background image

7

© Copyright 2019 Zoeller

®

 Co. All rights reserved.

OPERATION

GENERAL

Zoeller pumps are lubricated and tested at the factory prior 

to shipment and require minimum pre-start-up maintenance.
Maximum operating temperature of pump liquid for standard 

model pumps must not exceed 130 °F (54 °C). For longest service 

life all pumps should be totally submerged on long pumping cycles 

and a maximum of 1/2 hour run time per hour.
These units are not designed to handle liquids other than water 

or sewage. If pump is used in water contaminated with heavy, 

viscous, or abrasive materials, the warranty will be voided.

NAMEPLATE DATA

The nameplate, located on the top of pump, indicates specific 

information about the construction of the pump. The model 

number, and date code information should be recorded on the 

front page in the “Owner’s Information” section of this manual.

SHORT TERM STORAGE

If pump is to be stored, the following is advised:
•  Store pump inside whenever possible or cover with some type 

of protective covering

•  Tape or seal in plastic bag the terminal ends of wire leads
•  Spray coat unpainted surfaces with rust inhibiting oil
•  The impeller should be rotated every three months in order to 

keep the seals lubricated and not develop a permanent set

If panel is to be stored, the following is advised:
•  Store the panel inside whenever possible and leave in 

the shipping box

•  All openings shall be sealed
•  Store in an upright position
•  Do not stack anything on top of panel

START-UP PROCEDURE

Before placing the equipment into operation the following 

checked:

•  Correct pump rotation (3 Phase units only)
•  Clean pit
•  Panel dry and securely installed
•  Floats positioned properly
•  Discharge valves open
•  3/16” vent hole drilled in pipe between check valve and pump

Once the above has been verified proceed with the following 

checks:

•  Pump power cables properly connected to panel
•  Float cables properly connected to panel
•  Conduit connections to panel are properly sealed
•  Motor overload protection is set in the panel
•  After installing the pump into the containment area, with 

adequate submergence, open the shut-off valve fully. Start 

the unit using manual controls. If flow is appreciably less than 

rated performance, pump may be air locked. To expel trapped 

air, jog the unit several times, using the manual controls

•  Have a qualified electrician take voltage and current 

measurements on the black wire of single phase or all 

three power wires of three phase with the pump running. 

Record these readings in the space provided in the “

Owner’s 

Information”

 section on page 1 of this manual for future 

reference

After the preoperational functional test has been completed, 

system is ready for operation. Zoeller recommends completing 

a Start-up Report (ZM1074) whenever a system is started for the 

first time or after a system has had a significant change take 

place (i.e. pump replacement, overhaul, etc.). A copy of the Start-

up Report should remain with the system for future reference.

ADJUSTMENT PROCEDURE

Pumps: No adjustments are required other than assuring 

correct rotation.

Panels:  The motor overload protection in the panel  must be set 

to the F.L.A. rating on the pump nameplate (or refer to 

pump data sheet).

Floats:  Refer to the system drawing for desired location of 

each float function.

Valves:  Discharge valves should be placed in the fully open 

position. Systems should not be operated for extended 

periods of time with the discharge valves partially 

closed due to damaging the valve.

SHUTDOWN PROCEDURES

If a system is shutdown for more than six months, the 

following is recommended:
Pumps:  If pit is to remain dry, then the pump can remain in the 

pit. With the pump in the pit, it should be operated for 

five minutes once every three months. If the pit is to 

remain wet, the pump should be removed and stored 

as noted above.

Panels:  The panel should have all openings sealed to prevent 

moisture and dust from entering the enclosure. Prior 

to restarting system, the panel should be inspected for 

presence of moisture and any loose connections.

Valves:  Consult the valve/actuator supplier for information 

concerning these systems components.

Summary of Contents for 6155

Page 1: ...GE 6267 6282 6284 6292 6293 6294 6295 6404 6405 6155 6161 6163 6165 6185 6186 6188 6189 Commercial Duty Pumps Model Number ______________ DateCode _______________ Simplex Duplex Job Name ____________________________________________ Distributor ____________________________________________ Date of Purchase _________ Zoeller S O No ______________ Contractor ___________________________________________...

Page 2: ...e These materials should be retained for future reference 1 Make certain that the receptacle is within the reach of the pump s power supply cord DO NOT USE AN EXTENSION CORD Extension cords that are too long or too light do not deliver sufficient voltage to the pump motor But more important they could present a safety hazard if the insulation were to become damaged or the connection end were to fa...

Page 3: ...2 9 G6189 2 3450 460 3 60 6 0 2 8 19 7 J 13 5 11 7 BA6189 2 3450 575 3 60 5 8 2 1 15 9 J 20 8 18 1 N6267 1 2 1725 115 1 60 10 4 6 8 25 0 G 2 5 1 7 E6267 1 2 1725 230 1 60 5 8 3 6 12 5 G 8 1 7 1 I6267 1 2 1725 200 208 1 60 6 2 4 2 21 0 K 6 4 5 2 J6267 1 2 1725 200 208 3 60 2 6 1 9 8 3 G 14 7 13 1 F6267 1 2 1725 230 3 60 2 6 2 0 7 1 G 18 6 16 2 G6267 1 2 1725 460 3 60 1 5 1 1 5 1 K 49 0 43 0 N6282 1...

Page 4: ...e cover 1 Electrical wiring and protection must be in accordance with National Electrical Code and any other applicable state and local electrical requirements 2 Install proper Zoeller unicheck combination union and check valve preferably just above the basin to allow easy removal of the pump for cleaning or repair On sewage effluent or dewatering if high head or below cover installation is requir...

Page 5: ...arranty repairs must be made by Zoeller Authorized Service Stations 5 On existing applications where the control panel only has one moisture sensor hookup per pump one moisture sensor lead from the pump should be hooked to the moisture sensor lead in the panel the other moisture sensor lead from the pump should be hooked to ground to complete the circuit 6 The moisture sensor circuit can be checke...

Page 6: ...TIC SINGLE PHASE OPTIONAL 330K OHMS RESISTANCE BEFORE 6 2000 N O BROWN 011348 NONAUTOMATIC SINGLE PHASE These pumps are nonautomatic They typically require a control panel A motor starter circuit control circuit and alarm circuit within the panel are standard features Outdoor enclosures and alternating relays are often required Variable level float switches are the most common level sensing device...

Page 7: ...re properly sealed Motor overload protection is set in the panel After installing the pump into the containment area with adequate submergence open the shut off valve fully Start theunitusingmanualcontrols Ifflowisappreciablylessthan ratedperformance pumpmaybeairlocked Toexpeltrapped air jog the unit several times using the manual controls Have a qualified electrician take voltage and current meas...

Page 8: ...tivated it s indicating that moisture is present and the pump should be removed and serviced in order to avoid damage to the motor SERVICE CHECKLIST Condition A Pump will not start or run B Motor overheats and trips overload C Pump will not shut off D Pump operates but delivers little or no water E Pump starts and stops too often F Red beacon comes on at control panel G Grease and solids accumulat...

Reviews: