5.
TROUBLE SHOOTING
Fault: No functions of signal automation!
5.1 Check whether terminals 2 + 3 are connected to the correct voltage as indicated
on the unit`s name plate.
5.2 Check fuses F1 and F2 on the power supply pc-board. As replacement only use
fuses for feeble currents semi-time lag, 250 V, 5x20 mm oK
for 230V AC
1A
ident no. 683320101
for 115V AC
1,6A ident no. 683320216
for 24V DC
6,3A ident no. 683320163
5.3 Should above measures be insufficient to eliminate the failure, the key and control
pc-board as well as the power supply pc-board can be taken out easily. For this
purpose first take off the front frame and then the terminal strip. After loosening
the 4 screws in the front plate, this can be pulled out of the casing, along with
the pc-boards.
6.
TECHNICAL DESIGN
The signal automaton consists of two different sections:
6.1 The front plate with key pc-board 01616886 and control pc-board 01416877 with
all necessary keys.
The signal automaton is controlled by a micro processor. In case of a failure
this can be taken out without having effect on the hand signal release.
6.2 The power supply pc-board 01616876 with switching relay, terminal strip,
fuses and power supply.
11/09 MH
ZÖLLNER-KIEL
01808749.07-4e
subject to alteration!