INSTALLATION MANUAL

 

BX-246

AUTOMATION 

FOR SLIDING GATES

 English

EN

119BU50EN

Summary of Contents for BX-246

Page 1: ...INSTALLATION MANUAL BX 246 AUTOMATION FOR SLIDING GATES English EN 119BU50EN ...

Page 2: ...e is no vegetation in the area of operation of the photocells and that there are no obstacles in the area of operation of the operator Do not allow children to play with the fixed command devices or in the gate s area of operation Keep any remote control devices i e transmitters or any control devices away from children as well to prevent the operator from being activated accidentally The operator ...

Page 3: ...IS ONLY FOR PROFESSIONAL OR QUALIFIED INSTALLERS 2 2 Limitations to use This product is engineered and manufactured by CAME CANCELLI AUTOMATICI S p A in compliance with current safety standards The operator is made of a cast aluminium part inside of which operates the irreversible electromechanical gearmotor and an ABS plastic lining which holds the electronic card transformer and the clamp to hou...

Page 4: ... any irregularities that may obstruct the gate s movement The upper guide rails must not create any friction Make sure that there is a closing and an opening endstops Make sure that the operator is attached to a solid surface and protected from any impacts Make sure you have a suitable omnipolar cut off device with contacts more than 3 mm apart and independent sectioned off power supply Check that...

Page 5: ...al loads the sizes given on the table must be re evaluated based on actual power draw and distances When connecting products that are not specified in this manual please follow the documentation provided with said products 5 3 Cable list and minimum thickness Connection Type of cable Length of cable 1 10 m Length of cable 10 20 m Length of cable 20 30 m Control panel power supply 230V FROR CEI 20 ...

Page 6: ...xamples as the space for installing the ratiomotor and accessories varies according to obstructions It is thus up to the system installer to select the most suitable solution Shunt pit 5 5 Securing the plate and installing the assembly Conduits for electric cables Prepare the securing plate insert the bolts into the holes and lock them using the supplied nuts and washers Extract the preformed brac...

Page 7: ...NGLISH To position the plate in relation to the rack please see the measurements on the diagram Fill the form box with cement and wait for at least 24 hours for it to solidify Remove the form box fill the pit around the cement block with soil Unbolt the nuts and washers from the bolts The securing plate must be clean perfectly aligned and with the bolt threads completely on the surface Insert the e...

Page 8: ...e cable shafts Lift the gearmotor from the securing plate by about 5 to 10mm by using the threaded steel levelling feet to allow any later adjustments between the pinion and the rack The following illustrations for the securing the rack are just examples of applications It is up to the installer to choose the best solution Releasing the gearmotor see paragraph on manual release Rest the rack on th...

Page 9: ...gate manually and register the pinion to rack distance using the threaded steel levelling feet for vertical adjusting and the slotted holes horizontal adjusting This prevents the weight of the gate from bearing on the operator Once adjustments are finished secure the assembly using the nuts and washers Insert the cover after performing the adjustments and settings on the electronic card Levelling f...

Page 10: ...obed key into the lock push it in and turn it clockwise 5 6 Mounting the endstop fins Place the endstop fins onto the rack and secure them using a 3 mm Allen wrench Their positioning limits the gate run Note the gate schould not slam against the mechanical stop when opening or closing Mechanical stop WARNING opening the door will disengage the motor i e it will not function To operate the motor the...

Page 11: ...he accessories cannot exceed 37W of overall power The card is fitted with an amperometric device which constantly monitors the motor s drive When the gate runs into an obstacle the amperometric sensor immediately detects the overload on the drive and so inverts the gate s movement opens it if it is closing closes it if it is opening Warning after 3 obstacle detections the gate stops when in opening...

Page 12: ...change at any time and without obligation on CAME cancelli automatici s p a to notify users ENGLISH Orange Orange White Red Black Red White Red 6 3 Electrical connections 24 V DC motor with encoder Closing microswitch Gearmotor endstop and encoder Modifications to the electrical connections for right hand installations Invert the gearmotor U V and FA FC endstop phases Opening microswitch Descripti...

Page 13: ...arth Open gate status light contact range 24V 3W max Signal that gate is open turns off when gate is closed Movement flashing light Contact range 24V 25W max Flashes during the gate s opening and closing phases Stop button N C contact Gate stop button Excludes automatic closing For motion to resume press the command button or the remote control button Key selector and or command button N O contact ...

Page 14: ... N C contact for re open during closing phase Input for EN 12978 standard compliant safety devices such as photocells If contact is opened while gate is closing the gate inverts its direction partial stop N C contact Input for EN 12978 standard compliant safety devices such as photocells Gate stops if moving and automatically shuts if this functions has been selected DIR DELTAS photocells DIR DELT...

Page 15: ...edges During gate opening opening the contact causes inversion of movement until gate is fully close if not used short circuit contact 2 C8 DF with DFI con nections monitor card At each open close command the card check the photocells efficiency Any problems with the photocells will cause the PROG Led to flash on the electronic card which cancels any commands from the radio transmitter or push butt...

Page 16: ...ncy of any safety devices i e photocells after every opening or closing command 8 OFF Total stop This function stops the gate and then excludes any automatic closing cycle to set in motion again use either the keypad or transmitter Insert the safety device in 1 2 If unused set DIP switch to ON 9 OFF Opening during closing If the photocells detect an obstacle during gate s closing gate motion is in...

Page 17: ...ed 1 Yellow led Normally off Shows activation of the PARTIAL STOP button 3p Yellow Led indicator Normally off Indicates that the PARTIAL OPENING button has been activated 7 Yellow Led indicator Normally off Indicates that the OPENING and CLOSING button has been activated C1 Yellow led Normally off Shows that there are obstacles between the photocells which are in OPEN WHILE CLOSING mode C3 Yellow ...

Page 18: ...p a to notify users ENGLISH 10 Programmation to save gate run and decelerations adjustments Do the adjustment by making the operator execute a complete opening closing manoeuvre The control board automatically registers the gate run adjustments with opening and closing decelerations To save the adjustment position dip 6 in ON and press CH1 button until the signalling led stays on Re position the d...

Page 19: ... the radio control Possible output of the radio receiver s second channel NO contact Contact rated for 5A 24V DC Connect the antenna s RG58 cable Cut off the main power supply and remove any batteries Fit the AF board onto the electronic board The electronic board recognizes the AF board only when the operator is powered up again Keep the CH1 button on the electronic board pressed the warning LED ...

Page 20: ...ill close only in automatic closing mode Coordinate the direction of travel of the two gearmotors and by modifying the motor s rotation invert the cables on terminals FA FC and M N Make the electrical connections only on the motor s control board 12 Connecting two coupled gearmotors having a single control Whereas the adjustments and features must be made on both boards Connect the two boards toge...

Page 21: ...g the operator immediately Danger of crushing hands Danger of crushing feet Danger High voltage No transit during operation Important safety instructions 14 Maintenance 14 1 Periodic maintenance Periodic maintenance to be carried out by the end user is as follows wipe clean the glass surface of the photocells check that the safety devices work properly remove any obstructions We suggest checking t...

Page 22: ...ither stuck or broken The opening closing button or the key selector are stuck Fhotocells in partial stop mode Check that the power is up Call assistance Replace batteries Call assistance Call assistance Call assistance Call assistance The gate opens but will not close The photocells are engaged Sensitive edge triggered Check that photocells are clean and in good working order Call assistance The ...

Page 23: ...matter DO NOT DISPOSE OF IN NATURE Installer s stamp Operator name Date of job Technician s signature Requester s signature Job performed ____________________________________________________________________________ ______________________________________________________________________________________ ______________________________________________________________________________________ Installer s...

Page 24: ...ver het bedrijf de producten en hulp in uw eigen taal PT Para toda e qualquer informação acerca da empresa de produtos e assistência técnica em sua língua PL Wszystkie inne informacje dotyczące firmy produktów oraz usług i pomocy technicznej w Waszym języku znajdują się na stronie RU Для получения дополнительной информации о компании продукции и сервисной поддержке на вашем языке HU A vállalatra te...