APPLICATION

The LiftMaster

®

 Protector System models CPS-RPEN4 and CPS-RPEN4GM, are single-sided safety devices 

providing monitored entrapment protection for use with LiftMaster

®

 Commercial Door and Gate Operators. 

The CPS-RPEN4 and CPS-RPEN4GM may be installed in areas exposed to rain or moisture. The images are for 
reference and your product may look different. 

Model CPS-RPEN4 (LiftMaster

®

 Commercial 

Door Operators)

Model CPS-RPEN4GM (LiftMaster

®

 

Gate Operators)

Logic 4 

FDCL Commercial Door Operator

CSL24V Series

RSW12V Series

LA500

Medium Duty Logic 

FDOA Commercial Door Operator

CSW24V Series

LA400

FDC Commercial Door 
Operator

FDOB Commercial Door Operator

RSL12V Series

LA412

LIFTMASTER

®

 PROTECTOR SYSTEM

IMPORTANT INFORMATION ABOUT THE PHOTOELECTRIC SENSOR

Be sure power to the operator is disconnected.

When properly connected and aligned, the photoelectric sensor will detect an obstruction in the path of its 
beam. If an obstruction breaks the beam while the door/gate is closing, the operator will stop and typically 
reverse to the full open position.
The sensor must be installed so that it faces the refl ector across the entrapment zone, no more than 
6" (15 cm) above the fl oor for a door and no more than 27.5" (69.6 cm) above grade for a gate. Minimum 
installation width of 5 feet and maximum width of 50 feet. The devices can either be installed on the left or right 
of the entrapment zone.
The brackets must be securely fastened to a solid surface such as the wall framing. If installing in masonry 
construction, add a piece of wood at each location to avoid drilling extra holes in masonry if repositioning is 
necessary. 
The invisible light beam path must be unobstructed. No part of the gate or door (or door tracks, springs, 
hinges, rollers or other hardware) may interrupt the beam while the door/gate is closing.

CARTON INVENTORY

Photoelectric Sensor. . . . . . . . . . . . . . . . . . . . . . . (1)
Mounting Brackets  . . . . . . . . . . . . . . . . . . . . . . . . (2)
Refl ectors  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . (2)

Refl ectors Support Bracket . . . . . . . . . . . . . . . . . . (1)
Installation Instruction  . . . . . . . . . . . . . . . . . . . . . (1) 
Self-tapping Screws  . . . . . . . . . . . . . . . . . . . . . . . (4)

To prevent possible SERIOUS INJURY or DEATH from a closing door or gate:

•   Be sure to DISCONNECT POWER to the operator BEFORE installing the photoelectric sensor.

•   The door or gate MUST be in the fully opened or closed position BEFORE installing the LiftMaster

®

 

Monitored Entrapment Protection device.

•   Correctly connect and align the photoelectric sensor.

•   Install the photoelectric sensor beam NO HIGHER than 6" (15 cm) above the fl oor for door and 

27.5" (69.8 cm) above grade for gate operators.

•   LiftMaster

®

 Monitored Entrapment Protection devices are for use with LiftMaster

®

 Commercial Door 

and Gate Operators ONLY. Use with ANY other product voids the warranty.

•   Entrapment protection devices MUST be installed per the operator owner's manual for each Entrapment 

Zone. 

LIFTMASTER

®

 

PROTECTOR SYSTEM

MODELS CPS-RPEN4 AND CPS-RPEN4GM

Summary of Contents for CPS-RPEN4

Page 1: ...aximum width of 50 feet The devices can either be installed on the left or right of the entrapment zone The brackets must be securely fastened to a solid surface such as the wall framing If installing in masonry construction add a piece of wood at each location to avoid drilling extra holes in masonry if repositioning is necessary The invisible light beam path must be unobstructed No part of the g...

Page 2: ...ATE APPLICATION MODEL CPS RPEN4GM SLIDE GATE ENTRAPMENT ZONES Photoelectric Sensor Photoelectric Sensor Photoelectric Sensor Photoelectric Sensor Reflector Reflector Reflector Reflector 6 15 cm max above the floor and away from the door Facing the door from inside the building installation procedures are the same for all door types Photoelectric Sensor Reflector Invisible Light Beam Protection Area Entr...

Page 3: ...s not recommended 2 Slide the photoelectric sensor and the reflector onto the mounting brackets and secure with self tapping screws provided WALL MOUNT Hardware Not provided 6 6 6 Hardware Not provided FLOOR MOUNT Hardware Not provided DIRECT MOUNT WITHOUT MOUNTING BRACKET WALL MOUNT FLOOR MOUNT Photoelectric Sensor Photoelectric Sensor Reflector Reflector ...

Page 4: ...receiving a 1 2 thread conduit Connect the photoelectric sensor as illustrated below for your operator type The wiring is polarity sensitive so make certain to wire as indicated below TTC 24VAC 24VAC LMEP EDGE OPEN CLOSE MAS COMMON TIMER DEFEAT POWER TIMER ENABLE 3 3 PHASE 1 PHASE Blue Brown LOGIC 4 Control Board D14 COM INTRLK STOP LED OPEN CLOSE TTC LEARN 1 LMEP1 LMEP2 2 3 4 5 6 7 STOP CLOSE OPE...

Page 5: ...ll or Fence GATE APPLICATION INSTALLATION Install the photoelectric sensors and reflector up to 5 12 7 cm maximum from the gate 1 Assemble reflector 2 Slide the photoelectric sensor and the reflector onto the mounting brackets and secure with self tapping screws provided Photoelectric Sensor Reflector ...

Page 6: ...NT WITH BRACKET PROVIDED Hardware Not provided Hardware Not provided 3 Attach mounting bracket to solid surface with hardware not provided Hardware Not provided Hardware Not provided 27 5 maximum above grade 27 5 maximum above grade 27 5 maximum above grade 27 5 maximum above grade 27 5 maximum above grade 27 5 maximum above grade GROUND GROUND GROUND GROUND GROUND GROUND ...

Page 7: ...ated below for your operator type The wiring is polarity sensitive connect the BLUE wire to the terminal and the BROWN wire to the terminal MODELS LA412 RSW12V AND RSL12V SERIES MODELS CSL24V SERIES AND CSW24V SERIES Sensor for CLOSE cycle Sensor for OPEN cycle Control Board Control Board Sensor for CLOSE cycle Sensor for OPEN cycle Sensor for OPEN cycle MODEL LA500 SERIES MODEL LA400 SERIES Contr...

Page 8: ... should not move Now remove the obstruction and give the operator a close command The door should close and when the path of the photoelectric sensor is obstructed the door should reverse Gate installations The photoelectric sensor can be installed to work on either the open or closing cycles Refer to the gate operator installation manual for more information Symptom Cause Resolution No alignment ...

Page 9: ...re installés à gauche ou à droite de la zone de piégeage Les supports doivent être bien vissés à une surface solide comme la charpente d un mur Si la pose se fait dans une construction en maçonnerie ajouter un morceau de bois à chaque endroit pour éviter de percer des trous supplémentaires dans la maçonnerie si un repositionnement est nécessaire Il ne doit y avoir aucun obstacle dans le rayon du f...

Page 10: ... e ZONES DE PIÉGEAGE DE PORTAIL PIVOTANT APPLICATION POUR PORTAIL MODÈLE CPS RPEN4GM ZONES DE PIÉGEAGE DE PORTAIL COULISSANT 6 po 15 cm max au dessus du sol et à l écart de la porte 6 po 15 cm max au dessus du sol et à l écart de la porte Faisant face à la porte depuis l intérieur de l immeuble les directives d installation sont les mêmes pour tous les types de porte Capteur photoélectrique Capteu...

Page 11: ...ommandé 2 Faire glisser le capteur photoélectrique et le réflecteur sur les supports de montage et les fixer avec les vis autotaraudeuses fournies à cet effet Visserie non fournie Visserie non fournie Visserie non fournie 6 po 6 po 6 po MONTAGE DIRECT SANS SUPPORT DE MONTAGE MONTAGE AU MUR MONTAGE AU SOL Capteur photoélectrique Capteur photoélectrique Réflecteur Réflecteur MONTAGE AU MUR MONTAGE AU SO...

Page 12: ... recevoir une conduite filetée de 1 2 po Connecter le capteur photoélectrique comme illustré ci dessous pour votre type d actionneur Le câblage est sensible à la polarité S assurer que le câblage est installé comme indiqué ci dessous TTC 24VAC 24VAC LMEP EDGE OPEN CLOSE MAS COMMON TIMER DEFEAT POWER TIMER ENABLE 3 3 PHASE 1 PHASE Bleu Marron LOGIC 4 Tableau de commande D14 COM INTRLK STOP LED OPEN ...

Page 13: ...TALLATION Installer les capteurs photoélectriques et le réflecteur à une distance maximale de 5 po 12 7 cm du portail 1 Assembler le réflecteur 2 Faire glisser le capteur photoélectrique et le réflecteur sur les supports de montage et les fixer avec les vis autotaraudeuses fournies à cet effet Capteur photoélectrique Réflecteur Capteur photoélectrique ...

Page 14: ...isserie non fournie 27 5 po 69 8 cm au dessus du sol 27 5 po 69 8 cm au dessus du sol 27 5 po 69 8 cm au dessus du sol 27 5 po 69 8 cm au dessus du sol 27 5 po 69 8 cm au dessus du sol 27 5 po 69 8 cm au dessus du sol SOL SOL SOL SOL SOL SOL Visserie non fournie Visserie non fournie Réflecteur Capteur photoélectrique Capteur photoélectrique Visserie non fournie Visserie non fournie Réflecteur ...

Page 15: ...pour le type d actionneur Le câblage est sensible à la polarité connecter le câble BLEU à la borne et le câble MARRON à la borne MODÈLES DE SÉRIES LA412 RSW12V ET RSL12V MODÈLES DE SÉRIES CSL24V ET CSW24V Capteur pour cycle FERMÉ Capteur pour cycle OUVERT MODÈLE DE SÉRIE LA500 MODÈLE DE SÉRIE LA400 Capteur pour cycle FERMÉ Capteur pour cycle FERMÉ Capteur pour cycle FERMÉ Capteur pour cycle OUVERT...

Page 16: ...r à l actionneur une commande de fermeture La porte devrait se fermer et lorsqu un obstacle se trouve dans le rayon du capteur photoélectrique la porte devrait inverser sa course Installations pour portail Le capteur photoélectrique peut être installé de manière à fonctionner sur les cycles d ouverture ou de fermeture Consulter le manuel d installation de l actionneur du portail pour plus d inform...

Reviews: