Testing
Test one Zonecheck
1. Insert the key into the key-switch and turn to self test (the pump light will
activate) (see fig 1).
2. When the flow-switch operates, the water-flow light will activate (please
wait for up to 30 seconds for the flow-switch to operate).
3. Return to ‘standby’ position and remove the key.
Test a group of Zonechecks
1. To test all the Zonechecks in the group, insert the key into the key-switch
and turn to group test (see fig 1).
2. Look at the central fire control panel to confirm simultaneous activation of
all the flow-switches within the group.
3. Return to ‘standby’ position and remove the key.
CONTACT CENTRAL
MONITORING STATION OR
APPROPRIATE FIRE SAFETY
PERSONNEL PRIOR TO
TESTING
When test is complete turn key back to the ‘standby’ position.
120 V,AC~, 60Hz
SELF
TEST
WATER
FLOW
GROUP
TEST
Project Fire Products Limited tel +44 (0)1889 271271
Fig 1