background image

Automated Logic Corporation

1150 Roberts Blvd.

Kennesaw, GA 30144

• 

770/429-3000

770/429-3001 Fax

• 

www.automatedlogic.com

• 

Copyright 2000 Automated Logic Corporation. All rights reserved. Automated Logic, the

Automated Logic logo, SuperVision, Eikon, and Alert are registered trademarks of Automated Logic Corporation.
InterOp is a trademark of Automated Logic Corporation. BACnet

®

is a registered trademark of ASHRAE. All other brand

and product names are trademarked by their respective companies.

Technical Instructions

M4106nx

Using the M4106nx 2
Specifications 3
Mounting 3
Addressing 3
Power Wiring 3
CMnet Communications 4
Communicating with the Workstation 5
Inputs 5
Digital Outputs 7
Analog Outputs 7
Channel Numbers 8
Transferring Memory 9
Troubleshooting 9

Formatting the Module 9
LEDs 9
Protection 10
Production Date 10

Summary of Contents for M4106nx

Page 1: ...nterOp is a trademark of Automated Logic Corporation BACnet is a registered trademark of ASHRAE All other brand and product names are trademarked by their respective companies Technical Instructions M4 106nx Using the M4106nx 2 Specifications 3 Mounting 3 Addressing 3 Power Wiring 3 CMnet Communications 4 Communicating with the Workstation 5 Inputs 5 Digital Outputs 7 Analog Outputs 7 Channel Numb...

Page 2: ... accordance with the instruction manual may cause harmful interference to radio communications Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense Figure 1 Module Dimensions and Layout 2 3 4 7cm DXG 5DWH 6ZLWFK GGUHVV 6ZLWFKHV RUPDW XWWRQ 3RZHU 6ZLWFK QG DQG 9DF 7HUPLQDOV X ...

Page 3: ...Part 15 Subpart B Class A Mounting Screw the M4106nx into an enclosed panel using the mounting holes provided on the cover plate Be sure to leave about 2 inches 5 centimeters on each side for wiring Addressing Before setting or changing the address make sure the M4106nx s power is off The M4106nx only reads the address when the module is turned on After changing the address you must transfer memor...

Page 4: ...the differences between ARCNET and ARC156 please refer to ARC156 CMnet Wiring Technical Instructions Use the appropriate wire for CMnet communications When using an ARC156 CMnet use an A3ARC156 wire available from Magnum Cable Corporation Cleveland OH 44110 0500 800 421 0820 Use a dedicated 22AWG to 18AWG twisted pair wire for legacy CMnet EIA 485 wiring For more information about CMnet wiring ref...

Page 5: ...tion type using Table 1 Inputs The M4106nx module has ten universal inputs to accept the types of signals listed below Refer to Table 2 for information about wire length gauge and shielding Thermistor Precon type 2 10kohm at 77 F Input voltages should range between 0 489V and 3 825V for thermistors 0 to 5VDC The output impedance of a 0 to 5VDC source must not exceed 10kohms The input impedance of ...

Page 6: ...4 For each input enter the channel number offset and gain on the Function Block s Parameter page in SuperVision Valid channel numbers are listed in Channel Numbers on page 8 5 To verify each input s operation have each sensor create a known value and compare it to the condition reported on the FB s Status page Table 2 Input wiring restrictions Input Maximum Length Minimum Gauge Shielding 0 to 5VDC...

Page 7: ...ponds to HOA switch number one channel 82 corresponds to HOA switch two and so on An off status on these channels means the HOA switch is in Auto mode An on status means the HOA switch is in Manual mode Analog Outputs The M4106nx module has six analog outputs that support voltage devices in the 0 10VDC range The device that is being controlled must have a minimum of 500 Ohms resistance measured fr...

Page 8: ... 0O 4 2 0 m A 2 5 0 A B B A A A B B A A B B A B B A A A B B A A B B UI 3 Thermistor 33 17 to 213 F 27 to 100 6 C 0 00 0 00 15 88 15 69 mA or Volts 33 0 to 20mA 0 to 5V Digital 23 UI 4 Thermistor 34 17 to 213 F 27 to 100 6 C 0 00 0 00 15 88 15 69 mA or Volts 34 0 to 20mA 0 to 5V Digital 24 UI 5 Thermistor 35 17 to 213 F 27 to 100 6 C 0 00 0 00 15 88 15 69 mA or Volts 35 0 to 20mA 0 to 5V Digital 25...

Page 9: ...odule you can as a last resort manually format the module to try to restore communication Formatting the module erases all memory so you need to transfer memory back to the module once it is formatted 1 Turn the module s power off Make sure the module s address switches are not set to 0 0 2 Press and hold the Format button see Figure 1 on page 2 for location 3 While continuing to hold the Format b...

Page 10: ...ows the date the module was manufactured The first three characters on the sticker indicate the type of module The next three characters show the year month and week of manufacture The month digit is in hexadecimal Table 7 LED Signals Run LED Error LED Condition 2 flashes per second Off Normal 2 flashes per second 1 flash per second Normal but module is alone on the CMnet 2 flashes per second 2 fl...

Reviews: