START-UP OPERATIONS
It is recommended to open the registration panel to verify that there have been no
movements during transport, ensuring that the pre-filter, the GRSystem and the absolute
filter are correctly positioned and fixed in position
The access panel is opened by removing the 8 M6 Allen screws (4 on each side), it being
important to re-tighten them correctly to ensure the tightness of the unit.
The unit automatically starts up when powered up. *
Before starting up, all the access panels to the equipment must be closed.
Keep the start switch in the stop position and then connect the equipment.
Connect the external general power switch to the unit, keeping the unit's start switch
in the stop position. Once this is done, check that the voltage at the electrical input
terminals of the equipment corresponds to that established on the nameplate (the
minimum allowed voltage will be 10% less than the nominal voltage indicated on the
nameplate).
It will be verified that the earth connection is well connected.
Once all the checks have been made, remove the stop position of the equipment (turn it
ON).
The fan will not start if the ductwork is not completely closed, as the connection of the
fan without load can cause overcurrents that could damage the motor.
EMERGENCY OPERATIONS
If any problems are noted on the unit, turned it off using the emergency shut-off switch.
These emergency operations will generally be the result of some problem with the
electrical circuit, in which case you may have problems with the motors. You will
therefore need to disconnect the power to locate the fault, which may be inside the unit
(short circuit) or external to it (problems with the power supply, voltage variations, etc).
In t he event of fire, it must be extinguished using suitable extinguishers. Extinguishers
should be appropriate for use on electrical fires.
9
Pure Air Residential