background image

8

© Copyright 2016 Zoeller

®

 Co. All rights reserved.

Troubleshooting Guide

CONDITION

POSSIBLE CAUSE

REMEDY

A

PUMP WILL NOT START OR RUN.

Low voltage, blown fuse open circuit.

Have a qualified electrician check fuse and circuit.

Impeller bound.

Replace fuse.

Blown pump fuse.
Defective Switch

Contact factory.

Motor or wiring shorted.

B

PUMP STARTS TOO SOON.

Float “ON” point is adjusted too low.

Refer to STEP 2.

C

PUMP WILL NOT SHUT OFF.

Float is obstructed.

I

nspect float operation and correct problem.

Float “Off” point adjusted too low.

Adjust “Off” point. Refer to 

STEP 2.

Faulty float switch.

Contact factory.

D

PUMP OPERATES BUT DELIVERS LITTLE 

OR NO WATER.

Debris around intake.

Clean area around intake.

Blockage in discharge pipe.

Remove pipe and flush out debris.

Low voltage.

Check condition of battery. Replace as necessary or 

recharge.

Blown fuse, open circuit.

Have a qualified electrician check circuit.

Incorrect float adjustment

Refer to STEP 2 for proper installation.

Pump is air locked.

Drill ¼” hole in discharge pipe below waterline.

Vertical lift too high.

Change discharge piping or contact tech. service.

Base plate is “loose” or corroded.

Remove pump from pit and tighten as necessary.

Pump runs in reverse.

Make certain that the red(+) lead and black(-) leads go to 

the appropriate battery terminals.

Damaged Impeller.

Contact factory.

E

RED LIGHT ON CHARGER IS OUT.

Power outage.

Normal condition Red light will be illuminated once line 

power is restored.

AC line fuse blown.

Have a qualified electrician replace with new fuse on the 

circuit board.

Defective controller or light burned out.

Contact factory.

No AC power, battery less than 5V.

Battery has depleted below 5V due to prolonged operation 

without AC power.  Call for service or replace battery.

F

RED LIGHT FLASHING.

The charger fan may be defective.

Have a qualified electrician inspect the charger.

G

GREEN & YELLOW LIGHTS FLASH 

INTERMITTENTLY.

Positive & Negative battery leads are 

reversed.

Make certain that the positive (red) & negative (black) leads 

go to the proper battery terminals. 

Battery maintenance required.

Check water lever of battery, refill as necessary (Do not 

overfill).

Defective battery. Replace as necessary.

Battery has a “Dead Short”.

Replace battery. Battery has aged beyond its ability to 

chemically store electricity.

Loose battery connections.

Tighten red and black battery leads.

Corroded battery terminals.

Clean terminal as necessary. Apply grease to terminals to 

prevent future corrosion problems.

H

YELLOW LIGHT IS OUT.

Battery voltage hasd dropped below 8V.

Battery depleted below 8V due to normal operation.  Will 

be illuminated once AC power is restored and battery is 

charged.

Battery may be defective.

Replace battery.

Light may be defective.

Contact factory.

I

GREEN LIGHT IS OUT

Battery voltage has dropped below 12V.

Battery depleted below 12V due to normal operation.  Will 

be illuminated once AC power is restored and battery is 

charged.

Light may be defective.

Contact factory.

J

RED, GREEN & YELLOW LIGHTS FLASH 

IN SEQUENCE.

Lights flash for approximately for 4 

seconds.

Normal condition. The lights indicate that the system is 

properly installed.

K

CONSTANTLY ADDING DISTILLED WATER 

TO BATTERY.

Defective battery.

Have battery inspected. The charger will overcharge a 

battery with a defective cell.

Defective controller.

Contact factory.

L

ROTTEN EGG SMELL IN BASEMENT.

Charger is overcharging battery.

Have battery inspected. The charger will overcharge a 

battery with a defective cell.

Summary of Contents for AquaNot 585

Page 1: ...th a primary and a DC backup pump SEE BELOW FOR LIST OF WARNINGS 1 Testing for Ground As a safety measure each electrical outlet should be checked for ground using an Underwriters Laboratory listed circuit analyzer which will indicate if the power neutral and ground wires are correctly connected to your outlet If they are not call a qualified licensed electrician 2 For your protection always disco...

Page 2: ...nty MANUFACTURER EXPRESSLY DISCLAIMS LIABILITY FOR SPECIAL CONSEQUENTIAL OR INCIDENTAL DAMAGES OR BREACH OF EXPRESSED OR IMPLIED WARRANTY AND ANY IMPLIED WARRANTY OF FITNESS FOR A PARTICULAR PURPOSE AND OF MERCHANTABILITY SHALL BE LIMITED TO THE DURATION OF THE EXPRESSED WARRANTY Some states do not allow limitations on the duration of an implied warranty so the above limitation may not apply to yo...

Page 3: ...k valve see step 3 in the dis charge line DO NOT use a discharge pipe smaller than the recommended pump discharge sizes 6 DO test pump immediately after installation to be sure that the system is working properly 7 DO review all applicable local and national codes and verify that the installation conforms to each of them Performance Characteristics 6 The battery charger should be placed on a shelf...

Page 4: ...rick or similar material has been used to raise the pump in the pit it will be necessary to account for the thickness of the brick Figure 2 2 Figure 2 1 SK1776 SK1777 STEP 1 Placement of the Pump in the Pit Note If your pit has a cover then it will have to be modified to accept the Aquanot 1 1 Inspect the pit for debris and clean as necessary 1 2 Place the pump in the pit making certain that it is...

Page 5: ...the Aquanot starts 6 3 Verify that the pump starts and stops at the desired on off points 6 4 Verify that there are no leaks in the discharge line 6 5 If adjustment is necessary raise or lower the appropriate stop s according to STEP 2 IMPORTANT Spacing between upper and lower stops determine amount of water removed from pit 6 6 If the pump is not operating properly after following the above steps...

Page 6: ...he condition of the battery Operation of the Aquanot Charger All Aquanot pump systems are equipped with an alarm which sounds when the pump is activated The alarm will automatically silence when the pumping cycle is completed Activation of the audible alarm indicates that the primary pump has failed or line power to the primary pump is not present When ever the alarm is activated the primary pump ...

Page 7: ...p Motor 1 013873 013873 013873 013873 013873 013873 013873 013873 013873 013873 013873 013873 9 Column 1 011942 011942 011942 011942 011942 011942 011942 011942 011942 011942 011942 011942 10 Adapter Drive 1 011940 011940 011940 011940 011940 011940 011940 011940 011940 011940 011940 011940 11 Shaft 1 011944 011944 011944 011944 011944 011944 011944 011944 011944 011944 011944 011944 12 Head w Bra...

Page 8: ...han 5V Battery has depleted below 5V due to prolonged operation without AC power Call for service or replace battery F RED LIGHT FLASHING The charger fan may be defective Have a qualified electrician inspect the charger G GREEN YELLOW LIGHTS FLASH INTERMITTENTLY Positive Negative battery leads are reversed Make certain that the positive red negative black leads go to the proper battery terminals B...

Reviews: