background image

Caution!

The CPT 1/A transmitter should be connected only after the supply voltage has been checked. The transmitter outlets should not 

be connected to the actuator frame, neither should they be earthed, even accidentally.

1)

   Before the supply voltage is checked the transmitter should be disconnected from the AC mains. At the actuator terminals 

to which the transmitter is connected, the voltage can be best measured by a digital voltmeter withan input resistance of 
at least 1 Mohm. This voltage should be within the range of 18 to 25 Vdc, but should not exceed 30 V since otherwise 
the transmitter might be damaged. Then, connect the transmitter so that the positive terminal of the power supply is 
connected to the „plus“ pole of the transmitter, i.e., to the pin provided with a red insulator (r)+ (nearer to the transmitter 
centre), and the terminal with a white coating (extended to terminal -52- or H) to the „minus“ pole of the transmitter (white 
insulator). In the la-test design variant, the red conductor is „plus“ and the black conductor is „minus“.

2)

   Connect temporarily a milliammeter, preferentially a digital instrument with an accuracy of at least 0.5% in series with 

the transmitter. Bring the output shaft into the CLOSE position. In this case, the signal value should decrease. If this is not 
the case, turn the output shaft in the CLOSE direction till the signal starts decreasing and the output shaft reaches 
the CLOSE position.
Then, loosen the screws of the transmitter shim plates so that the whole transmitter can be turned to set a current 

of 4 mA. Retighten the screws of the transmitter shims. Subsequently, adjust the actuator output shaft to the OPEN 
position. Set the current to 20 mA by the trimming resistor fitted on the transmitter face (nearer to the edge). 

The trimmer has 12 turns, but no stops. Thus, it cannot be damaged.
If a considerable correction of 20 mA current is required the 4 mA and 20 mA setting procedure should be repeated. 

Then, disconnect the milliammeter. Avoid turning the screw situated nearer to the middle and secured by a dropof 
varnish. Retighten the fixing screws of the transmitter shim plates and secured them with a drop of varnish. 
On completion of the adjusting procedure, check the terminal voltage of the transmitter by a voltmeter. This voltage 
should be within the range of 9 to 16 V with 20 mA current.

 

Note:

The transmitter characteristic has two branches: A descending one and an ascending one with respect to 

the CLOSE position (Z).

Setting of current position transmitter CPT1. 

Before starting setting the current transmitter it is necessary to set the end-limit positions (torque or position switches) of 

the actuator and connect them into the tripping circuit of the electric motor. In case of an external source of feeding voltage, 
verification must be carried out that it does not exceed the maximum value 30 V DC (limit value when CPT1 is still not 
damaged). Recommended value is 18 – 28 V DC. 

Positive pole of the source is connected to the positive pole of the 

transmitter CPT1; a milli-ammeter of precision at least 0.5 % connected into 
the circuit. The current loop must be earthed in one point. The figure does not 
show the earthing that can be made at any point of the circuit. 
1.  

Shift the output shaft into the position Closed. During closing, the current 
signal value should decrease. If it increases release the transmitter body 
and, by turning of about 180°, shift to the descending part of the 
outputcharacteristics. Set 4 mA by fine turning. Tighten the shim plates to 
secure the transmitter against spontaneousturning.

2.  

Shift the output shaft to the position Open and set 20 mA using a potentio-
meter on the transmitter body. The potentiometer has a range of 12 revo-
lutions and it has no stops so that it cannot be damaged by furtherturning. 

3.  

Once again verify the current value in the position Closed. If it has changed 
too much repeat the points 1. and 2. If the required corrections are large this procedure should be repeated several times. 
After the setting, securethe transmitter against turning and drip the screws with varnish. 

4.  

Use a voltmeter to check the voltage on the CPT1 terminals. In order to keep linearity of the output signal 
the voltage must not drop below 9 V, not even with off-take 20 mA. If this condition is not met it is necessary to increase 
the feeding voltage (within the range of recommend values) or to decrease total resistance of the current loop R.

Setting of current position transmitter DCPT. 

1.  Set of end-limit positions

Before starting the setting, verification must be carried out that the end-limit positions are within the range 

60° – 340° of revolution  DCPT. Otherwise, after setting, an error arises (LED 2x).

1.1. Position “4 mA”

Set the drive into the required position and press the push-button 

“4”

 until LED blinks (about 2 s).

12

Summary of Contents for MODACT MON 100/130-100

Page 1: ...Electric Multi turn Actuators 1 10 MOUNTING INSTRUCTIONS MOUNTING INSTRUCTIONS Type numbers 52 030 52 036 Type numbers 52 030 52 032...

Page 2: ......

Page 3: ...heated up blown out air is drawn in the motor again For air inlet the minimum distance from the wall is 40 mm Therefore the space in which the motor is located should be sufficiently large clean and v...

Page 4: ...million cycles with operation time during which the output shaft is moving at least 250 hours Service life in operating hours h depends on load and number of switching Not always high frequency of sw...

Page 5: ...se asynchronous motor 1 drives via countershaft gearing 2 the sun gear of differential gear unit 2 which is enclosed in the supporting actuator box power gear transmission 3 In the mechanical power co...

Page 6: ...nit 14 Transmitter adjusting mechanism 15 Resistance position transmitter with mechanical position indicator 16 Position limit switching unit 17 Anti condensation heater 66 Fixing screws 67 Basic cont...

Page 7: ...e division of the band between the points of maximum and minimum tripping torque and thus for more accurate adjustment of the torque outside the factory in a location where no loading stand is availab...

Page 8: ...t of the working stroke of the actuator except the narrow band about the end positions The signalling switch should close before the position limit switch while the output shaft is still moving The up...

Page 9: ...cal position indicator is always 160 for different values of working stroke of the actuator and thus for different amounts of displacement of the camshaft in the signalling unit This ensure that at an...

Page 10: ...cator 42 Resistance transmitter 43 Pinion of resistance transmitter Fig 7 Resistance transmitter with position indicator Legend K 1 Gear K 2 Drive gear K 3 Adjusting gear 47 Lock screw of adjusting ge...

Page 11: ...Then the required gear of the pair of gears fitted on the transmitter shaft should be brought into engagement The gear of a smaller diameter is designated A whereas the larger gear is designated B Ad...

Page 12: ...range of 9 to 16 V with 20 mA current Note The transmitter characteristic has two branches A descending one and an ascending one with respect to the CLOSE position Z Setting of current position trans...

Page 13: ...nd 20 depressed and release them after a single blink of LED In this way the option menu 4 1 Calibration of current 4 mA is entered 4 1 Calibration of current 4 mA Connect the ammeter to testing termi...

Page 14: ...the rod should shift out again If this is not the case turn the screw 56 or 59 by a small amount 5 Readjust the fitting to the OPEN position by the required number of revolutions making use of the act...

Page 15: ...documentation Any discrepancy defect or damage should be immediately reported to the supplier When the unpacked actuator is not immediately installed it should be stored at a dust free location with...

Page 16: ...case the two phase conductors should be mutually reversed on the terminal board 10 OPERATION AND MAINTENANCE Depending on the operating conditions the operation of rotary actuators usually involves o...

Page 17: ...he change over gear round a suitable amount with respect to the output shaft For this purpose the change over gearis provided with two slots for a connecting spline Moreover the change over gear can b...

Page 18: ...94 2735 2 3 4 8 26 x x U x x MON MOP 95 125 7 C 63 95 125 7 1xx7070 8AB 0 09 630 0 36 2 2 49 x x C x x MON MOP 100 210 9 C 210 9 1xx7070 6AA 0 18 850 0 74 2 3 49 x x 0 x x MON MOP 100 185 15 C 185 15...

Page 19: ...00 1330 35 1xx7107 4AA 3 1420 6 40 5 6 87 x x 7 x x MON MOP 1100 1530 63 500 1100 1530 63 1xx9113 4LA 5 5 1440 12 10 6 8 109 x x 9 x x MON MOP 1250 1640 45 630 1250 1640 45 1xx7134 6AA 5 5 950 12 80 5...

Page 20: ...30 8 7 4 3 50 x x 5 x NJ MONJ 95 124 145 63 95 124 145 1LF7090 2 1 5 2845 9 25 4 5 51 52 031 x x F x NJ MONJ 150 195 40 100 150 195 40 1LF7083 4 0 75 1405 4 8 3 9 41 x x 9 x NJ MONJ 160 208 65 100 160...

Page 21: ...ers are given in Tables 1 2 including designation In this position give the number or letter corresponding to the required parameters MODACT MON MOP MONJ Control MODACT MONJ MON MOP Without signalling...

Page 22: ...375 234 445 Type marking 52 036 xxxxN design A 52 036 xxxxN design B 1 C D E A B C 757 463 750 712 418 705 Type marking H A 97 C A 298 C B 484 342 178 MAX 963 J K E G F B 375 Non passable punch throug...

Page 23: ...694 200 144 350 455 145 382 123 519 288 807 250 190 410 540 178 442 153 598 328 926 375 234 470 Type marking 1x cable bushing M 20x1 5 10 14 mm 1x cable bushing M 25x1 5 13 18 mm external protective...

Page 24: ...ld not be stressed by another additional force The protective extension should be made by the customer including the hole in its cover Modifications for rising spindle Type No 52 030 52 031 52 033 52...

Page 25: ...2 140 165 254 298 M 10 M 16 M 20 M 16 M 20 4 4 4 8 8 3 4 5 5 5 12 5 20 25 20 25 40 60 80 100 120 10 12 15 16 18 14 20 24 30 40 28 41 5 53 72 72 20 30 40 50 60 50 70 90 110 120 22 5 33 43 53 5 64 6 8 1...

Page 26: ...1 72 70 165 110 695 2 72 130 5 32 120 127 4 A B1 identical dimensions A B1 Assignment of adapters to actuators Type No Dimension mm Shape 52 030 52 031 52 033 52 035 52 032 52 034 d1 d2 f8 d3 d4 Numb...

Page 27: ...ol BMO Position transmitter resistance V1 V2 current passive CPT1 current active DCPT DCPZ without transmitter Signalling switches SO SZ Blinker B Electric motors used For the actuators MON MOP three...

Page 28: ...electric motor Example of one phase electric motor control MODACT MONJ actuators Example of wiring power circuits for controlling a single phase electric for selecting both directions of rotation Con...

Page 29: ...motor Wiring diagram of MODACT MONJ electric actuators DCPT DCPZ BMO CPT1 CPT1 open close P0938 E Outlet position Control voltage 3 phase motor Wiring diagram of MODACT MON MOP electric actuators DCPT...

Page 30: ...Z2 U2 Z1 C C 1f motor P0939 E L1 N L1 ZAV OTV mA mA Outlet position Control voltage 1 phase motor P0940 E Wiring diagram of MODACT MON MOP electric actuators 5 6 41 30 29 33 34 36 35 13 12 15 16 17 18...

Page 31: ...IA XGK 12 88 J21 ICS available from ZPA Pe ky 1 Torque limit switches MO MZ 2337441060 to separate order Microswitch D433 B8LD available from ZPA Pe ky 1 Position limit switches PO PZ 2337441098 to se...

Page 32: ...2785014 for the rising spindle of fitting Sealing ring 60x50 PN 029280 2 1 Sealing of output shaft 2327311090 in the control box cover 52 033 Sealing ring 200x3 PN 029281 2 1 Packing between the power...

Page 33: ...ntrol box cover 2327311044 Sealing ring 90x80 PN 029280 2 1 Sealing of output shaft 232p7311011 in the control box cover Sealing ring 32x2 PN 029281 2 1 Sealing of glass 2327311037 of local position i...

Page 34: ...control board 99556 3 52 031 6 Potentiometer 2 x 100 ohm 40510285 1 To be mounted on control board 99556 3 52 030 Potentiometer 2 x 100 ohm 214628650 1 To be mounted on control board for indicator 99...

Page 35: ...n actuators MODACT MO EEx MOED EEx Explosion proof electric multi turn actuators MODACT MOA Electric multi turn actuators for nuclear power stations application outside containment MODACT MOA OC Elect...

Page 36: ...1 9 fax 420 321 785 165 420 321 785 167 e mail zpa zpa pecky cz ZPA Pe ky a s t 5 kv tna 166 289 11 PE KY Czech Republic www zpa pecky cz el 420 321 785 141 9 ax 420 321 785 165 420 321 785 167 e mail...

Reviews: