background image

6

© Copyright 2015 Zoeller

®

 Co. All rights reserved.

PUMP INSTALLATION (continued)

positioning motor against the mounting frame and assembling 

with four (4) 3/8” x 3/4” cap screws.  The mounting base is 

connected at the bottom of the mounting frame with two (2) of the 

four (4) 3/8” x 3/4” cap screws.

5.   Follow steps 5, 6, 7 and 8 of Rotor Seal Assembly to reassemble 

the remainder of the pump.  Because damage to the shaft seal is 

most likely to occur in disassembly, a new seal will be necessary.

Symptom

Possible Cause(s)

Corrective Action

Pump won’t start or run.

1.   Blown  fuse.

2.   Low line voltage.

3.   Loose, broken or incorrect wiring.

4.   Defective  motor.

5.   Defective pressure switch.

6.   Impeller or seal.

7.   Bad  capacitor.

1.   If blown, replace with fuse of proper size. Use time 

delay fuses.

2.   If voltage under recommended minimum, check size 

of wiring from main switch on property. If OK, contact 

power company.

3.   Rewire any incorrect circuits. Tighten connections, 

replace defective wires.

4.   Replace.

5.   Adjust switch settings. Clean contacts with emery 

cloth if dirty.

6.   If impeller won’t turn, remove housing and locate 

source of binding.

7.   Replace.

Pump starts and stops too often.

1.   Leak in pressure tank.

2.   Defective air volume control.

3.   Faulty pressure switch.

4.   Leak on discharge side of system.

5.   Leak on suction side of system.

6.   Leak in foot valve.

1.   Repair leaks or replace tank.

2.   Clean or replace defective control.

3.   Adjust switch settings. Clean contacts with emery 

cloth if dirty.

4.   Repair leaks as necessary.

5.   Make sure above ground connections are tight. Then 

repeat test. If necessary, pull piping and repair leak.

6.   Repair or replace.

Pump won’t shut off.

1.   Wrong pressure switch setting or 

setting “drift”.

2.   Defective pressure switch.

3.   Loss of prime.

4.   Low well level.

5.   Fouled  ejector.

1.   Adjust switch to proper setting.

2.   Replace switch if defective.

3.   Reprime if necessary.

4.   If undersized, replace pump or ejector.

5.   Clean.

Pump operates, but delivers little or no water.

1.   Low line voltage.

2.   System incompletely primed.

3.   Air lock in suction line.

4.   Undersized  piping.

5.   Leak in air volume control or tubing.

6.   Leak on suction side of system.

7.   Low well capacity.

8.   Plugged  ejector.

9.   Defective or plugged foot valve and/

or strainer.

10.  Worn or defective pump parts or 

plugged impeller.

1.   If voltage under recommended minimum, check size 

of wiring from main switch on property. If OK, contact 

power company.

2.   Reprime if necessary.

3.   Rearrange piping to eliminate air lock.

4.   Replace undersized piping or install pump with higher 

capacity.

5.   Tighten all fittings and replace control if necessary.

6.   Make sure above ground connections are tight. Re-

peat test. If necessary, pull piping and repair leak.

7.   Close down the valve on discharge side of pump to 

limit flow of water, in keeping with well capacity.

8.   Clean and reinstall if dirty.

9.   Clean, repair or replace as needed.

10.  Replace worn parts or pump. Clean parts if required.

TROUBLESHOOTING

Summary of Contents for NE460

Page 1: ...en you see this symbol on the pump or in the manual look for one of the following signal words and be alert to the potential for personal injury or property damage Warns of hazards that WILL cause serious personal injury death or major property damage Warns of hazards that CAN cause serious personal injury death or major property damage Warns of hazards that CAN cause personal injury or property d...

Page 2: ...ife expectancy can occur if the ground water is not cold 86 ºF 30 ºC or contains air or gases 9 DO NOT run the pump dry DO NOT run the pump with a completely closed discharge DO NOT pump chemical or corrosive liquids Failure to follow above warnings could result in damage to the pump voiding the warranty and causing personal injury 10 CAUTION Check to be sure your power source is capable of handli...

Page 3: ...nstallation of jet pumps 2 Plastic pipe must have a minimum pressure rating of 160 PSI WELL TO PUMP PIPING 1 All offset piping should slope upwards from well to pump 2 Avoid dips or pockets in offset piping or air will accumulate at high points which will make priming difficult 3 Install unions at pump and at well to aid in servicing 4 Allow enough room around pump and piping installation for usin...

Page 4: ...r change the red and gray wire to voltage required Figure 5 Dual Voltage Wiring Diagram 2 To change voltage remove the rear access cover of the motor which is held in place with two 2 screws Change the red and gray wire on the transfer switch board to the voltage required Replace rear access cover before starting or operating pump Failure to do so can result in personal injury 3 Your pump motor ha...

Page 5: ... bracket MOTOR REPLACEMENT Figure 5 1 Uni Frame motors can be replaced in the field with any standard Nema J jet pump motor by following the following instructions CAUTION Before attempting to replace the motor make certain that the power supply is disconnected and the system pressure is relieved 2 Remove pump body Ref No 8 diffuser Ref No 7 impeller Ref No 6 and shaft seal Ref No 4 by following s...

Page 6: ... 2 Clean or replace defective control 3 Adjust switch settings Clean contacts with emery cloth if dirty 4 Repair leaks as necessary 5 Make sure above ground connections are tight Then repeat test If necessary pull piping and repair leak 6 Repair or replace Pump won t shut off 1 Wrong pressure switch setting or setting drift 2 Defective pressure switch 3 Loss of prime 4 Low well level 5 Fouled ejec...

Page 7: ...HORSEPOWER 1 2 3 4 MODEL NO PART NO 460 0006 461 0006 DESCRIPTION QTY 1 Motor Nema J Thd Motor Cover w Screws Screws Cover Motor Lead Wire 021301R 021302 136135A 98J105 1 2 1 98J107 1 2 1 2 3 Mounting Ring Hex Hd Cap Screws 3 8 x 3 4 135314 4 135314 4 4 5 6 7 8 9 10 Ring Square Cut Seal Rotary w Spring Impeller Diffuser Rubber Diffuser Pump Body Plug Priming 131100 132428 132583 1 139348 132424 1 ...

Page 8: ... O BOX 16347 Louisville KY 40256 0347 SHIPTO 3649 Cane Run Road Louisville KY 40211 1961 502 778 2731 1 800 928 PUMP FAX 502 774 3624 Visit our web site zoellerpumps com Copyright 2015 Zoeller Co All rights reserved ...

Reviews: