board.  There are 4 key-hole mounting points in each corner 
of the case.  The case has openings in the rear of the case 
as well as the side for all wiring.  Wiring can come from the 
back as well as the side in order to make a neat installation.   
CONTENTS 
The BPE24 includes 10 feet of pressure tubing (which can be 
cut down to size). 
 
OPERATION 
The  BPE24  controls  up to 4 zones on a single HVAC  unit. 
When the BPE24 gets a signal from the Zone Controller that 
a zone damper is to be powered open it immediately opens 
the  corresponding  zone damper(s) on the output terminals. 
Anytime the BPE24

’s pressu

re sensor detects the pressure in 

the supply plenum is higher than the Upper Limit Set Point it 
will modulate the closed zone dampers open to relieve the 
excess  pressure  into  those  zones.  As  these  dampers 
modulate open the air pressure should drop below the high 
set-point  and  the  zone  dampers  stop.    When  the  BPE24

’s 

pressure sensor is below than the Lower Limit Set Point it will 
close the zone dampers.   Once the pressure has equalized 
to higher than the Lower Limit set point and lower than the 
Upper  Limit set point the BPE24 will signal the dampers to 
stay in their current position.  
 
IMPORTANT: When the dampers are being modulated or 
signaled to stop the LEDs on the zone dampers may not be 
illuminated. This is completely normal and the LEDs will only 
illuminate  when  the  damper  is  fully  open  (green)  or  fully 
closed (red). 
 
Upper Limit 
The Upper Limit is adjus

table from 0.25”WC to 2”WC.  

This 

is  the  limit  that  once  exceeded  all  dampers  in  the  closed 
zones will begin to modulate open. To enter the Upper Limit 
menu  from  the  main  status  display  press  SW1  and  using 
SW1  and  SW2  you  can  raise  or  lower  the  Upper  Limit. 
Once you have finished setting the upper limit the menu will 
automatically exit after 5 seconds back to the main screen. 
 
Lower Limit 
The Lower Limit is adjustabl

e from 0.15”WC to 1.90”WC.

 

This  is  the  limit  that  once  the  pressure  drops  below  it  all 
dampers  in  the  closed  off  zones  will  begin  to  modulate 
closed.  To  enter the Lower Limit menu from the main status 
display press SW2 and using SW1 and SW2 you can raise 
or lower the Lower Limit. Once you have finished setting the 
lower limit the menu will automatically exit after 5 seconds 
back to the main screen. 
 
Dead Band  
There  is  a  minimum 

0.10”WC

  dead  band  between  the 

upper  and  lower  limits  that  insures  there  is  a  sufficient 

pressure  range  that  can  be  maintained  for  the dampers to 
modulate properly without constantly opening and closing to 
maintain pressure.   
 
Sensor Calibration 
The  pressure  sensor  is  factory  calibrated  but  due  to  the 
differences in elevation it may be a good idea to calibrate 
the  pressure  sensor  in  the  location  it  is  installed.  The 
important thing to note is that if the sensor is calibrated with 
the HVAC unit running or in a windy environment it can lead 
to a bad calibration measurement. 
To  calibrate  the  pressure sensor press and hold both SW1 
and  SW2  if  the  unit  does  not  immediately  show  the 

“Calibrating Please Wait”

 try pressing the upper button first 

then  the  lower button while still holding the top button. As 
soon as the calibration message appears release the buttons 
and  calibration  only  takes  approximately  6  seconds  from 
there. 
 
Display 
The  LCD  Display  will  display  the  status  of  the  zones  OP 
(open), CL (closed), or a number from 01 to 99 to indicate 
what percent the zones that were in the closed position were 
modulated  open  in  order to relieve the excess air from the 
ductwork. If a zone is available for modulation that means 
that the Zone control board is sending a close signal to the 
BPE24. In the upper right hand corner the display will read P 
in with the pressure reading being displayed just below it. 
 
Transformer 

  A  24  Volt  AC,  40VA  Transformer  is 

recommended  to  power  the  BPE24  and  can  be  the  same 
transformer powering the zone control panel.   
 

 

24V

 T

R

A

N

S

C
R

C
R

T24 -24V 40VA

TRANSFORMER

 

 
 
PRESSURE SENSOR 
The BPE24 pressure sensor is a very sensitive device, never 
blow  into  the  sensor  with  your  mouth  as  the  amount  of 
pressure that the human body can produce far exceeds the 
limitations of the sensor and it can be damaged that way. If 
there  is  a  need  to  test  the  sensor  simply  fold  the  pressure 
tube  on  itself  and  squeeze  as  this  will  create  a  gentler 
pressure increase on the sensor 
 
TROUBLESHOOTING 

Summary of Contents for By-Pass Eliminator 24 BPE24

Page 1: ...Pass Eliminator 24 Model BPE24 For use with 24V Power Open PowerClosed Damper Motors and Control Panels Only Installation and Operating Instructions ControllingYour Comfort Room by Room F o l l o w u s o n ...

Page 2: ... in the duct system modulate the closed dampers to gradually open to relieve the air pressure back below the high set point When this occurs the zone dampers will stop INSTALLATION The BPE24 can be mounted against flush surface and should be located within 10 of where the pressure sensor tube is placed in the duct Ideally if mounted next to the zone control panel this will minimize the length of w...

Page 3: ...er the Lower Limit menu from the main status display press SW2 and using SW1 and SW2 you can raise or lower the Lower Limit Once you have finished setting the lower limit the menu will automatically exit after 5 seconds back to the main screen Dead Band There is a minimum 0 10 WC dead band between the upper and lower limits that insures there is a sufficient pressure range that can be maintained f...

Page 4: ... check the transformer and the power supply to it Zone s Not Closing If a zone is not closing and there is an active HVAC call it may be that there is an excessive amount of air being bypassed into the zone End all HVAC calls and using the damper test button on the Main Controller you can check to see if the dampers are properly cycling Damper Motor Checkout Procedure To check out the dampers the ...

Page 5: ... Eliminator 24 Wiring Diagram From respective Zone Damper Connections on Zone Control Board To 24V AC on Zone Panel 24V Power Open Power Closed Dampers NOTE If there is a Specific zone that should not be used to relieve air wire zone damper directlyto zone panel ...