ZURN AquaSense ZEMS6142AV Installation, Operation, Maintenance And Parts Manual Download Page 6

FV38-WCS • Page 6

Figure 12

Figure 13

STEP 10  –  Test and Adjustment  (Figure 13)

(Also see “Sensor Features” on Page 7.)
Zurn Automatic Sensors are preset at the factory and provide
the user with selectable options as follows:

Switch 1  –  Automatic Flush (Factory setting is on.)

Switch 2  –  Red/Green LED (Factory setting is on.)

Switch 3  –  Courtesy Flush (Factory setting is on.)

•  Red/Green LED – 

With power applied the red light will 

illuminate when an object is detected. The green light will
illuminate after the object has been detected for a minimum
of 8 seconds then leaves. The green light indicates the 
flushing sequence.

•  Range Adjustments – 

The Zurn Automatic Sensors are 

factory set to operate at a range of 50". This range should 
be satisfactory for most installations. If the range is too short
(i.e., not detecting the user) or too long, adjust the range.

• 

To Make A Range Adjustment – 

Remove the rubber push

caps. The range adjust ment is shown in Figure 13. Using a
small screwdriver, turn the range adjustment clockwise to
increase range (maximum range is 60") or counterclockwise
to decrease range (minmum range is 12").

CAUTION:

Range adjustment rotates only 1/2 turn total from

min. to max. Do not exceed this or sensor will be damaged.

Stand in front of the Zurn Automatic Sensor at the desired distance;
the red light will illuminate when you are within range.

Repeat adjustment procedure until the desired range is obtained.

• Switch Settings

(Figure 13)

The three switches control the following options. They can be
activated or deactivated by means of the switches (down is
on, up is off).

Switch 1 – Automatic Flush – 

The unit will auto matically

flush 24 hours after last user.

Switch 2 –  Red/Green LED  – 

When an object is detected

the Red LED illuminates. The Green LED illuminates while
flushing.

Switch 3 – Courtesy Flush – 

When an object has been

detected for two seconds, the unit flushes and goes into the
normal mode. This is repeatable after 90 seconds.

NOTE:

After the options have been selected the reset button

must

be pushed for sensor to accept selections. Make sure

rubber push caps are securely installed after making adjust-
ments to protect sensor from moisture.

STEP 11  –  Adjust Control Stop 

(Figures 6 and 12)

Adjust the control stop to meet the flow rate required for proper
cleaning of the fixture. Open control stop counter clockwise one-
half turn from closed position. Activate Flushometer simulating a
user. Adjust the control stop after each flush until the rate of
flow delivered properly cleanses the fixture.

RUBBER

PUSH CAPS

RESET BUTTON

RANGE
ADJUSTMENT

SELECTION
SWITCHES
(SHOWN IN
FACTORY 
POSITION)

SENSOR
COVER

GREEN

BLUE (–)

BROWN (+)

VALVE BODY COVER

INTERNAL PLASTIC
COVER

TRIP MECHANISM

CONTROL STOP

INTERNAL KIT

Summary of Contents for AquaSense ZEMS6142AV

Page 1: ... prepaid at Sanford NC with evidence that they have been properly maintained and used in accordance with instructions We shall not be responsible for any labor charges or any loss injury or damages whatsoever including incidental or consequential damages The sole and exclusive remedy shall be limited to the replacement of the defective goods Before installation and use the purchaser shall determin...

Page 2: ...nections Sensor units should not be located across from each other or in close proximity to highly reflective surfaces The Zurn AquaVantage is designed to operate over the entire pressure range recommended by plumbing fixture manufacturers and will produce a metered flush when activated Protect the chrome or special finish of this AquaVantage Do not use toothed tools to install or service the valv...

Page 3: ...upply power to a maximum of eight flush valves for an approximate three day period during a power failure The Low Battery indicator will come on when the batteries have reached a caution level The Flushometers will function when the light is illuminated until the batteries are completely discharged The Low Battery light will illuminate even if the main power has not failed but the batteries have d...

Page 4: ...leave a minimum of 1 1 4 of scoriation to ensure engagement with compression coupling Assemble pipe elbows couplings slip washers rubber gaskets and flanges as illustrated in Figure 8 Hand tighten all couplings Once installation is completed tighten all connections STEP 5 Actuator Cable Installation Figures 9 and 10 1 Drill 1 3 4 diameter hole per Figure 9 2 Run fish tape from electrical box to 1 ...

Page 5: ...p Figures 11A and 11B Be certain power is off to prevent damage to electrical components Connect the sensor to the actuator and power converter exactly as shown in Figure 11A Figure 11B if battery backup is being used Also the wiring diagram on the battery backup may be used Double check that power converter polarity is correct STEP 7 Mount Automatic Sensor Figure 2 Install the Zurn Automatic Sens...

Page 6: ...c Sensor at the desired distance the red light will illuminate when you are within range Repeat adjustment procedure until the desired range is obtained Switch Settings Figure 13 The three switches control the following options They can be activated or deactivated by means of the switches down is on up is off Switch 1 Automatic Flush The unit will automatically flush 24 hours after last user Switc...

Page 7: ...ration lights red and green The red light is lit when an object is detected The green is lit when the unit is flushing The indicator lights can be manually activated deactivated at any time Maintenance Override For Maintenance Purposes The sensor may be disabled for 10 minutes by placing a magnet on the sensor lens for 3 to 5 seconds After 10 minutes the sensor will automatically resume functionin...

Page 8: ...m 5A P6000 QT1 4 CP 11 2 x 4 Outlet Tube CP 6 P6000 G TUBE Flange 7 P6000 HN CP 11 2 Slip Joint Coupling CP 8 P6000 QT4 11 2 Coupling S 30 Gasket 9 P6000 QT3 L RB 11 2 Outlet Tube RB specify L dim 10 Specify Series Valve Body CP specify valve type Item Part No Description 11 PESS6000 22 Sensor Cover Plate 12 PESS6000 23 Bracket 13 PESS6000 24 Push Button 14 PESS6000 25 Yoke 15 PEMS6000 26 Sensor 1...

Reviews: