MODEL: 
 
TCP4000-H090

 

AC INPUT:  

 
 
 

Note 

 3 PHASE 

VOLTAGE: 115

277V / 200

480V, 3W + PE 

CURRENT: 12 

 5.6 A 

FREQUENCY: 50 - 60 Hz 
Input selection is automatic, no manual 
change is required. 

 

DC OUTPUT: 

 

VOLTAGE: adjustable 30 

 100 Vdc 

CURRENT: 39A / 45A  
POWER: MAX. 3500W/4000W 

 

SAFETY APPROVALS 

 

UL/CSA 62368-1 2

nd

 edition - completed 

 

IEC 62368-1 2

nd

 edition - completed 

 

CE Mark for LVD - completed 

 

 

 

 

INSTALLATION REQUIREMENTS 

1.

 

For details and mechanical drawings, access the AC-DC Data Sheet/App Notes link on the Bel Power Solutions website at: 
belfuse.com/power-solutions and go to the respective TCP4000 listing. 

2.

 

Inside the power supply are 3 input fuses with rating 20A/500V. Recommended rating of upstream fuse or circuit breaker is 40A per phase. 

CAUTIONS 

These  component  level  power  supplies  are  intended  exclusively  for  installation  within  other  equipment  by  an  industrial  assembly  operation  or  by 
professional installers. These are Class 1 power supplies; the unit must be properly connected to earth ground in end use. A component power supply 
should  be  installed  in  end-use  equipment  according  to  the  requirements  of  the  safety  standard  used  for  that  equipment.  This  power  supply  is  not 
designed to be operated outside of an enclosure which provides a means of mechanical, electrical, and fire protection. Power supply does not meet 
ES1 requirements, maximal output voltage is 100VDC. 

 

PROTECTIVE EARTHING 

The Power Supply must be properly grounded to mains protective earth termination at end use. 

ENVIRONMENTAL CONDITIONS: 

TRANSPORTATION & STORAGE:  Ambient Temperature Range -40 °C to +85 °C 

Relative Humidity Range: 5% to 95% RH Non-Condensing 
Altitude: to 12 192 m (40 000 feet) ASL 

 

OPERATION:  Ambient Temp. Range -20°C to +70°C (at 100% load)

Relative Humidity Range: 10% to 90% RH Non-Condensing 
Altitude: to 3048 m (10 000 feet) ASL 
 

 

Note: 

  

1

 Cooling plate temperature range -20°C to +50°C (at 100% load). 

WARNING 

1.

 

The equipment is for business use (Class A) and has acquired electromagnetic conformity registration. Therefore, the sellers and users are 
required to take caution in this regard.  

2.

 

The AC Leakage Current exceeds 3.5mA at maximal input voltage and frequency (3 x 528Vac / 60Hz). Typical values are: ~1.8mA at input 3 x 
200 

 208Vac (L-L) / 50 - 60Hz; ~3.0mA at 3 x 400Vac (L-L) / 50Hz and ~4.1mA at 3 x 528Vac (L-L) / 60Hz. 

3.

 

Switch-off the input AC power before doing any intervention or manipulation with the unit! Do not touch output contacts 

 discharging time is 2 

minutes after turn-off! 

4.

 

In order to ensure maximal useful lifetime of the power supply, minimal time between SWITCH-OFF and SWITCH-ON of the input AC power is 30 
seconds and it is not allowed more than 100 cycles within 120 minutes otherwise damage of power supply can occur.

 

SERVICING 

In case of failure, the Power Supply must be returned to a Bel Power Solutions Authorized Service Center. There are no user serviceable parts in the 
Power Supply. 

LIMITED WARRANTY 

Bel Power Solutions warrants each power supply of its manufacture for a period of two years from the date of original shipment. This warranty applies to 
defects  in  materials  and  workmanship  that  result  in  non-performance  to  published  specifications.  The  product(s)  must  be  returned  to  a  Bel  Power 
Solutions Authorized Service Center for repair with a Bel Power Solutions preassigned RMA number. 
Bel  Power  Solutions  assumes  no  liabilities  for  consequential  damages  of  any  kind  through  the  use  or  misuse  of  its  products  by  any  user.  No  other 
obligations are expressed or implied. 
Please note that the specifications, terms, and conditions stated are subject to change without notice. 

NUCLEAR AND MEDICAL APPLICATIONS 

Bel Power Solutions products are not designed, intended for use in, or authorized for use as critical components in life support systems, equipment used 
in hazardous environments, or nuclear control systems without the express written consent of the respective divisional president of Bel Power Solutions. 

TECHNICAL REVISIONS 

The appearance of products, including safety agency certifications pictured on labels, may change depending on the date manufactured. Specifications 
are subject to change without notice. 
 

Summary of Contents for TCP4000-H090

Page 1: ...ormity registration Therefore the sellers and users are required to take caution in this regard 2 The AC Leakage Current exceeds 3 5mA at maximal input voltage and frequency 3 x 528Vac 60Hz Typical values are 1 8mA at input 3 x 200 208Vac L L 50 60Hz 3 0mA at 3 x 400Vac L L 50Hz and 4 1mA at 3 x 528Vac L L 60Hz 3 Switch off the input AC power before doing any intervention or manipulation with the ...

Page 2: ...assis Min 2 5 mm2 AC Line 1 L1 Input Power AC Fused Min 2 5 mm2 528 Vrms line to line 16 Arms per line AC Line 2 L2 Input Power AC Fused Min 2 5 mm2 AC Line 3 L3 Input Power AC Fused Min 2 5 mm2 POWER OUTPUTS CONNECTOR BUS BARS Connector type Bus bar see Fig 1 Mating part Ring terminal for M4 screw with appropriate cross section for wire SIGNAL NAME PIN TYPE SIGNAL REFERENCE LOW LEVEL HIGH LEVEL V...

Page 3: ...RS485 Half Duplex Differential pair 2 RS485 2B 60 mA 60 Ω 50 pF2 7 to 12 VDC 8 mA ADDR INIT IN 3 The unit s address change required SRTN 0 4 VDC 2 5 VDC 3 6 VDC 0 2 mA IN OK 4 AC Power Fail Warning open collector external pull up needed to max 7 V SRTN 0 4 VDC Pull up 7 VDC 10 mA OUT OK 5 Output Voltage Fault open collector external pull up needed to max 7 V SRTN 0 4 VDC Pull up 7 VDC 10 mA INHIBI...

Page 4: ...in to SRTN SRTN 0 4 VDC 2 5 VDC 3 6 VDC 0 2 mA SRTN1 8 Internal Ground Signal Return RS485 1B 9 RS485 Half Duplex Differential pair 1 RS485 1B 60 mA 60 Ω 50 pF2 7 to 12 VDC 8 mA RS485 2B 10 RS485 Half Duplex Differential pair 2 RS485 2B 60 mA 60 Ω 50 pF2 7 to 12 VDC 8 mA Not Connected 11 OT FAIL 12 Over Temperature PSU Fail open collector external pull up needed to max 7 VDC SRTN 0 4 VDC Pull up 7...

Page 5: ...ature difference of contact area of cold plate and power supply should be 5 C at worst case total power dissipation of each PSU max 300W Recommended is to use heat transfer paste with thermal conductivity 2 5 W m K between unit and cold plate surface roughness Ra 3 2 of the aluminium plate is acceptable Recommended tightening torque of M4 screws for assembling unit to aluminium cold plate is 3 5 4...

Reviews: