3
0x01, Alarm Level == 0x11)
to the Module. The load or the lamp plugged into
the On/Off Module SHD2110 or Lamp Module SHD2210 will flash for 10
seconds.
Advanced Operation
The following information is for someone that has some experience setting up a
Z-Wave system or someone that has computer software running a Z-Wave
controller.
Enabling/Disabling Power Saving Function (for testing)
When no movement has been detected for 10 seconds, the SHD1112 will enter the
power saving mode. It can be disabled or enabled power saving function by setting
Configuration Parameter # 3.
This parameter can be configured with the value of 0 through 127, where 0 means
power saving being enabled and others mean power saving being disabled.
Note:
As long as the batteries have been refitted, the Detector will enable the
power saving function automatically.
Configuring the Phase Level of ON Command
The Configuration parameter that can be used to adjust the phase level of ON
command is transmitted is Configuration Parameter # 1. This parameter can be
configured with the value of 0 through 127.
Value 0: Set Device OFF(0x00)
Value 1-99: Set Device On (1-99)
Value 100-127: Set Device On to the last phase (0xFF)
Note:
0xFF means the device will be on to the last phase before the device was
turned off.
Wakeup Command Class
The Motion Detector will send a Wakeup Notification Command if it has been
included into a Z-Wave network. The prerequisite is the connected Z-Wave
controller needs to emit a node ID and wakeup time interval to the Detector.
The Motion Detector will wake up periodically as desired depending on time interval
you set from wake up command class and resend the Wakeup Notification
Command unless configured for another time interval. The Motion Detector will stay
awake for 10 seconds and then go back to sleep to conserve battery life.
The time interval between Wakeup Notification Commands can be adjusted if you
have a device in which that is supported. Refer to that device
’s instructions.
Troubleshooting
Symptom
Possible Cause
Recommendation
Cannot carry out
inclusion and association
1. Run out of battery
power
2. Check if reverse
battery polarity
3. Check if the detector
is out of order
1. Replace a new
battery
2. Refit the battery
with correct polarity
3. Ensure the
detector is
working properly
Cannot control the
connected modules
1. Run out of battery
power
2. Check if the detector
is out of order
1. Replace a new
battery
2. Ensure the
detector is working
properly
The detector not working
1. Run out of battery
power
2. Check if the mounting
location is proper
3. Check if the detector
is mounted above a
radiator or heater
4. Check if the detector
is out of order
1. Replace a new
battery
2. Reposition its
mounting location
3. Remove the
source of
interference or
reposition its
mounting location
4. Ensure the
detector is working
properly