background image

6

© Copyright 2016 Zoeller

®

 Co. All rights reserved.

 

The charger automatically monitors and charges your battery. In the event of a power outage the pump will be powered by the 

battery. Once line power is restored, the charger will recharge the battery. If there is a failure of the primary pump, the charger will 

supply power to the pump through the battery  if line power is present; otherwise, the battery will take over until the problem has 

been corrected.

  The lights on the front panel of the charger indicate the state of system:

  The red light:  Indicates that AC line power is present.

  The green light:  Indicates that the battery is charged to 12V DC*.

 

During periods of extended power outage the charge on the battery may drop below 12V DC which would cause the green 

light to go out. This is normal. The green light will be illuminated once the charger restores the voltage level to 12V DC.

  The yellow light: Indicates that the battery is charged above 8V DC.

 

If the yellow light is not illuminated, it indicates that the charge on the battery is below 8V DC. If the line power is out, the pump 

may have depleted the battery due to normal operation. If there has been no power outage and the primary pump is working 

properly, it may indicate that the battery is defective or that the controller is defective. Refer to the Troubleshooting guide on 

page 8 for further instructions.

 

If the Green and Yellow lights flash intermittently, refer to Section G in the Trouble Shooting Guide on page 8.

  *Voltage is only one indicator of the state of the battery, and does not reflect the true condition of the battery. Use a hydrometer to 

more accurately determine the condition of the battery.

Operation of the Aquanot

®

 Charger

 

All 

Aquanot

®

 pump systems are equipped with an alarm which sounds when the pump is activated. The alarm will automatically 

silence when the pumping cycle is completed.

  Activation of the audible alarm indicates that the primary pump has failed or line power to the primary pump is not present. When-

ever the alarm is activated the primary pump and outlet should be inspected.

  The On/Off switch, located on the side of the alarm enclosure, allows the audible alarm to be turned off, however, this practice is 

not recommended. Verify that the alarm switch is in the “on” position, by manually turning the pump “on”.

Operation of the Audible Alarm

 

There are millions of batteries manufactured each year, so it is impossible to guarantee consistent quality. A defective battery will 
never become fully charged and may damage the circuits of the charger. It is for this reason that Zoeller offers its own line of bat-
teries. We offer two types of batteries; Water/Acid Deep-Cycle, and AGM - both power the pump continuously for over 3-1/2 hours. 
These times are based on continuous pumping at 10’ of static head. Actual times will vary depending on static head, volume of 
water entering the pit, and the condition of the battery.

 

Follow these recommendations:

 

• 

Use a B.C.I. size 27, 29, or 31 deep-cycle battery, 175 minute reserve capacity, or larger.

  • 

Do NOT use a “maintenance-free” battery unless it is an AGM battery.

  • 

Replace your battery every 3 years.

  • 

Do not let corrosion build up on the battery terminals.

  • 

Do not place your battery on a concrete floor where it will discharge faster.

  • 

To check specific gravity, follow the instructions on a hydrometer (not applicable for AGM batteries).

  PROTECT YOUR WARRANTY: 

 

  • 

Water level in batteries must be checked once a month (not applicable for AGM batteries).

The Aquanot

®

 Battery

Summary of Contents for AquaNot 585

Page 1: ...th a primary and a DC backup pump SEE BELOW FOR LIST OF WARNINGS 1 Testing for Ground As a safety measure each electrical outlet should be checked for ground using an Underwriters Laboratory listed circuit analyzer which will indicate if the power neutral and ground wires are correctly connected to your outlet If they are not call a qualified licensed electrician 2 For your protection always disco...

Page 2: ...nty MANUFACTURER EXPRESSLY DISCLAIMS LIABILITY FOR SPECIAL CONSEQUENTIAL OR INCIDENTAL DAMAGES OR BREACH OF EXPRESSED OR IMPLIED WARRANTY AND ANY IMPLIED WARRANTY OF FITNESS FOR A PARTICULAR PURPOSE AND OF MERCHANTABILITY SHALL BE LIMITED TO THE DURATION OF THE EXPRESSED WARRANTY Some states do not allow limitations on the duration of an implied warranty so the above limitation may not apply to yo...

Page 3: ...k valve see step 3 in the dis charge line DO NOT use a discharge pipe smaller than the recommended pump discharge sizes 6 DO test pump immediately after installation to be sure that the system is working properly 7 DO review all applicable local and national codes and verify that the installation conforms to each of them Performance Characteristics 6 The battery charger should be placed on a shelf...

Page 4: ...rick or similar material has been used to raise the pump in the pit it will be necessary to account for the thickness of the brick Figure 2 2 Figure 2 1 SK1776 SK1777 STEP 1 Placement of the Pump in the Pit Note If your pit has a cover then it will have to be modified to accept the Aquanot 1 1 Inspect the pit for debris and clean as necessary 1 2 Place the pump in the pit making certain that it is...

Page 5: ...the Aquanot starts 6 3 Verify that the pump starts and stops at the desired on off points 6 4 Verify that there are no leaks in the discharge line 6 5 If adjustment is necessary raise or lower the appropriate stop s according to STEP 2 IMPORTANT Spacing between upper and lower stops determine amount of water removed from pit 6 6 If the pump is not operating properly after following the above steps...

Page 6: ...he condition of the battery Operation of the Aquanot Charger All Aquanot pump systems are equipped with an alarm which sounds when the pump is activated The alarm will automatically silence when the pumping cycle is completed Activation of the audible alarm indicates that the primary pump has failed or line power to the primary pump is not present When ever the alarm is activated the primary pump ...

Page 7: ...p Motor 1 013873 013873 013873 013873 013873 013873 013873 013873 013873 013873 013873 013873 9 Column 1 011942 011942 011942 011942 011942 011942 011942 011942 011942 011942 011942 011942 10 Adapter Drive 1 011940 011940 011940 011940 011940 011940 011940 011940 011940 011940 011940 011940 11 Shaft 1 011944 011944 011944 011944 011944 011944 011944 011944 011944 011944 011944 011944 12 Head w Bra...

Page 8: ...han 5V Battery has depleted below 5V due to prolonged operation without AC power Call for service or replace battery F RED LIGHT FLASHING The charger fan may be defective Have a qualified electrician inspect the charger G GREEN YELLOW LIGHTS FLASH INTERMITTENTLY Positive Negative battery leads are reversed Make certain that the positive red negative black leads go to the proper battery terminals B...

Reviews: