manualshive.com logo in svg
background image

 
 
 
 
 
 
 
 
 
 

 

 

 
 
 

   

 

 
 

TOBi™ PI Wi-Z 

  

Performance Indicator and Event Logger 
 

 
 
 
Quick Installation Guide   

 
 
 

 
 
 

S47-0180 Revised 10/13/2020 

 

 

 

     

Safety Instructions

 

 

WARNING 

BATTERIES CONTAIN LETHAL VOLTAGE LEVELS.  

INSTALLATION AND SERVICING MUST BE PERFORMED 

BY QUALIFIED PERSONNEL. 

 
 

IMPORTANT:  SAVE THESE INSTRUCTIONS! 

READ AND FOLLOW ALL INSTRUCTIONS BEFORE 

INSTALLING, OPERATING, OR SERVICING TOBI.  ANY 

DEVIATION CAN CAUSE SERIOUS AND PERMANENT 

DAMAGE.  FAILURE TO FOLLOW THE INSTRUCTIONS 

WILL VOID THE WARRANTY. 

 
Do not touch un-insulated parts of the output connector or 
battery terminals.  A possibility of serious electrical shock 
exists. 
 
Never smoke, use an open flame, or create sparks in the 
vicinity of the battery.  Ventilate well when the battery is in an 
enclosed space. 
 
Lead-acid batteries contain sulfuric acid, which is caustic 
and can cause chemical burns to the skin. Refer to the 
battery manufacturer’s instructions for safe handling of 
batteries. Use proper personal protective equipment.  Do not 
get in eyes, on skin, or on clothing.  In cases of contact with 
eyes, flush immediately with clean water for 15 minutes.  
Seek medical attention immediately. 
 
Care should be observed when using tools on or around the 
battery to avoid shorting the battery.  Do not lay tools on top 
of the battery. 

 
 
 
 
 
 

Содержание TOBi PI Wi-Z

Страница 1: ...or or battery terminals A possibility of serious electrical shock exists Never smoke use an open flame or create sparks in the vicinity of the battery Ventilate well when the battery is in an enclosed space Lead acid batteries contain sulfuric acid which is caustic and can cause chemical burns to the skin Refer to the battery manufacturer s instructions for safe handling of batteries Use proper pe...

Страница 2: ...or other services will be provided by CTI CTI shall not be obligated to reimburse the original user or any other person for any work performed 3 2 Replacement and exchange parts will be warranted for the remainder of the original warranty period or for a period of thirty 30 days whichever is greater 3 3 CTI shall not be liable for direct or indirect special or consequential damages in excess of su...

Страница 3: ...4 Strap Thermistor black wires with ring terminal 5 12V Post blue wire 6 Water Level Probe with lead probe and grommet at the end 7 Cell Thermistor thick black cable with black probe and grommet at the end 8 Positive Post red wire 1 Attach the BLACK wire to the negative post of the battery by first drilling a 5 32 pilot hole in the center of the post Attach the ring terminal of the lead to the bat...

Страница 4: ...rill a hole in the lid of one of the cells near the center of the battery refer to figure 2 Choose a cell that is at least 4 cells from the negative post of the battery 8V Ensure the area under the cell lid is clear to the moss shield before drilling Trim the lead water probe using wire cutters so that the tip will be approximately 1 8 above the moss shield after installing the probe Press the pro...

Страница 5: ...w complete You are ready to calibrate the current sensor and enter battery data into the system Please refer to the Tobi Wi Z Software User Guide for instructions on calibrating and initializing your new Tobi PI Wi Z This device complies with part 15 of the FCC rules Operation is subject to the following two conditions 1 This device may not cause harmful interference 2 This device must accept any ...

Отзывы: