manualshive.com logo in svg
background image

  

EN - english

 

 

Instructions for installation and operation

Compressed air refrigeration dryer

DRYPOINT

®

 RA 1080-8800

 

 

 

 

 

 

Содержание DRYPOINT RA 1080-8800

Страница 1: ...EN english Instructions for installation and operation Compressed air refrigeration dryer DRYPOINT RA 1080 8800 ...

Страница 2: ... Please read these installation and operating instructions carefully before mounting and starting up the DRYPOINT RA 1080 8800 and follow our directions Perfect functioning of the DRYPOINT RA 1080 8800 and thus reliable compressed air drying can only be guaranteed when the provisions and notes stipulated here are strictly adhered to ...

Страница 3: ...ol panel 25 11 2 Functional description 25 11 3 Flow chart air cooled 26 11 4 Flow chart water cooled 26 11 5 Refrigerating compressor 27 11 6 Condenser air cooled 27 11 7 Condenser water cooled 27 11 8 Cooling water regulating valve 27 11 9 Filter dryer 27 11 10 Capillary tube 27 11 11 Aluminium heat exchanger 27 11 12 Hot gas bypass valve 27 11 13 Refrigerant pressure switches LPS HPS 27 11 14 C...

Страница 4: ...onic control unit DMC 24 Sheet 1 3 58 13 3 3 Electric diagrams DRYPOINT RA 1080 2200 Electronic control unit DMC 24 Sheet 2 3 59 13 3 4 Electric diagrams DRYPOINT RA 1080 2200 Electronic control unit DMC 24 Sheet 3 3 60 13 3 5 Electric diagrams DRYPOINT RA 2400 4400 Electronic control unit DMC 24 Sheet 1 4 61 13 3 6 Electric diagrams DRYPOINT RA 2400 4400 Electronic control unit DMC 24 Sheet 2 4 6...

Страница 5: ...doc 4004 Pos 3 Beko Technische Dokumentation Sicherheit Hinweis Anleitung BEKO 0 mod_1184147787557_6 doc 5758 Please check whether or not these instructions correspond to the device type Please adhere to all advice given in these operating instructions They include essential information which must be observed during installation operation and maintenance Therefore it must be ensured that these ope...

Страница 6: ...nlet ARIA AIR LUFT AIR Connection point compressed air outlet Connection point condensate drain Connection point cooling water inlet water cooled Connection point cooling water outlet water cooled 1 Certified skilled personnel are persons who are authorised by the manufacturer with experience and technical training who are well grounded in the respective provisions and laws and capable of carrying...

Страница 7: ...ol advises the user to observe the environmental aspects and comply with the recommendations connected with this symbol 2 Certified skilled personnel are persons who are authorised by the manufacturer with experience and technical training who are well grounded in the respective provisions and laws and capable of carrying out the required works and of identifying and avoiding any risks during the ...

Страница 8: ...en accessories are used Danger Compressed air Risk of serious injury or death through contact with quickly or suddenly escaping compressed air or through bursting and or unsecured plant components Compressed air is a highly dangerous energy source Never work on the dryer when the system is under pressure Never direct the compressed air outlet or condensate drain hoses at persons The user is respon...

Страница 9: ...each of children Breathing protection ambient air independent respirator at high concentrations Eye protection sealing goggles Hand protection protective gloves e g made of leather Personal protection protective clothing Skin protection use protective cream In addition the safety data sheet for the refrigerant needs to be observed Caution Hot surfaces During operation several components can reach ...

Страница 10: ... interventions may endanger persons and plants and lead to malfunction Unauthorised interventions modification and abuse of the pressure devices are prohibited The removal of sealings and leadings at safety devices is prohibited Operators of the devices must observe the local and national pressure equipment regulations in the country of installation Pos 8 Beko Technische Dokumentation Sicherheit S...

Страница 11: ...er throughput water cooled The ambient temperature When delivered the dryer is tested and fully assembled The customer only needs to connect the device to the system in accordance with the instructions in the following chapters Pos 15 Beko Technische Dokumentation Überschriften 1 Ausschluss vom Anwendungsbereich 0 mod_1236003439359_6 doc 13709 4 Exclusion from a field of application Pos 16 Beko Te...

Страница 12: ... the pressure parts The DRYPOINT RA 1080 8800 compressed air refrigeration dryer must neither be installed in insufficiently ventilated rooms nor near heat sources or inflammable substances To avoid fractures resulting from material fatigue the refrigeration dryer should not be exposed to vibrations during operation The maximum operating pressure indicated by the manufacturer on the name plate mus...

Страница 13: ...ong shocks can cause irreparable damage 7 Storage SCC0001 Keep the device away from extreme weather conditions even when packaged Keep the dryer in an upright position also while it is stored Tilting the device or turning it upside down can cause irreparable damage to some components When the dryer is not in use it can be stored in its packaging in a dust free and protected place at a temperature ...

Страница 14: ...which chemicals with a corrosive effect explosive gases toxic gases evaporation heat high ambient temperatures or extreme dust and dirt can be found Minimum installation requirements Choose an area which is clean and dry free from dust and protected against atmospheric disturbances The load bearing zone must be even horizontal and able to bear the weight of the dryer Minimum ambient temperature 1 ...

Страница 15: ...consumption constantly varies with peak values which considerably exceed the throughput rate of the compressor The storage capacity of the tank must be dimensioned in such a way that a possible short term high air demand peak air consumption can be compensated Do not obstruct the ventilation grille not even partially Prevent any recirculation of the outgoing cooling air Protect the dryer against d...

Страница 16: ...30 C Air inlet temperature 40 C Pressure dew point 5 C Factor F1 1 05 Factor F2 0 95 Factor F3 0 81 Factor F4 1 09 Every function parameter corresponds to a numerical factor which multiplied by the planned nominal capacity determines the following Actual air throughput 3 000 x 1 05 x 0 95 x 0 81 x 1 09 2 642 m h 2 642 m h is the maximum air mass of the dryer under the aforementioned operating cond...

Страница 17: ...hich protect the dryer against possible vibrations in the pipework Note Contaminated intake air In the event that the intake air is strongly contaminated ISO 8573 1 class 3 3 or poorer quality we recommend the additional installation of a prefilter e g CLEARPOINT F040 to avoid clogging of the heat exchanger Ende der Stückliste 8 5 Connection to the cooling water network Danger Compressed air and u...

Страница 18: ...NO3 100 mg l or ppm Saturation mark SI 0 2 0 0 2 Fe 0 2 mg l or ppm HCO3 70 300 mg l or ppm Al 0 2 mg l or ppm SO4 2 70 mg l or ppm Mn 0 1 mg l or ppm Note 1 Other temperatures upon request check the data on the name plate 2 Other pressures upon request check the data on the name plate 3 Pressure difference at the water connection of the dryer at maximum water flow Other delivery pressures upon re...

Страница 19: ...es on the name plate of the dryer The cross section of the power supply cables must correspond to the consumption of the dryer In this respect the ambient temperature the cable laying conditions the length of the cables and the requirements of the local electricity supplier need to be considered LGT0028 L1 L2 L3 PE QS CAUTION Please observe the direction of rotation of the compressor In this syste...

Страница 20: ...ordance with the local provisions It is advisable to install a water oil separator to which the total amount of condensate from the compressors dryers tanks filters etc is supplied We recommend ÖWAMAT oil water separators for dispersed compressor condensate and BEKOSPLIT emulsion splitting plants for emulsified condensate 9 Start up 9 1 Preliminary stages Note Exceeding of the operating parameters...

Страница 21: ...connected correctly Change two of the three phases at the supply mains see Section 8 7 Wait at least two hours before starting the dryer the crankcase heater of the compressor needs to heat up the compressor oil Press the button for at least two seconds to start the dryer If the compressor was out of operation for a sufficient period of time it will start immediately If this is not the case the di...

Страница 22: ...1 Control panel Ensure that the dew point temperature indicated on the DMC24 is within the permissible range Shut down the air compressor Switch the dryer off after several minutes by pressing the button on the DMC24 for at least two seconds The display then shows Dryer remote control ON OFF See instructions in Section 11 15 7 Only use potential free contacts that are suitable for low voltage Ensu...

Страница 23: ...Technical data DRYPOINT RA 1080 8800 23 10 Technical data 10 1 Technical data DRYPOINT RA 1080 8800 3 400 50 ...

Страница 24: ...Technical data 24 DRYPOINT RA 1080 8800 10 2 Technical data DRYPOINT RA 1080 8800 3 460 60 ...

Страница 25: ...ed through the air air heat exchanger so that it is reheated to up to 8 C below the inlet temperature when leaving the dryer Refrigeration cycle The refrigerant is conducted through the compressor and reaches a condenser under high pressure There cooling down takes place making the refrigerant condense to a liquid state which is under high pressure The liquid is pressed through a capillary tube wh...

Страница 26: ...3 T3 Temperature probe Compressor suction c Condensate separator 12 4 T4 Temperature probe Compressor discharge 2 Refrigerant pressure switch LPS P 13 Condensate drain isolation valve 4 Refrigerant pressure switch HPS P 18 Condenser water cooled 6 Refrigerating compressor 19 Cooling water regulating valve water cooled 7 Hot gas bypass valve 20 Liquid collector RA 5400 8800 AC RA 1080 8800 WC 8 Con...

Страница 27: ...ure inside of the evaporator The lower the outlet pressure at the capillary tube the lower the evaporation temperature The length and the inner diameter of the capillary tube are exactly dimensioned to ensure the performance of the dryer Settings or maintenance works are not required 11 11 Aluminium heat exchanger The heat exchanger module consists of an air air heat exchanger an air refrigerant h...

Страница 28: ...nge log Log Alarm red info Info menu Remote control active ESC Test button condensate drain ESC Temperature in C info set Instrument setting menu Temperature in F log reset Reset alarm and or service Pressure in bar g Pressure in psi g The DMC24 controls all operations alarms and instrument settings of the dryer The display and the LEDs indicate all operating conditions The LED shows that the comp...

Страница 29: ... to return to the list of displayable parameters Press ESC to leave the Info menu if after a period of two minutes no button is pressed the menu is exited automatically Info Description T1 Temperature probe T1 dew point T2 Temperature probe T2 Air IN T3 Temperature probe T3 Compressor suction T4 Temperature probe T4 Compressor discharge HP Condensation pressure HP HrS Total number of operating hou...

Страница 30: ...ervice technician must check the dryer and eliminate the problem that led to the activation of the service warning Service warning Description PF1 Probe 1 failure failure temperature probe 1 PF2 Probe 2 failure failure temperature probe 2 PF3 Probe 3 failure failure temperature probe 3 HdP High dew point dew point too high higher than the adjusted HdA value LdP Low dew point dew point too low Sett...

Страница 31: ...omatically subsequent to the reset of the alarms NOTE the operator service technician must check the dryer and eliminate the problem that led to the activation of the alarm Alarm Description HP High pressure the refrigerant high pressure guard HPS has triggered note the pressure switch has a reset button LP Low pressure the refrigerant low pressure guard LPS has triggered COn Compressor the compre...

Страница 32: ...lights up and it is no longer possible to switch the dryer on or off from the local control panel the condensate drain test is possible and you have access to the info and log menus When the contact between terminals 2 and 3 is closed close the second contact between terminals 1 and 2 to switch on the dryer Open the contact between terminals 1 and 2 to switch off the dryer Only use potential free ...

Страница 33: ...time for condensate drain valve 1 20 min 1 min 1 HdA High DewPoint Alarm Alarm threshold for a high DewPoint the alarm disappears when the temperature drop 1 C 2 F below alarm point 0 0 25 0 C or 32 77 F 0 5 C or 1 F 20 or 68 Hdd High DewPoint Delay high DewPoint alarm enable delay 01 20 minutes 1 min 15 HdS High DewPoint alarm STOP select if high DewPoint alarm stops dryer YES or does not stop dr...

Страница 34: ...to the electronic control and a membrane solenoid valve opens to discharge the condensate The BEKOMAT closes before compressed air emerges Note These BEKOMAT condensate drains were designed in particular for the operation in a DRYPOINT RA refrigeration dryer The installation in other compressed air processing systems or the replacement with another drain brand can lead to malfunction The maximum o...

Страница 35: ...leshooting spare parts and dismantling chapters leads to the expiration of the guarantee Improper maintenance may result in dangerous situations for the personnel and or the device Danger Supply voltage Contact with non insulated parts carrying supply voltage involves the risk of an electric shock resulting in injuries and death Only qualified and skilled personnel are authorised to run electrical...

Страница 36: ...irectives in force apply to the qualification and expertise of the certified skilled personnel For safe operation the device must only be installed and operated in accordance with the indications in the operating instructions In addition the national and operational statutory provisions and safety regulations as well as the accident prevention regulations required for the respective case of applic...

Страница 37: ...ram replace it DMC24 The LED is on see the corresponding point Refrigerant gas loss contact a specialist for refrigerating plants In the event that the fan still does not work replace it Dew point too high Dryer does not start up see the corresponding paragraph The T1 dew point sensor does not record the temperature properly ensure that the sensor is pushed down to the bottom of the aluminium tube...

Страница 38: ...tinuously discharges condensate BEKOMAT discharge unit is dirty see BEKOMAT manual Water in the line The dryer does not start see the corresponding section If installed untreated air flows through the bypass group close it The dryer does not drain condensate see the corresponding paragraph The pressure dew point is too high see the corresponding paragraph The high pressure switch HPS has triggered...

Страница 39: ...utes and retry air cooled 10 Hdt The outlet temperature protection of the compressor has triggered as a result of a very high temperature probe T4 see the corresponding paragraph 11 ICE The temperature inside the exchanger probe T1 is too low the dew point is too low see the corresponding paragraph 12 LCP The condensation pressure is too low see the corresponding paragraph 13 PF4 Failure temperatu...

Страница 40: ...re too high Find out the reason for the fault 1 The ambient air temperature is too high or the air change insufficient in this area ensure sufficient ventilation air cooled 2 The condenser filter is dirty please clean or replace it air cooled 3 The fan does not work see the corresponding section air cooled 4 The cooling water is too hot re establish the nominal conditions water cooled 5 The coolin...

Страница 41: ...nance troubleshooting spare parts and dismantling DRYPOINT RA 1080 8800 41 12 3 Recommended spare parts NOTE To order the recommended spare parts or other elements the data on the name plate must be indicated ...

Страница 42: ...Maintenance troubleshooting spare parts and dismantling 42 DRYPOINT RA 1080 8800 ...

Страница 43: ...ies of the refrigerant used Refrigerant Chemical formula MIK GWP R407C HFC R32 125 134a 23 25 52 CHF2CF3 CH2F2 CH2FCF3 1000 ppm 1653 12 5 Dismantling the dryer When the dryer is dismantled all parts and operating materials related to the plant need to be disposed of separately Component Material Refrigerant R407C oil Roof and supports Structural steel epoxy paint coat Refrigerating compressor Stee...

Страница 44: ...Appendices 44 DRYPOINT RA 1080 8800 13 Appendices 13 1 Dryer dimensions 13 1 1 Dimensions DRYPOINT RA 1080 2200 ...

Страница 45: ...Appendices DRYPOINT RA 1080 8800 45 13 1 2 Dimensions DRYPOINT RA 2400 4400 ...

Страница 46: ...Appendices 46 DRYPOINT RA 1080 8800 13 1 3 Dimensions DRYPOINT RA 5400 6600 ...

Страница 47: ...Appendices DRYPOINT RA 1080 8800 47 13 1 4 Dimensions DRYPOINT RA 7200 8800 ...

Страница 48: ...54 Left sidewall 8 Condenser air cooled 55 Cover 9 Condenser fan 56 Base plate 10 Filter dryer 57 Upper plate 11 Capillary tube 58 Carrier support 12 T1 temperature probe dew point 59 Support bracket 13 Condensate drain service valve 60 Control panel 17 Air dryer control 65 Condenser filter 18 Condenser water cooled 66 QE door 19 Condenser water regulating valve water cooled 81 Adhesive label flow...

Страница 49: ...Appendices DRYPOINT RA 1080 8800 49 13 2 2 Exploded diagram DRYPOINT RA 1080 2200 AC ...

Страница 50: ...Appendices 50 DRYPOINT RA 1080 8800 13 2 3 Exploded diagram DRYPOINT RA 2400 4400 AC ...

Страница 51: ...Appendices DRYPOINT RA 1080 8800 51 13 2 4 Exploded diagram DRYPOINT RA 5400 6600 AC ...

Страница 52: ...Appendices 52 DRYPOINT RA 1080 8800 13 2 5 Exploded diagram DRYPOINT RA 7200 8800 AC ...

Страница 53: ...Appendices DRYPOINT RA 1080 8800 53 13 2 6 Exploded diagram DRYPOINT RA 1080 2200 WC ...

Страница 54: ...Appendices 54 DRYPOINT RA 1080 8800 13 2 7 Exploded diagram DRYPOINT RA 2400 4400 WC ...

Страница 55: ...Appendices DRYPOINT RA 1080 8800 55 13 2 8 Exploded diagram DRYPOINT RA 5400 6600 WC ...

Страница 56: ...Appendices 56 DRYPOINT RA 1080 8800 13 2 9 Exploded diagram DRYPOINT RA 7200 8800 WC ...

Страница 57: ...igerant pressure transducer HPS Pressure switch compressor discharge side HIGH PRESSURE LPS Pressure switch compressor suction side LOW PRESSURE ELD BEKOMAT drain EVD Time controlled drain not used QS Main switch with locking device RC Compressor crankcase heater NT1 Only air cooled NT2 Check the transformer connections with regard to the supply voltage NT3 Jump if not installed NT4 Provided and c...

Страница 58: ...E MAX 16 A 3 400V 50Hz PE RCD Id 0 03A suggested Smin 2 5sqmm 14AWG Rev Note Sheet 01 of Drawing no 03 01 FU4 A TF FU1 2 FU3 B RC 2 7 3 MV1 TK M 2 1 KC1 11 12 TK W1 U1 V1 W2 U2 V2 2 2 2 6 4 KV1 1 3 5 BEKO TECHNOLOGIES GMBH http www beko de BKRA5478QCD001 See dryer nameplate OR 3 460V 60Hz PE 3 460V 60Hz PE 3 400V 50Hz PE L1 L2 L3 11 14 12 Technical modifications are subject to change without notic...

Страница 59: ...1 2 11 NU 12 6 5 1 5 4 3 A1 A2 KV2 2 0 KHP 24 21 14 1 4 14 11 RPP 13 Q1 1 3 MV1 2 0 KHP 14 11 25 27 26 DEWPOINT TEMP BT1 BT2 AIR IN TEMP BT3 BT4 24 22 23 P mA BHP 28 29 21 20 19 18 3 2 N 2 4 L 3 1 2 3 A 2 6 2 8 1 9 17 8 7 3 2 16 2 6 2 8 DMC24RU 1 3 1 6 1 5 1 3 1 6 1 5 A 13 10 3 1 L 2 3 3 2 N 2 4 ZL T Power ON Power OFF MAX 2A 48V and NO Alarm or Alarm 6 5 4 6 5 4 1 J1 DISPLAY EXP J2 J3 RS485 A B E...

Страница 60: ...AL TYPE TERMINAL UKK 5 RC COMPRESSOR CRANKCASE HEATER HIGH PRESSURE SWITCH HPS MV1 LPS 9 024 024 CDI 12 CDI DI2 DI4 2 1 5 4 3 6 UKK 5 13 11 10 12 14 RC1 00 10 RC2 00 DR1 DR2 CDI DI5 LOW PRESSURE SWITCH 8 7 00 UDT ELD BEKO TECHNOLOGIES GMBH http www beko de BKRA5478QCD001 BEKOMAT FAN THERMAL PROTECTION PE L1 L3 L2 Technical modifications are subject to change without notice errors not excluded ...

Страница 61: ... U T1 V T2 M W T3 2 4 KC1 1 3 QC1 2 7 QV1 BKRA5478QCD002 OR 3 460V 60Hz PE Smin 6sqmm 10AWG RCD Id 0 03A suggested FUSE MAX 32 A 3 400V 50Hz PE BEKO TECHNOLOGIES GMBH http www beko de See dryer nameplate 3 460V 60Hz PE 3 400V 50Hz PE TF L1 L3 L2 RPP 11 14 2 6 12 W2 U1 V1 W1 U2 V2 2 3 KV2 KV1 2 2 KV0 2 1 U1 V1 W1 M 3 2 7 TK TK MV1 M 2 8 TK TK 3 MV2 Technical modifications are subject to change with...

Страница 62: ...1 DMC24 A MV2 13 14 QV1 1 5 N U N U 11 12 1 9 1 3 5 3 1 6 4 2 1 6 1 7 1 3 1 3 1 7 1 6 DMC24MA 27 K 15 13 9 14 29 28 T II I 11 12 10 22 26 25 24 23 21 20 ZL 8 7 19 18 B J3 RS485 DISPLAY 1 2 3 4 5 6 A 17 16 EXP J2 J1 5 NO Alarm and MAX 2A 48V Power ON 4 Power OFF 4 6 Alarm or 5 6 A A1 KHP 2 0 24 21 A1 A1 KC1 KV2 KV1 A2 A2 A2 DEWPOINT TEMP AIR IN TEMP 00 3 2 3 0 BEKO TECHNOLOGIES GMBH http www beko d...

Страница 63: ...C 24 Sheet 3 4 0 1 3 2 4 5 6 7 8 9 Rev Note Sheet 03 of Drawing no 04 01 B A 11 14 22 24 2 8 KDR 2 5 KDR 2 5 3 2 1 3 2 4 1 2 3 1 2 3 1 1 3 2 1 3 2 4 N 3 1 2 3 L 2 8 ELD1 ELD2 BEKO TECHNOLOGIES GMBH http www beko de BKRA5478QCD002 Technical modifications are subject to change without notice errors not excluded ...

Страница 64: ...MV1 COMPRESSOR CRANKCASE HEATER RC 00 DI2 CDI 12 024 WIRE TERMINAL TERMINAL TYPE UKK 5 DI4 024 00 35 UDT 31 10 00 RC1 RC2 UKK 5 024 17 32 CDI 16 15 33 00 20 18 19 9 1 5 3 2 4 7 6 8 10 11 12 13 14 MV2 21 22 DI5 34 ELD1 ELD2 BKRA5478QCD002 BEKO TECHNOLOGIES GMBH http www beko de FAN THERMAL PROTECTION FAN THERMAL PROTECTION BEKOMAT BEKOMAT L3 L1 L2 PE Technical modifications are subject to change wi...

Страница 65: ... 12 3 6 5 6 3 2 MC1 3 U T1 V T2 M W T3 2 4 KC1 1 3 QC1 BKRA5478QCD003 OR 3 460V 60Hz PE Smin 16sqmm 6AWG RCD Id 0 03A suggested FUSE MAX 63A 3 400V 50Hz PE BEKO TECHNOLOGIES GMBH http www beko de See dryer nameplate 3 460V 60Hz PE 3 400V 50Hz PE TF L1 L3 L2 RPP 11 14 3 6 12 3 6 TK TK Technical modifications are subject to change without notice errors not excluded 2 0 L L2 L3 L1 N S1 S2 M2 M1 M 3 3...

Страница 66: ... Note Sheet 02 of Drawing no 06 00 3 7 QV1 BKRA5478QCD003 BEKO TECHNOLOGIES GMBH http www beko de 3 3 KV2 KV1 3 2 KV0 3 1 Technical modifications are subject to change without notice errors not excluded MV2 MV1 3 7 3 7 M V1 3 U1 TK W1 TK M U1 V1 TK 3 W1 W2 TK U2 V2 3 8 MV4 3 V1 M 3 8 TK U1 TK W1 MV3 M U1 TK V1 3 TK W1 1 9 W2 U2 V2 W2 U2 V2 U2 W2 V2 ...

Страница 67: ... 5 3 1 6 4 2 2 2 2 3 1 3 1 3 2 3 2 2 DMC24MA 27 K 15 13 9 14 29 28 T II I 11 12 10 22 26 25 24 23 21 20 ZL 8 7 19 18 B J3 RS485 DISPLAY 1 2 3 4 5 6 A 17 EXP J2 J1 5 NO Alarm and MAX 2A 48V Power ON 4 Power OFF 4 6 Alarm or 5 6 A A1 KHP 2 0 24 21 A1 A1 KC1 KV2 KV1 A2 A2 A2 DEWPOINT TEMP CONDENSING PRESS COMPRES DISCHARGE TEMP COMPRES SUCTION TEMP AIR IN TEMP 00 4 2 4 0 11 7 8 3 12 6 2 1 10 9 5 4 BE...

Страница 68: ...e Sheet 04 of Drawing no 06 00 B A 5 9 6 10 3 8 KDR 3 5 KDR 3 5 3 2 1 3 2 4 1 2 3 1 2 3 1 1 3 2 1 3 2 4 N 3 1 2 3 L ELD1 ELD2 BEKO TECHNOLOGIES GMBH http www beko de BKRA5478QCD003 Technical modifications are subject to change without notice errors not excluded 8 7 ELD3 1 3 3 2 N 2 4 3 1 L 2 3 ELD4 3 2 1 3 1 2 2 4 3 1 1 1 2 3 11 3 5 KDR 12 3 8 KDR 3 5 ...

Страница 69: ... 14 13 ELD3 ELD4 29 34 31 30 33 32 38 35 36 37 39 40 S3 R3 U1 1 UKK 5 V1 1 W1 1 V1 2 U1 2 W1 2 MV1 M 3 MV2 MV4 MV3 M 3 00 024 00 024 45 46 DI5 48 47 T3 S3 R3 T3 S4 R4 T4 T4 S4 R4 MC1 6 5 Technical modifications are subject to change without notice errors not excluded DI3 15 HIGH PRESSURE SWITCH LOW PRESSURE SWITCH RA8800 ONLY COMPRESSOR THERMAL PROTECTION FAN THERMAL PROTECTION FAN THERMAL PROTECT...

Страница 70: ...ams DRYPOINT RA 5400 8800 Electronic control unit DMC 24 Sheet 6 6 0 1 3 2 4 5 6 7 8 9 Rev Note Sheet 06 of Drawing no 06 00 BKRA5478QCD003 BEKO TECHNOLOGIES GMBH http www beko de Technical modifications are subject to change without notice errors not excluded ...

Страница 71: ...Appendices DRYPOINT RA 1080 8800 71 ...

Страница 72: ...Appendices 72 DRYPOINT RA 1080 8800 ...

Страница 73: ...Declaration of conformity CE DRYPOINT RA 1080 8800 73 14 Declaration of conformity CE ...

Страница 74: ...Declaration of conformity CE 74 DRYPOINT RA 1080 8800 ...

Страница 75: ...sions 44 E Electrical connections 19 Exclusion from a field of application 11 Exclusion of a field of application 11 Exploded diagrams 48 49 50 51 52 F Field of application 11 Filter dryer 27 Flow chart 26 Functional description 25 H Heat exchanger 27 Heating resistor compressor housing DRYPOINT RA 1080 8800 28 Hot gas bypass valve 27 I Initial start up 21 Installation 14 Installation plan 15 M Ma...

Страница 76: ...z o o ul Chłapowskiego 47 PL 02 787 Warszawa Phone 48 0 22 855 30 95 info pl beko de Scandinavia BEKO TECHNOLOGIES AB Industrivägen 39 S 43361 Sävedalen Phone 46 31 26 35 00 aleksander suven beko de España Spain BEKO Tecnológica España S L Polígono Industrial Armenteres C Primer de Maig no 6 E 08980 Sant Feliu de Llobregat Phone 34 93 632 76 68 info es beko de South East Asia BEKO TECHNOLOGIES S E...

Отзывы: