A-100IMWP 

ILLUMINATED MULLION KEYPAD 

 

WIRING & PROGRAMMING INSTRUCTIONS 

WI1497  7/06 

GENERAL DESCRIPTION 

The A-100IMWP is a self-contained access control keypad 
designed outdoor applications.  Its heavy stainless steel mul-
lion-style surface mount enclosure is designed to be used in 
narrow stile applications.  The A-100IMWP operates up to 
three outputs (two relays and 1 open-collector transistor) 
and can be used to trigger a door strike, an electromagnetic 
door lock, or any other relay-activated device.  Programming 
is performed manually at the keypad, allowing up to 150 indi-
vidual Users, each with their unique User Codes.  The A-100 
Series includes the indoor stainless steel A-100 (see 
WI1495) and the rugged sealed environment A-100WP (see 
WI1496). 

 

In a typical application, the A-100IMWP will energize one or 
both relays upon the keypad entry of a valid User Code.  
Outputs 1 and 2 are two relays of the three contact Form C 
type, and Output 3 is an open collector transistor (terminal 
labeled "OC") that switches "on" (closes with the ground ter-
minal) when energized.  The length of time the outputs are 
energized (their "activation duration") can be programmed to 
between 1 and 99 seconds.  A Request-to-Exit button will 
momentarily short Output 1 by wiring terminals M and P1 
using a normally-open momentary-close switch.   

 

To program the keypad functions you must first perform the 
initial startup procedure, then enter 

Program Mode 

by press-

ing the Master Code at the keypad.  Once in Program Mode, 
all system functions can be accessed and programmed.  
Exit Program Mode to put the keypad (with its new program-
ming) into use. 

SPECIFICATIONS 

12 to 24VDC (polarized) or 12 to 24VAC voltage input  

Output 1:  5A/250VAC relay 

Output 2:  1A/125VAC relay 

Output 3:  250mA open collector  

Capacity of 150 User Codes of 3 to 6 digits 

Output activation duration programmable from 01-99 
seconds (program "00" to select "toggle" mode) 

All programming stored in non-volatile EEPROM mem-
ory 

Orange LED Keypress feedback 

Output #1 relay activation duration programmable per 
user code 

Keypad illumination duration programmable from 10-99 
seconds (for backlit keypad models only) 

Tamper switch output terminals (S1 - S2) on PCB 

Sounder feedback "beeps" can be activated or deacti-
vated for user code entries 

Operating Temperature:    -13°F to 131°F 

                                                 -25°C to +55°C 

Dimensions (WxHxD):    1¾" x 6½" x 1 1/8" 

                                                 4.4cm x 16.5cm x 2.9cm 

Operating Voltage:      12VDC to 28VDC 

                                          10VAC to 26 VAC 

Maximum Current Draw: 

12VDC:  15mA (Standby)     108mA (Active) 
24VDC:  21mA (Standby)     125mA (Active) 
12VAC:  33mA (Standby)      192mA (Active) 
24VAC:  54mA (Standby)      233mA (Active) 

 
 

GETTING STARTED 

First Time Startup--Self-Test 

After you unpack the lock from its factory packaging, we 
recommend you perform the initial startup procedure 
(outlined below).  For keypads already in use, this startup 
procedure can also be used to erase all existing keypad 
programming and return the keypad back to its original 
"out of box" factory default condition.   

 

1.  

Install the jumper 

located on the back of the keypad 

(right position). 

2.  

Apply power 

(12-24VDC polarized or 12-24VAC) to 

the power input terminals. 

Orange LED blinks once 

3.  

Press 

7890#123456*

  

Red LED turns ON 

Orange LED turns ON 

Green LED turns ON 

 

345 Bayview Avenue 

Amityville, New York 11701 

For Sales and Repairs 1-800-ALA-LOCK 

For Technical Service 1-800-645-9440 

 

 

Publicly traded on NASDAQ   Symbol: NSSC 

© ALARM LOCK 2006 

A-100IMWP Wiring Table  

Description 

Wire Colors 

+ 12V or 24V AC/DC Input 

Red 

– Ground 

Black 

Request to Exit Input 

Purple 

Request to Exit Input 

Pink 

Relay 1 Normally Open 

Yellow 

Relay 1 Common 

Brown 

Relay 1 Normally Closed  

Dark Blue 

Relay 2 Normally Open 

Light Blue 

Relay 2 Common 

 

Light Green 

Relay 2 Normally Closed 

 

Orange 

Open Collector Output 

Dark Green 

Tamper SW Output 

Gray 

Tamper SW Output 

White 

Summary of Contents for A-100IMWP

Page 1: ...150 User Codes of 3 to 6 digits Output activation duration programmable from 01 99 seconds program 00 to select toggle mode All programming stored in non volatile EEPROM mem ory Orange LED Keypress fe...

Page 2: ...below Think of a new four digit numeric Master Code and either commit it to memory or write it here ___ ___ ___ ___ Note Only numbers zero through 9 are valid digits for either User Codes or the Mast...

Page 3: ...vation Duration Program time from 01 to 99 seconds Program 00 to select latch mode where output remains activated by the entry of a valid User Code until deactivated by the entry of a second valid Use...

Page 4: ...er G1 User Code G1 re enter User Code G1 Some examples of the 2 digits field press 12 to activate Outputs 1 and 2 press 23 to activate Outputs 2 and 3 press 13 to activate Outputs 1 and 3 press 02 to...

Page 5: ...twhile waiting for a keypress Confirmserrors Blinkswhen editing an existing User Number Orange Flashes to confirmkeypress Steady On to confirmin ProgramMode Flashes to confirmkeypress Green Confirmsac...

Page 6: ...ter User Code G1 33 Add or Edit a User Code with Output 1 Duration Press 33 G1 time 01 99 G1 User Number G1 User Code G1 re enter User Code G1 34 Delete User Code Press 34 G1 User Number G1 52 Add or...

Page 7: ...7 MOUNTING TEMPLATE The A 100IMWP is designed to be installed in its stainless mounting base The base is 1 wide and 6 tall...

Page 8: ...roduct has been repaired by others improperly installed improperly used abused altered damaged subjected to accident nuisance flood fire or acts of God or on which any serial numbers have been altered...

Reviews: