FIRE AND ALARM CONSOLE 

S2000M

 

 

Maintenance guide 

Summary of Contents for S2000M

Page 1: ...FIRE AND ALARM CONSOLE S2000M Maintenance guide ...

Page 2: ... 30 2 1 7 6 Entry zone settings 31 2 1 7 7 Setting user messages 31 2 1 7 8 Controlling S2000 BI devices settings 31 2 1 7 9 Using the console for creating of systems controlling gas powder or aerosol fire extinguishing installations based on S2000 ASPT devices 32 2 1 7 10 Using the console with sprinkler or drencher extinguishing units based on devices POTOK 3N 33 2 1 7 11 Using the console with ...

Page 3: ...rogramming 47 2 2 4 4 Console extra settings 48 2 2 4 5 Password management 49 2 2 4 6 Console address setting in prorgamming mode 51 2 2 4 7 Console address setting in personal computer work mode 51 2 2 4 8 Console RS 232 interface operative mode settings 51 2 2 4 9 The ring RS 485 interface operative mode settings 52 2 2 4 10 Console entering into programming mode 53 2 2 5 Reset settings to defa...

Page 4: ...commands through RS 485 interface Controller S2000 KDL analyzes the state of addressable detectors and connected via 2 wire addressable communication line expanders transmits the status information to the console and allows to arm disarm them by console command Keyboard S2000 K is design for additional partition control points and word under console control It also allows displaying transmitted by...

Page 5: ...ay use S2000 BI devices for partitions state indication 1 1 9 Console synchronizes time and date in devices It is necessary for normal time window operability in S2000 4 and S2000 2 devices Console provides connection between S2000 2 device It is necessary for normal operability network Anti pass back mode second passing prohibition in access control system on the basis of S2000 2 devices 1 1 10 C...

Page 6: ...and addres notificators Obligatory condition these loops should be saved in console database It has to be set message name console message receiving sound signal alarm level and has message to the one of the categories Message title is an arbitrary text line with length up to 16 symbols Sound signal is settled by selection from list of standard signals Alarm level determines message displaying pri...

Page 7: ...p Console has three default access levels for device control ARM and DISARM ARM w o DISARM MAX AUTHORITY Access level ARM w o DISARM gives the right for alarm loop individual or group arming and also alarm reset and alarm loop state request Access level ARM and DISARM gives also the right for alarm loop individual or group arming and disarming Access level MAX AUTHORITY has all control functions r...

Page 8: ...state Content Norm Notificator off Button pressed Short sound signal Notificator is off if alarm was on Successful operation Two short signals signal Confirmation Unsuccessful operation Long sound signal signal Error Intrusion alarm or Silent alarm messages are received Sound signal Alarm interrupted sound signal with signal duration approximately equal to the pause duration Fire prealarm message ...

Page 9: ...m or Fire alarm ON for a time else OFF output 4 Off for a time If Intrusion alarm or Fire alarm OFF for a time else ON output 5 Blinking Normal state OFF If Intrusion alarm or Fire alarm blink 0 5 s ON 0 5 s OFF else OFF output 6 Blinking Normal state ON If Intrusion alarm or Fire alarm blink 0 5 s ON 0 5 s OFF else ON output 7 Blinking for a time Normal state OFF If Intrusion alarm or Fire alarm ...

Page 10: ...output 2 If all zones are armed or disarmed then ON else OFF output 17 Turn on for a given time before arming If at least one zone is in Arming delay state then ON for a given time else OFF output 18 Turn off for a given time before arming If at least one zone is in Arming delay state then OFF for a given time else ON output 19 Turn on for a given time when arming If at least one zone is armed the...

Page 11: ...if at least two zones in partition have Fire alarm status and there are no zones having states Auxiliary alarm Relay disconnected Open relay output Relay output short circuit When the failure removed the relay output will not be on 35 ASPT A1 ON for a given time if at least one zone in partition have Fire alarm status and there are no zones having states Auxiliary alarm Relay disconnected Open rel...

Page 12: ...as the maximum value being equal 8191 875 second 4 Programs 11 33 34 and 35 are designed to control the fire automatic equipment including autoextinguishing devices According to the autoextinguishing systems requirements one can activated the extinguishing equipment on premises when there is fire alarm in two independent fire alarm loops checking this premises To avoid the leak of extinguishing co...

Page 13: ...eset when arming To do this the detectors are powered through normally closed contact of S2000 SP1 device relay output This output is given by the executive program 17 and control time sufficient to reset detectors For 4 wired detectors alarm loops the arming delay is to be given Arming delay must be more then the sum of resetting time and maximum restore time of detectors after power reset As a r...

Page 14: ...et of console S2000M Name Quantity Note Check and control fire alarm S2000M console 1 Check and control fire alarm S2000M console Maintenance guide 1 Screw with 1 3х20 016 3 Dowel 8х35 3 Printer cable 1 Supplied for additional price Personal computer communication cable 1 Supplied for additional price 1 4 Description the product and capabilities 1 4 1 Console has the plastic case The printed circu...

Page 15: ...I S2000 IТ or S2000 2 Printer printing device with serial interface RS 232 e g Epson LX 300 or LX 300 1 printer connection cable Power supply DC power supply from 10 2 to 28 4 V current supply no more than 150мА Figure 1 Typical maintenance connection S2000M console circuit Attention On the console board there is 5 pin auxiliary slot It is prohibited to set pin tampers or shortly connect the pins ...

Page 16: ... S2000 4 S2000 SP1 or resistor 620 Ohm between contacts A and B for S2000 S2000 K and S2000 KS At all other devices jumpers should be removed S2000M console can be set at any place in the RS 485 line If it is first or last device in the line then between contacts A and B matching resistor 620 Ohm need to be set Branches in the line are not undesirable because they increase reflection signal in the...

Page 17: ...m panel IP UPS 12V 24V 620 Om PKU PKP PKP PKP 620 Ом below 3000 m IP IP IP IP RS 485 A RS 485 B 0 V Figure 2 Device RS 485 interface connection circuit PKU console S2000M PKP alarm panel P interface repeater PKU P P Below 2000 m Below 2000 m Below 2000 m IP IP PKP PKP PKP PKP PKP PKP R R R R R R IP power supplier R matching resistance 620 Ohm Figure 3 Extend line length with the help of RS 485 int...

Page 18: ...unstable For example if transmission equipment imports delay 3 ms then S2000M console receive reply from device more then 6 ms after request Because console waits reply from device no more 5 ms device will not be detected To solve these problems few connection parameters made customizable There are standby time at duty cycle poll device search at command and set of customizable delays before trans...

Page 19: ...2 4 3 Figure 5 S2000 console connection circuit It is configured by personal computer through RS 232 interface Also it is shown using it as RS 232 RS 485 interface converter 2 1 5 Printer connection to console or ARM S2000 If console is used with printer the last one has to be set for next parameters according instruction Description Setting name in LX 300 Value in LX 300 Interface type I F mode S...

Page 20: ...format Program can work periodically to read messages from S2000 console It is possible S2000 has buffer for 1023 events Connection console to personal computer with ARM S2000 is shown on the Figure 5 In program ARM S2000 S2000 1 2х source message and address should be set By perforce console address can be changed see item 2 2 4 7 Attention For work with S2000M consoles of version 1 20 ARM S2000 ...

Page 21: ... way set the RS 232 operating mode to the S2000 PC value and give the switching delay as described in section 2 2 4 8 It is recommended to set the switching delay at least 60 seconds Two above switching ways are just alike in terms of capabilities Their benefits in comparison with each other are as follows switching by means of S2000 SP1 switching from S2000 PC mode 1 The galvanic isolation is lik...

Page 22: ... to the S2000 PC value and give the switching delay 3 Active console The console is directly connected to the computer via RS 232 interface with the the devices being connected to the console through RS 485 interface The console monitors all the devices and gets their states with the computer polling the concole or consoles and getting the device operative information Both the console and the comp...

Page 23: ...he RS 485 interface line by their RS 232 outputs via S2000 PI convertors The devices are connected to the RS 485 outputs of consoles Figure 7 displayes the way of connecting several S2000M consoles to the computer In addition to the capability of several consoles the S2000 PI convertors provides the galvanic isolation between the PC and the console When ARM Orion reserving by several consoles the ...

Page 24: ...yboard yello white brow gree 1 1 2 3 A B 0 В XT3 ISOLATED S2000 PI RS 485 To consoles RS 485 To devices 1 2 3 4 GND TxD RxD 5 В XT5 1 2 3 A B 0 В XT3 ISOLATED S2000 PI 7 6 5 GND DTR TxD XT1 3 3 4 1 A B 0 В S2000М 2 U XT1 2 XT1 1 Uп 1 2 GND XT1 BP subsystem 1 subsystem 2 To all subsystems Figure 7 Connection of several S2000M to the PC with ARM Orion with galvanic isolation of interface RS 485 diag...

Page 25: ...necessary to enter engineer password To write configuration in the file select command Save or Save as in File menu or press button Save configuration file Configuration can be saved in text or encrypted file Edited configuration can be saved in a file loaded from a file written to the console nonvolatile memory or read from the console memory To write or read the configuration S2000M console has ...

Page 26: ...t off the power of the console or exit from programming mode If it is happened writing operation has to be repeated S2000М COM PC A B XT1 2 3 4 PC computer PI interface converter RS 232 RS 485 for example PI PI GR S2000 PI S2000М S2000M alarm console RS 485 A RS 485 B PI RS 485 To devices Figure 8 S2000M connection for configuration by personal computer through RS 485 interface Configuration creat...

Page 27: ...ve marking If it reguires to drag all device zones into the partition one can drag the device itself from device tree Zones can be assigned with the text description Select the reguired zone in Device zones window and click the Description line in Inspector window Enter the text string up to 16 symbols Partitions can be integrated into groups There can be created up to 128 partition groups To crea...

Page 28: ... window Partitions in selected level of top window Authority levels The partition will be added in the authority level partition list Selected partition in the inspector s window control privilegies of the partition can be set enabling or denying arm or disarm Adding and editing of passwords are made on the Passwords tab of program pprog exe At password setting user number password type code value...

Page 29: ...uts it is necessary select physical relays device address and relay number in device which will be used for system control Determine partitions that controlled by relay s state connect relay and partition Determine relay state dependence from state of connected partitions select control program These settings are run by program pprog exe when console configured Control program number is selected a...

Page 30: ...sages can be transmitted to S2000 IT phone informators Messages should not sent to the other devices because they are not needed them for work and delay system operability For setting events transition to the devices select the devices which will receive messages from the console Messages can be sent independently translation to the address or like broadcast message to all devices at once common t...

Page 31: ... are determined in scripts Rename script for each standard message gives new name sound signal alarm level and category Script allows rename up to 4 standard messages Console allows create up to 32 rename scripts Script can be set for any alarm loop or few ALs from console database If loop rename script is set then standard messages of the loop will be replaced to user defined messages if such rep...

Page 32: ...2 03 and above along with S2000М console The controlling of S2000 ASPT devices with versions less than 2 00 is limited by automatic launching control mode and remote launch in local control mode only out of partitions Such control doesn t require the configuring of the console and described in section 2 2 3 4 All zones of S2000 ASPT loops inner zones and output circuits should be combined into one...

Page 33: ... designed to display only one area of fire extinguishing The extinguishing area is represented by the pump station one or two duty pumps standby pump and jockey pump Create the partition for pump station and one partition for each pump when configuring the console Include Potok 3N device zones controlling the status of pump station into the pump station partition and zones controlling the status o...

Page 34: ...device detection and other messages It is recommended to change setup password because user can get unauthorized access to program functions One or several user device control passwords have to be given see item 2 2 4 5 To set the modes it is required to set the parameters ALARM SOUND and CODES REQUIRED ALARM SOUND parameter needs to be on if inner sound annunciator messages should be alarmed othe...

Page 35: ...e shows text description of partition and loop If partition has not text description when key 2 pressed panel show partition number device address and alarm loop number When keys 3 pressed console shows user name if text user password description is not given console show its database number when key 3 pressed Pressing key 9 Message number in console buffer can be shown The last message has number...

Page 36: ...key 3 user name who arm partition can be seen At pressure key 1 ARMED PART 100 U 80 where 100 is partition number 80 is user number Printer 20 12 18 26 59 ARMED PART 10 S1 100 Corridor 1 floor Administrator partition 100 Corridor 1 floor armed 20 December at 18 hours 26 minutes 59 seconds at reader 1 at device with address 10 by user Administrator Receiving device message console displays it on LC...

Page 37: ...d or Touch Memory key or Proximity card protected If password is correct and its owner has control privilegies console saves USER S CODE ENTR message in the buffer and gives the user available access according with 2 2 2 1 2 2 2 3 items of this manual If the password is not recognized the ILLEGAL CODE message is saved in event buffer If the password entered has no required autrority level ACCESS D...

Page 38: ...es of partition press TRBL The console will display the partition descriptor name or the number if no named in the first line and its state of highest priority Press 4 for scrolling and showing the list of states in decreasing priority order Press 3 to return the previous entry Use 4 and 3 and press ENT to display all zones with such state for example with the state Intrusion alarm Use 4 and 3 key...

Page 39: ... functions This control functions are destined for manual remote control by loops and alarm panel outputs arming disarming alarm reset and so on They are available by user which has control rights W O PART CONTROL ARM and DISARM ARM w o DISARM or MAX AUTHORITY In order to get access to control functions press ENT and input password If password is correct console forms message USER S CODE ENTR and ...

Page 40: ...ess valid value from 1 to 127 or select valid address value by 4 3 keys and press ENT Common arming Type password Select ARM menu item by 4 3 and ENT keys or press hot key 1 Select ARM ALL menu item by 4 3 and ENT keys or press hot key 3 Enter device address valid value from 1 to 127 or select valid address value by 4 3 keys and press ENT Single loop disarming Type password Select DISARM menu item...

Page 41: ...value from 1 to 127 or select valid address value by 4 3 keys and press ENT 2 2 3 3 Manual external device outputs control Manual relay or open collector type outputs controlling given by sertain programs are realized as follows Type password Select MANUAL CONTROL menu item by 4 3 and ENT keys or press hot key 4 Select RELAY menu item by 4 3 and ENT keys or press hot key 1 for quick transition Ent...

Page 42: ...rent launching mode In this example S2000 ASPT controls the fire extinguishing equipment in manual mode Press ENT to select launching mode Select launching mode AUTO or MANUAL by 4 and 3 keys then press ENT If command has succeeded panel displays new launching mode In this example S2000 ASPT was switched to AUTO mode Extinguish equipment manual launch Type password Select MANUAL CONTROL menu item ...

Page 43: ...loop number state In this example selected loop has ARM FAILED state Each 0 5 seconds the console automatically reguests state of selected alarm loop Use the 4 3 keys to view states of other loops of selected device The loop states are described in appendix B 2 2 3 6 Alarm loop resistance measurement This command allows estimating loop resistance value device power voltage the temperature or smoki...

Page 44: ...2 0 kOhm to 6 0 kOhm Normal range for alarm loop type 4 is from 2 0 kOhm to 11 0 kOhm б Correspondence between loop resistance and S2000 4 ADC device value alarm loop resistance 0 1 kOhm 2 kOhm 4 7 kOhm 6 kOhm 10 kOhm 16 kOhm Open ADC value for S2000 4 255 140 93 49 40 25 16 0 ADC value for S2000 4 01 255 229 153 81 66 42 27 0 This table can be found in maintenance guide of S2000 4 device Normal r...

Page 45: ... message transition speed is higher then phone line message transition one message buffer of S2000 IT can be overflowed in short time Normally emptying of buffer can take a long time Console can send command to empty message buffer without event transition through phone line Type password Select AUX FUNCTIONS menu item by 4 3 and ENT keys or press hot key 6 Select CLR COMM MSG menu item by 4 3 and...

Page 46: ...etting and clock correction setting console date changing device network address programming and changing addresses of 2 wire devices setting console parameters password setting personal computer programming 2 2 4 1 Date and time settings and clock correction Time setting Enter the programming menu press button PRG Type engineer password Select CLOCK SETUP menu item by 4 3 and ENT keys or press ho...

Page 47: ...ire devices addresses changing 2 wire devices address can be changed in case of it is known Enter in programming menu press button PRG Type engineer password Select ADDRESSES menu item by 4 3 and ENT keys or press hot key 3 Select 2 WIRE DEVICES menu item by 4 3 and ENT keys or press hot key 2 Select CHANGE ADDRESS menu item by 4 3 and press ENT Enter S2000 KDL address valid value from 1 to 127 or...

Page 48: ... command LCD will displays message ADDR PROGRAMM S2000 KDL enter the address programming mode Press CLR to cancel address programming To programming 2 wire device address make all reguired steps described in device maintenance guide The device address having set S2000 KDL automaticalle exit address programming mode the console makes sound signal Success and displays messages about device states If...

Page 49: ...er MAX PASSWORD press ENT input new value and finish input by pressing ENT button This example demonstrate default parameter values 2 2 4 5 Password management Password management includes adding new passwords changing and removing available passwords Note 1 Engineer password password number 1 can be only changed 2 If password already exists the password with the same number cannot be added 3 Seve...

Page 50: ...ration Valid values are from 1 to 252 Authority level settings are described in the item 2 1 7 3 Console allows password programming as PIN codes Touch Memory keys or Proximity cards Touch Memory keys and Proximity cards are entered from Touch Memory or Proximity readers connected to S2000 4 or S2000 2 device identically to the procedure described above replacing symbol typing by key touching or c...

Page 51: ...ect RS485 SETTINGS menu item by 4 3 keys and press ENT or press hot key 4 Select S2000 ADDR menu item by 4 and 3 keys To change address press ENT type new value and press ENT 2 2 4 7 Console address setting in personal computer work mode Console address in this mode is the address for polling by ARM S2000 and ARM Orion Pro programs Enter to programming menu press button PRG Type engineer password ...

Page 52: ...resense analysis was made If computer fails after this period READY indicator will blink see table 1 Give console address to work in the S2000 PC mode To work in the mode S2000 PC transition delay in active mode from interface conversion mode at personal computer turn off parameter PC TIMEOUT in menu RS232 SETTINGS need to be set Delay is given in the seconds in range from 0 to 255 seconds Default...

Page 53: ...amming mode console database is configured at personal computer with pprog exe program Press button PRG Type engineer password Select SETTINGS menu item by 4 3 and ENT keys or press hot key 5 Select RS232 SETTINGS menu item by 4 3 keys and press ENT or press hot key 6 When LCD displays PROGRAMMING MODE the console enter the remote programming mode through RS 485 or RS 232 interfaces To exit from p...

Page 54: ... console version 2 04 and possible some other devices connected through RS 485 interface Select it from detected device list and press PRG Open file with console libraries Program displays list of versions for given console device Select required version and press Write key After few seconds program prepare data for writing and write new firmware Write operation console has to shows FIRMWARE LOADI...

Page 55: ... in materials and workmanship for 18 months since putting in to operation but no more then 24 months since production under normal use and service S2000M fire and alarm console _ __________________________ Product designation serial number produced tested by quality control department in compliance with state standards and specifications and packed by NVP BOLID company Q C STAMP __________________...

Page 56: ...FIRE AND ALARM CONSOLE 56 Appendix A S2000M console dimensions ...

Page 57: ...been detected LNCH FAULT LAUNCHING DELAY The condition for launching of fire extinguishing equipment has met and launching delay is being counted LNCH DELAY LAUNCH BLOCKED The launching of fire extinguishing equipment was blocked up e g due to the door opening to the protected area LNCH BLOCK LAUNCH CANCEL The launching of fire extinguishing equipment was canceled e g due to the command Cancel ext...

Page 58: ...e line and controlled zone in question has been lost DISCONNECT CONFIGURATION ERROR Type mismatch of 2 wire line connected addressable device and value given in S2000 KDL configuration or mismatch of zone type and type of device connected to S2000 KDL CONFIG ERR FIRE TROUBLE Fire alarm system failure such as addressable device internal problem failure of DIP 34А optical system or S2000 KPB device ...

Page 59: ...TO EXTINGUISHING The automatically launching mode of extinguishing equipment is on EX AUTO AUXILIARY ALARM Auxiliary alarm loop is broken AUX ALARM AUXILIARE NORMAL Auxiliary alarm loop is OK is not broken AUX NORM RELAY DISCONNECTED The communication between the console and relay output has been lost with it status being unknown and the console controlling being disabled It is typically happens w...

Page 60: ... HIGH LOW TEMPERATURE The temperature is under temperature low threshold for temperature zone of S2000 KDL Tº LOW NORMAL TEMPERATURE The temperature is within preset range for temperature zone of S2000 KDL Tº NORM NORMAL OUTPUT Output circuit being controlled is normal operative RELAY NORM NORMAL POWER The device power supply is OK POWER NORM NORMAL AC AC power supply 220 V is OK AC NORM NORMAL BA...

Page 61: ...he command Cancel extinguish given from console or to the pressing RESET key of S2000 ASPT LAUNCH CANCEL 1 Fire alarm FIRE ALARM 1 Fire signal has been received and fire alarm is probable FIRE PREALARM 1 Intrusion alarm INTRUSION ALARM 2 Silent zone alarm SILENT ALARM 2 Entry zone alarm ENTRY ALARM 2 Open circuit failure in the alarm loop LOOP TRBL OPEN 3 Short circuit in the alarm loop LOOP TRBL ...

Page 62: ... FAILURE 8 Fire conditions have been detected FIRE SIGNAL 8 The service is required for the detector for example the smoke chamber of DIP 34A detector is dusted SERVICE REQUIRED 8 Temperature has exceeded the maximum value TEMPERATURE HIGH 8 Temperature has fallen below the minimum value TEMPERATURE LOW 8 Temperature has normal value TEMPERATURE NORM 8 The heat sensor failure has detected HEAT SEN...

Page 63: ...prohibited ACCESS CLOSED 6 Access control is deactivated ACCESS FREE MODE 6 Access control is activated ACCESS NORM MODE 6 Door is opened too long DOOR LEFT OPEN 6 Door is closed after blocking in open state DOOR CLOSED 6 Door has been opened without access granting DOOR FORCED 6 Depending on indicated device this message means either entering to the programming menu or to the password changing mo...

Page 64: ...FIRE AND ALARM CONSOLE 64 Event categories 5 ZONE ARM DISARM 1 FIRES 6 ACCESS 2 ALARMS 7 RELAY 3 FAULTS 8 SYSTEM INFO 4 ARM DISARM 9 AUXILIARY ...