Problem

Corrective Action

“Status – Good” posted in plumbSMART and faucet actuation 

event data not appearing in plumbSMART (< 2 hours) or 

“Device Not Communicating” warning or severe alert posted in 

plumbSMART for all devices (> 3 hours)

Step 1

Verify gateway Status LED flashes twice every 2 seconds.  If LED 

is OFF or ON solid, power cycle the gateway and wait for no 

more than 5 minutes for unit to initialize and connect.

Step 2

After initialization is finished, LORA LED should turn ON solid 

within an additional minute.

Step 3 

If LORA LED does not turn ON solid and ethernet cable 

connected, contact facility IT administrator to modify port rules 

to allow Zurn gateway to access the internet via local router.  

If gateway model is ETH/LTE, visually verify SIM card is installed 

in designated slot on the side of gateway.  If unit has a SIM card, 

then disconnect ethernet cable and power cycle the gateway 

and wait for unit to initialize and connect.  LORA LED should 

turn ON solid after initialization.

Step 4

If problem still present, move gateway closer to LoRa monitors 

and/or verify gateway mounting, orientation and connections 

comply with requirements listed in Zurn Gateway Installation 

Guide.

Contact Zurn Customer Service at 1.855.ONE.ZURN 

(1.855.663.9876) for assistance with additional troubleshooting 

steps.

Trouble Shooting: Gateway

For further assistance with troubleshooting, visit https://plumbsmart.zurn.com/app/training

Problem

Corrective Action

“Device Not Communicating” posted in plumbSMART

Step 1

Verify LoRa Monitor electronics is plugged in.  Alert on product’s 

page in plumbSMART should clear within 1 hour or on next 

faucet activation. (Refresh web page by clicking on reload icon 

in the browser to clear the alert.) 

Step 2

If problem still present, verify gateway is within range of LoRa 

Monitor and functioning (see Gateway Troubleshooting section)

Step 3 

If problem still present, verify plumbSMART subscription status 

on product page’s Details tab listed as “Activated” 

NETWORK:  

Senet

SUBSCRIPTION STATUS: 

Activated

LAST HEARD FROM: 

07/14/2020, 04:29 PM CDT

If listed as “Deactivated”, contact Zurn Custom Service at 1.855.

ONE.ZURN (1.855.663.9876) for assistance.

“Status – Good” posted in plumbSMART and faucet not 

actuating 

Step 1

Verify LoRa Monitor’s cables are connected to IR sensor 

and Faucet actuator electronics.  Restore proper electrical 

connection, as needed.

Step 2 

Test activate the faucet.

If problem persists, see Faucet Troubleshooting section in this 

guide for other steps.

“Status – Good” posted in plumbSMART and faucet actuates but 

usage event data not appearing in plumbSMART Charts

Step 1

Verify gateway is powered and LoRa Status LED is ON.  If 

not, apply power per Zurn Gateway Installation Guide or see 

Gateway Troubleshooting section in this guide of other steps.

Step 2

If problem still present, verify plumbSMART subscription status 

on product page’s Details tab listed as “Activated” 

NETWORK:  

Senet

SUBSCRIPTION STATUS: 

Activated

LAST HEARD FROM: 

07/14/2020, 04:29 PM CDT

If listed as “Deactivated”, contact Zurn Customer Service at 

1.855.ONE.ZURN (1.855.663.9876) for assistance.

Step 3

If problem still present, the LoRa Monitor electronics may be 

faulty.  Contact Zurn Customer Service at 1.855.ONE.ZURN 

(1.855.663.9876) for assistance with additional troubleshooting 

steps and, if needed, unit replacement.

Trouble Shooting: LoRa Monitor

For further assistance with troubleshooting, visit https://plumbsmart.zurn.com/app/training

Summary of Contents for AquaSense Z6920-XL-W2

Page 1: ... of the product for his intended use and the purchaser assumes all risk and liability whatever in connection therewith Where permitted by law the implied warranty of merchantability is expressly excluded If the products sold hereunder are consumer products the implied warranty of merchantability is limited to a period of three years and shall be limited solely to the replacement of the defective g...

Page 2: ...For this reason these instructions should be left on site with the facility or maintenance manager Specifications Voltage 6 VDC Series 4 AA Alkaline or Lithium for faucet 4 VDC Series 4 AA Alkaline or Lithium for monitor Sensor Range Self calibrated dependent upon sink depth and finish Operating Water Pressure 10 125 psi Operational Water Temperature 33 F to 140 F 1 C to 60 C Aerator 1 5 GPM Vanda...

Page 3: ...lastic mounting washer 4 Assemble the electronics module Do not connect the electronic module to spout Spout Installation Instructions Cable to monitor 1 Install Monitor on wall surface within 2 feet radius of faucet with dry wall anchors screws or doubled sided VHB tape 2 Loosen lid screw with supplied 3mm Allen wrench Open lid and install supplied batteries Close lid and tighten lid screw 5 Tigh...

Page 4: ...eway is now ready to transmit data from your Zurn connected product 4 Zurn Gateways have been set to DHCP by default Please consult local IT support for possible additional access requirements for your network Step 3 Determining general Location for the Zurn Gateway Select a location central to all devices to be connected to this gateway Place the gateway as high as possible such as near the top o...

Page 5: ...Off Off Off Off Off Off On On Mode Select Sensing Mode Metering Mode Off On Sensor Sensitivity Low Off Normal On Mode A Off Mode B On Adjustable modes and features selection For further assistance with troubleshooting visit http www zurn com Problem Possible Cause Corrective Action Faucet is non responsive Battery voltage low or no power Change out batteries or verify power provided by ACA Sensor ...

Page 6: ...should clear within 1 hour or on next faucet activation Refresh web page by clicking on reload icon in the browser to clear the alert Step 2 If problem still present verify gateway is within range of LoRa Monitor and functioning see Gateway Troubleshooting section Step 3 If problem still present verify plumbSMART subscription status on product page s Details tab listed as Activated NETWORK Senet S...

Page 7: ...t data is properly presented in Chart Step 3 If problem still present contact building maintenance to verify sufficient water pressure in lines Step 4 If problem persists the LoRa Monitor may be paired to the incorrect fixture model Verify product image and model number from plumbSMART product page Details tab against model number cited on product literature and packaging If incorrect contact Zurn...

Page 8: ...3 8 Gooseneck Spout with Nut Item 1 P6900 GB 1 5 GPM Vandal Resistant Laminar Aerator Item 2 P6900 20J GN Z6920 No Lead Spout Base with Sensor Assembly Item 3A P6920 XL 2 Z6922 No Lead Spout Base with Sensor Assembly Item 3B P6922 XL 2 Z6920 Mounting Kit Item 4A P6920 43 Z6922 Mounting Kit Item 4B P6920 43 Smart Connected Faucet Retrofit Kit Item 5 P6900 RK W2 Description Product No Filter Kit Ite...

Page 9: ...TRIES LLC 511 W Freshwater Way Milwaukee WI U S A 53204 Ph 1 855 ONE ZURN Fax 919 775 3541 In Canada ZURN INDUSTRIES LIMITED 7900 Goreway Drive Unit 10 Brampton Ontario L6T 5W6 Ph 905 405 8272 Fax 905 405 1292 Rev A Date 01 20 21 C N No 143366 Prod Dwg No FV744 ...

Reviews: