background image

FV62  Rev. D   11/14/18
Page 2    

PRIOR TO INSTALLATION
Prior to installing the AquaSense “AV” Flushometer, install the items 
listed below:
•Closet or urinal fi xture
•Drain line
•Water supply line
IMPORTANT:
 • ALL PLUMBING IS TO BE INSTALLED IN ACCORDANCE WITH 

APPLICABLE CODES AND REGULATIONS.

 • WATER SUPPLY LINES MUST BE SIZED TO PROVIDE AN 

ADEQUATE VOLUME OF WATER FOR EACH FIXTURE.

 • FLUSH ALL WATER LINES PRIOR TO OPERATION (See Step 9).
The AquaSense “AV” is designed to operate with 20 to 80 psi (138 to 
552 kPa) of water pressure. THE MINIMUM PRESSURE REQUIRED TO 
THE VALVE IS DETERMINED BY THE TYPE OF FIXTURE SELECTED.  
Consult fi xture manufacturer for pressure requirements.
Protect the chrome or special fi nish of this fl ushometer. DO NOT USE 
TOOTHED TOOLS TO INSTALL OR SERVICE THE VALVE.

4. Determine the length of vacuum breaker tube required to join the fl ush 

valve and fi xture spud. Cut the vacuum breaker tube, if required, to this 
length. Assemble the vacuum breaker tube assembly and spud nut 
assembly to the fl ush valve and fi xture spud.

5. Hand tighten spud nut and vacuum breaker tube nut to fi xture and fl ush 

valve. Adjust the valve assembly for plumb. Tighten fi xture spud nut, 
vacuum breaker tube nut and lock nut with a wrench. 

Do not turn water 

on until batteries are inserted –see 8.

2. Prior to inserting the fl ush valve tailpiece into stop valve, be certain that 

the o-ring seal is located in o-ring seal groove at the end of the tailpiece 
and the locking nut and locking snap ring are located as shown. Care 
should be taken not to damage the o-ring when inserting the tailpiece 
into the stop valve. If lubrication is needed,  wetting the o-ring with water 
will be suffi cient.

1. Install stop valve assembly using proper size supply escutcheon and 

sweat solder adapter kit if applicable. Thread sealing compounds should 
be used on male NPT threads only. Flush supply line by opening the 
control stop. Turn on water supply to fl ush line of any debris or sediment.  
Then close control stop.

1

6. Loosen handle nut, aim sensor at desired tilt angle (horizontal, tilt up, or 

tilt down), hold in place and tighten handle nut

4

Adjust sensor 
angle to pick 
up user

Tilt Down

Horizontal

Tilt Up

6

7

7. Remove electronics access cover with vandal-resistant hex wrench 

provided.  Insert preassembled battery holder into electronics 
compartment.  Connect battery cable connector to electronics cable 
connector.  

(Important: Insert non-connector end of battery holder 

fi rst, as shown.  Ensure foam spacer is in place)

 

2

3. Insert the fl ush valve tailpiece into the stop valve and hand tighten the 

lock nut to the stop valve. Plumb the entire unit.

3

Summary of Contents for AquaSense AV ZR Series

Page 1: ...provided we are notified in writing of such defect and the goods are returned to us prepaid at Sanford NC with evidence that they have been properly maintained and used in accordance with instructions We shall not be responsible for any labor charges or any loss injury or damages whatsoever including incidental or consequential damages The sole and exclusive remedy shall be limited to the replacem...

Page 2: ...nut with a wrench Do not turn water on until batteries are inserted see 8 2 Prior to inserting the flush valve tailpiece into stop valve be certain that the o ring seal is located in o ring seal groove at the end of the tailpiece and the locking nut and locking snap ring are located as shown Care should be taken not to damage the o ring when inserting the tailpiece into the stop valve If lubricati...

Page 3: ...he final setting for urinals should be such that the fixture will not overflow when the valve is actuated twenty times in succession The stop cap screw cover should be replaced after final adjustments have been made Sensor Range Adjustment The range is factory set for urinal or closet applications If necessary the sensor range can be adjusted Pressing the reset button will initiate a ten minute se...

Page 4: ...ent For the first ten minutes of operation the red light will flash when an object is detected 2 Low Battery Indication When the batteries have reached the caution level the red light will flash when an object is detected 3 Abnormal Reflection Indicator When a reflective surface is present for longer than 30 minutes the red light will flash indicating that an object is being continuously detected ...

Page 5: ...age while reassembling the unit Insert the solenoid Item 7 into the housing and install the solenoid retaining clip Item 8 When installed properly the end of the solenoid housing is free to rotate Note Be careful not to crimp the battery wires while inserting the solenoid into the housing 3 Reinstall the RetroFlush sensor assembly Item 9 onto the flush valve using a wrench Be sure the solenoid inl...

Page 6: ...Item 8 When installed properly the end of the solenoid is free to rotate Notes Be careful not to crimp the battery wires while inserting the solenoid into the housing Also be sure the blue and gray wires of the solenoid valve extend into the sensor module cavity of the housing Item 9 6 Connect the sensor module blue and gray wires to the solenoid valve blue and gray wires and reinstall the sensor ...

Page 7: ...lume Control 3 5 GpF 3 PR6000 EU25 WS Low Consumption Urinal Volume Control 1 6 GpF 3 PR6000 EU25 WS1 Diaphragm PR6000 E15A Sensor Module Replacement Kits Product No Solenoid Valve Replacement Kit 8 9 10 PR6000 M Sensor Lens Kit 12 PR6000 SC High Volume Sensor 13 PR6000 SH Low Volume Sensor 13 PR6000 SL Battery Holder with Connecting Cable 15 16 PR6000 MB Metal Housing 11 PR6000 MH Vandal Resistan...

Page 8: ...e or chemical cleaners to clean flush valve as they will dull the luster and attack the chrome or special decorative finishes Use only mild soap and water then wipe dry with a clean cloth or towel While cleaning the bathroom tile and floor the flush valve and electronics should be protected from splattering of water cleaner acids and cleaning fluids that can damage the sensor flush valve Problem C...

Reviews: