManageUPS may prompt you to confirm ups identity and ratings information that the UPS does not communicate to ManageUPS Model The model number of the UPS unit Serial Number The serial number of the UPS unit Firmware Version The version number of the firmware in the UPS Capacity The maximum power output of the UPS Capacity is measured in VA and Watts The VA measurement is the maximum power availa...

Page 49: ...oltage The line voltage that the UPS is designed to operate with Nominal Input Frequency The line frequency that the UPS is designed to operate with Nominal Output Voltage The nominal output voltage supplied by the UPS Nominal Output Frequency The nominal frequency that supplied by the UPS ...

Page 50: ...Device Settings 913 623 Rev A Section V page 9 ...

Page 51: ...from the adapter A print formatted register map document is included in this document as Appendix E Modbus Jbus Serial Communications RS485 2 wire Half Duplex The default physical serial communication mode for ManageUPS Net Adapter P Series is RS485 2 wire half duplex configuration settings shown below Use the WEB interface above to change address and device ID setting to meet your requirements Mo...

Page 52: ...y serial communications with the building monitoring system The screen below will report the activity seen by the adapter on the serial network The UPS Alarm Test will cause the MODBUS RTU server to simulate alarm conditions Select the condition of interest and press Apply to activate the simulated alarm Verify that the alarm is interpreted correctly at the BMS Make sure to select None Selected an...

Page 53: ...Pin 1 D is connected to Pin 2 and Pin 4 D is connected to Pin 3 and Pin 5 Pins 4 and 5 are also used in full duplex mode Pin 6 is not used In half Duplex mode Pin s 2 4 and Pin s 3 5 are electrically connected to aid in the wiring of multiple devices on the Modbus network When the ManageUPS Net Adapter P Series is configured for full Duplex Pin s 4 5 are reassigned to RXD RXD respectively Wiring D...

Page 54: ...on for other Serial Communications network To configure the adapter to use one of the other serial communications modes you will need to change jumper settings on the adapter hardware Physical jumper locations are shown in the photo below Set jumper positions according to the table below P7 P8 P6 P9 ...

Page 55: ... measures and status information obtained from the UPS by the ManageUPS adapter Some addresses are reserved as space for entering custom identification objects This information will be retained in the adapter flash memory system and presented in specific register addresses Set this custom information using the WEB interface shown below The complete MODBUS register map is listed in Appendix E ...

Page 56: ...Insert the provided license key and press the Add License Key button Notice the Modbus Services feature in not available in the screen above The Modbus Services link will become available after the license key is accepted Referring to the image above the Modbus column indicates if the license key is supporting Modbus The Factory column indicates if the license was submitted in the factory To remov...

Page 57: ...ubleshooting There is a troubleshooting utility on the adapter that is accessible from the WEB interface Use this utility to view what the adapter is receiving and sending on the RS485 network connection See Modbus Jbus configuration screen on bottom of page 1 of this section of the document ...

Page 58: ...midity Measurement range 1 99 RH Accuracy 2 between 10 and 90 RH Input Contacts Accepts input from up to three 3 Form C dry contacts Output Relay 1 relay contact rated 1A 30V normally open or normally closed Environment Sensor Conformance Emissions EMC Directive 89 336 EEC as amended by 92 31 EEC and 93 68 EEC EN 55022 19948 A1 2000 A2 2003 EN 50091 2 1995 EN 61000 3 2 2000 EN 61000 3 3 1995 A1 20...

Page 59: ...r in the UP position 4 Set the address switches 2 5 of the each additional sensor to be unique different from the 1st sensor and different from any other sensor on the bus Terminator shown in the UP position Address Switch Translation Table 32 0000 33 0001 34 0010 35 0011 36 0100 37 0101 38 0110 39 0111 40 1000 41 1001 42 1010 43 1011 44 1100 45 1101 46 1110 47 1111 Address combination switches 2 ...

Page 60: ...ayed These values are returned as MIB objects in the Chloride Environment Sensor MIB Input Output Device Status Status View The current state and defined alarm condition are displayed for each input and output relay contact The states of these switches are also returned as MIB objects in the Chloride Environment Sensor MIB Status View Multiple Sensors If multiple sensors are connected to the bus e...

Page 61: ...PLY button in each section enters the settings for that section You should configure one section at a time pressing the APPLY button before configuring the next section Configuration options are explained in the on screen HELP utility A copy of the on line help entries are included on the following pages NOTE The control for Toggle the State of the Output relay does not permanently override an eve...

Page 62: ...t which the high temperature condition is generated for this sensor This value is the tempHiThreshold object in the Chloride Power Environment Sensor MIB Low Temp The temperature at which the low temperature condition is generated for this sensor This value is the tempLoThreshold object in the Chloride Power Environment Sensor MIB High RH The relative humidity at which the high relative humidity c...

Page 63: ...NormalState2 inputNormalState3 objects in the Chloride Power Environment Sensor MIB URL 1 3 A url associated with this device Must be in the format http hostname When this value is set the input name becomes a link on the environment status page These values are the inputUrl1 inputUrl2 inputUrl3 objects in the Chloride Power Environment Sensor MIB Event Severity 1 3 This setting determines the sev...

Page 64: ...ing determines the number of seconds the Energize Relay When conditions must be present before the relay is energized Hold The number of seconds the relay will be held in the energized state after the Delay time has expired If the Energize Relay When conditions are corrected before this time is up the relay will de energize An entry of 0 in this field will cause the relay to remain energized for a...

Page 65: ...628 1 3 6 1 2 1 33 The environment sensor MIB is a private enterprise MIB 1 3 6 1 4 1 1364 10 The sensor MIB is organized in tables of object values alarms and traps Each entry shown on the WEB interface is represented as an object in the sensorTable sensorEntries The table on the next page illustrates how the MIB handles entries for single sensor and multiple sensor configurations NOTE Screen sho...

Page 66: ...40 temperature 1 21 temperature 1 22 temperature 2 21 tempStatus 1 Normal tempStatus 1 Normal tempStatus 2 Normal tempHiSeverity 1 Warning tempHiSeverity 1 warning tempHiSeverity 2 disabled tempLoSeverity 1 informational tempLoSeverity 1 informational tempLoSeverity 2 disabled tempHiThreshold 1 43 tempHiThreshold 1 43 tempHiThreshold 2 50 tempLoThreshold 1 20 tempLoThreshold 1 20 tempLoThreshold 2...

Page 67: ...Environment Sensor 913 623 Rev A Section VII page 10 ...

Page 68: ...rt on your PC to the ManageUPS serial configuration port as described in the Supplemental Installation Note appropriate for your UPS The ManageUPS serial configuration port will be either the UPS communications port on internal adapters or the DB9 port marked TERM on external adapters Location of serial ports on external adapter Open a Terminal Session If your terminal settings are correct you sho...

Page 69: ... General Terminal Settings BPS 1200 2400 or 9600 Depends on UPS model family Other settings are standard for all Data Bits 8 Parity None Stop Bits 1 Flow Control None ASCII Setup Send line ends with line feeds Echo Off Configuring Hyper Terminal 1 2 3 4 5 6 ...

Page 70: ... Module Fan Failure Fan failure detected 17 upsAlarmFuseFailure Module Fuse Failure Input circuit breaker is open or charger fuse has blown 18 upsAlarmGeneralFault Module Requires Servicing A UPS fault was detected that is not specifically identified in the UPS protocol or defined in the standard MIB 19 upsAlarmDiagnosticTestFailed Module Diagnostics Failed A user initiated test has failed 20 upsA...

Page 71: ... output is off but the UPS control logic is still operating This trap can only be sent if the adapter is powered from a source other than UPS output 15 upsAlarmUpsSystemOff Module System Is Off UPS output and control logic is off Will likely never be seen 21 upsAlarmAwaitingPower Module Awaiting Power UPS output is off and the UPS is waiting for input power to be restored 22 UpsAlarmShutdown Pendi...

Page 72: ...ns with the UPS MopUPS Service Started The Adapter s device monitoring service has started successfully MopNSA remote shutdown failed to authenticate to IP address port MopNSA remote shutdown failed to connect to IP address port MopNSA remote shutdown succeeded to shutdown IP address Network Shutdown Controller Return Codes for MopUPS NSA RCCMD failed to connect to IP address on port port Informat...

Page 73: ... 8 Value assumes ManageUPS is the only accessory in the multi slot If a LIFE modem or other accessory is also installed in the multi slot accessory bay subtract 3 Contact the factory for further details on compatibility with other accessories ACTIVE 230V ACTIVE UPS communications slot power supply was redesigned in early 2005 to provide more power Check the serial number list below to determine wh...

Page 74: ... accessory bay subtract 3 Contact the factory for further details on compatibility with other accessories Series A 230V Series A UPS communications slot power supply was redesigned in early 2005 to provide more power Check the serial number list below to determine whether your unit has enhanced power availability 7 1kVA 0 Early Design 2 3kVA NA Enhanced Power Design All models 3 Series A Model Ser...

Page 75: ... 120V 3 6kVA 0 Sinergy E 10 20kVA 2 Sinergy II 5 ON v96 6 2 2 kVA 3 ONEAC Brand UPS Models ON v96 3 5kVA 3 ON UM 7 2kVA 5 8 Value assumes ManageUPS is the only accessory in the multi slot If a LIFE modem or other accessory is also installed in the multi slot accessory bay subtract 3 Contact the factory for further details on compatibility with other accessories ...

Page 76: ...ts a SNMPv1 translation of RFC1628 Meets the requirements of the upsFullCompliance module defined in RFC1628 Automatic Network Configuration DHCP client RFC2131 2136 DDNS and Apple Zero Configuration networking BONJOUR TM multicast mDNS service Network Access SNMP HTTP Telnet FTP Mopnet Network Update Firmware OS and Configuration update via FTP TFTP Fault messaging via SNMP Trap and or email Seri...

Page 77: ... Chloride 1 Masterguard 2 Oneac 3 Reserved 4 Reserved 5 Other 003h 4 2 upsIdentModel 0 SI SII 1 70 net C CP3020 2 90 net SIII CP3150 3 Reserved 4 Reserved 5 Reserved 6 Reserved 7 Reserved 8 80Net 9 Reserved 15 Series A Active 16 Series E Linear 004h 5 3 upsIdentUPSSoftware 1Version HH Major LL Minor 005h 6 4 upsIdentUPSSoftware 1DateYear 006h 7 5 upsIdentUPSSoftware 1DateMonth 007h 8 6 upsIdentUPS...

Page 78: ...y 013h 20 1 upsBatteryStatus 1 unknown 2 batteryNormal 3 batteryLow 4 batteryDepleted 014h 21 2 upsSecondsOnBattery s 015h 22 3 UpsEstimatedSeconds Remaining s 016h 23 4 UpsEstimatedCharge Remaining 017h 24 5 upsBatteryVoltage 0 1 V 018h 25 6 upsBatteryCurrent 0 1 A 019h 26 7 upsBatteryTemperature C 01Ah 27 8 reserved 01Bh 28 9 reserved 01Ch 29 10 reserved 01Dh 30 11 reserved 01Eh 31 12 reserved u...

Page 79: ... 1kW 02Ah 43 12 upsInputRealPower L3 0 1kW 02Bh 44 13 upsInputDCVoltage V 02Ch 45 14 reserved 02Dh 46 15 reserved 02Eh 47 16 reserved 02Fh 48 17 reserved 030h 49 18 reserved upsOutput 031h 50 1 upsOutputSource 1 other 2 none 3 normal 4 bypass 5 battery 6 booster 7 reducer 032h 51 2 upsOutputFrequency 0 1 Hz 033h 52 3 upsOutputNumLines 034h 53 4 upsOutputVoltage L1 V 035h 54 5 upsOutputVoltage L2 V...

Page 80: ...64 15 upsOutputPercentLoad L3 040h 65 16 reserved 041h 66 17 reserved 042h 67 18 reserved 043h 68 19 reserved 044h 69 20 reserved upsBypass 045h 70 1 upsBypassLineBads 046h 71 2 upsBypassFrequency 0 1 Hz 047h 72 3 upsBypass InputNumLines 048h 73 4 upsBypassVoltage L1 V 049h 74 5 upsBypassVoltage L2 V 04Ah 75 6 upsBypassVoltage L3 V V 04Bh 76 7 upsBypassCurrent L1 0 1 A 04Ch 77 8 upsBypassCurrent L...

Page 81: ...edBattery 056h bit 5 6 upsAlarmTempBad 056h bit 6 7 upsAlarmInputBad 056h bit 7 8 upsAlarmOutputBad 056h bit 8 9 reserved 056h bit 9 10 reserved 056h bit 10 11 reserved 056h bit 11 12 reserved 056h bit 12 13 reserved 056h bit 13 14 reserved 056h bit 14 15 reserved 056h bit 15 16 reserved 057h 88 bit 0 17 upsAlarmOutputOverload 057h bit 1 18 upsAlarmOnBypass 057h bit 2 19 upsAlarmBypassBad 057h bit...

Page 82: ...it 9 42 reserved 058h bit 10 43 reserved 058h bit 11 44 reserved 058h bit 12 45 reserved 058h bit 13 46 reserved 058h bit 14 47 reserved 058h bit 15 48 reserved 059h 90 bit 0 49 upsAlarmTestInProgress 059h bit 1 50 upsAlarmAutonomyCalibration 059h bit 2 51 upsAlarmGeneralWarning 059h bit 3 52 upsAlarmBatteryCharging 059h bit 4 53 upsAlarmBackfeedRelayFailure 059h bit 5 54 upsAlarmBatteryFuseBlown ...

Page 83: ...ed 3 05Eh 95 5 upsConditionNonSynchronism 060h 96 6 reserved 061h 97 7 reserved 062h 98 8 reserved 063h 99 9 reserved 064h 100 10 reserved upsParallelCondition 065h 101 1 upsInParallelSet 0 UPS is single 1 UPS is part of parallel set 066h 102 2 upsDetectParallel Problem 0 UPS is in single mode or runs in parallel mode and is fine 1 UPS detects a problem in parallel mode 067h 103 3 reserved 068h 10...