background image

4

 10.  Install the Fit Controller (see Figure 3) by using the anchors provided.  For 

best  cooling,  install  wall  mount  configuration.    The  controller  should  be 

located at least 3' (1 m) above the sump.

 11.  Connect the leads from the controller to the battery terminals.  Positive (+) 

lead to positive terminal and black neg. (-) lead to negative battery terminal.  

  

CAUTION

 Correct battery hook-up is essential for operation of 

the system.  Use wing nuts supplied with battery and eyelet connectors 

on  battery  wire  leads.   The  positive  terminal  is  the  larger  stud,  3/8"  (10 

mm) diameter.  The smaller stud, 5/16" (8 mm) diameter is the negative 

terminal.  The stud sizes on the AGM battery are identical. Apply grease to 

the terminals to help prevent corrosion.

 12.  Connect the pump's plug into the controller terminal. 
 13.  Plug the controller into the 115 V wall outlet.  The primary sump pump and the 

controller should be on separate circuits.

 14.  Reconnect power to the primary sump pump.

 15.  The Aquanot

®

 FIt Controller is designed for use with Z Control

®

.

  1.  The preferred method of installation for backup pumps is shown in Figure 1. 

 

The installation kit includes the necessary fittings. Includes the parts needed 

to install as in Figure 1. A check valve is incorporated in the discharge of the 

backup pump.

    NOTE: Do not install in small spaces where the controller will not be properly 

cooled.

  2.  Remove all parts from the shipping carton, and make sure all parts are included.  

Refer to the parts list on page 3.

  3.  Select a location for the battery and the controller.  The controller must be within 

8' (2.4 m) of a 115 V wall outlet and within 6' (1.8 m) of pump and basin.  Connect 

to a separate circuit from the primary pump.

  4.  If the primary pump is installed, disconnect power.

    NOTE: Discharge piping must be 1-1/2" SCH 40 PVC

  5.  Remove the discharge pipe from the pump and place it aside.

  6.  Solvent weld the DC Pump discharge reducer fitting to the tee as shown in 

Figure 1. Ensure the O-ring is properly located on the pump discharge. Slide the 

DC pump into the fitting, and tighten the hose clamp.

    NOTE:  The pump must be pushed all the way into the fitting to prevent the fitting 

from leaking.

  7.  Determine the position of the DC pump and measure for discharge piping. Use 

that measurement to cut the discharge pipe.  Solvent weld that piece to the tee.  

Measure, cut and solvent weld any remaining discharge piping above the tee. 

    NOTE:  Check float operations to ensure the hose clamp screws will not interfere 

with the float operation of the primary pump.

  8.  Assemble the operation float assembly per Figure 3. Install float switches as 

seen in Figure 1.

  9.  Install the operational float switch bracket above the "on" level of the primary 

pump using the clamp provided. Make certain the clamp is tight on the pipe to 

avoid slippage. Ensure that the "off" level of the float is 1" (2.5 cm) minimum 

above the outlet of the DC backup pump. Position the pumps in the sump and 

move  float  up  and  down,  ensuring  free  movement  without  interference  from 

any obstructions inside the sump or lid. The float switch can be moved on the 

discharge pipe, or the rubber stops can be adjusted as necessary. Cut extra 

float rod length below lower float stop to prevent debris from interfering with float 

operation. Install the high water switch with the "on" level set at least 1" (2.5 

cm) above the "on" level of the operational float using the supplied clamp. Move 

the switch up and down, ensuring free movement without interference from any 

obstructions inside the sump or lid.

INITIAL START-UP AND OPERATION

  1.  Test the installation for leaks by running water into the sump, allowing for 

normal operation of the primary pump.

  2.  Check the controller. The System ready light will be green when the 

unit is 

plugged into the 115 V wall outlet. The battery will indicate its condition when 

the controller has DC power. When the unit is first plugged in, all lights will 

flash and alarm will sound to verify all lights and the alarm work. Note that 

the charger may not begin charging for several minutes.

  3.  Disconnect the primary pump from its power source before touching any 

component in the sump pit.

 4. Lift 

the operational float switch. After a couple seconds the DC backup 

pump will run, and the alarm will sound after about 1 second. Lower the 

operational float switch after the alarm sounds. 

Take care that the intake 

of the DC pump is set above the inlet of the primary pump. Press silence 

for 3 seconds to clear out the alarm and reset the unit.

  

CAUTION

 Continuous dry running may cause overheating and damage 

the pump seals. Upon release of the float switch, the pump will shut off. 

Be sure there are no obstructions around the float.

 5. 

Check installation of the high water switch. Lift the high water float.  The 

alarm will sound, and the light will alert of high water. If the operational float 

is down, the pump will run until the float lowers and the pump is no longer 

pumping water, or the run timer expires a foat fault LED will be lit. If the 

operational float is up during high water, unit will alarm and high water float 

light will illuminate. The pump will turn off once water is pumped lower than 

the operational float.

  6.  Complete the final testing of your installation by ensuring the primary 

pump 

is still disconnected from power.  Then, unplug the fit controller from the 

115 V wall outlet.  Run water into the sump until the DC backup pump is 

activated by the operational float switch. Check all connections for leaks.

 

7.  Push the Silence button when the pump is running. This will silence the 

alarm. The pump will continue to run until the operational float is deactivated.

  8.  Reconnect the controller and the primary pump to the AC wall outlets. The 

primary pump may come on, lower the water level in the sump back to its 

normal operating level, and shut off.  Both primary and backup systems are 

now ready for use. Hold silence button for several seconds to reset the unit.

 

9.  The battery hold silence button for several seconds to reset the unit. LED 

will be yellow during normal charging operation. See page 6 for a description 

of controller functions.

    NOTE: When running the pumps, it is normal for a stream of water to  spray 

out of the 1/8" (3 mm) air relief hole. 

INSTALLATION

© Copyright 2019 Zoeller

®

 Co. All rights reserved.

Summary of Contents for 508-0014

Page 1: ...arning ca gov 1 Make sure there is a properly grounded 115 V receptacle available Do not use primary pump circuit The location must be within 6 1 8 m of the control box and battery The power supply for your DC control system plugsdirectlyintothe115Voutlet DO NOTUSEANEXTENSIONCORD 2 Make sure the 115 V electrical supply circuit is equipped with fuses or circuit breakers of proper capacity 3 DC emer...

Page 2: ...eset button for 3 seconds to reset the controller and clear any alarms or indicators 2 Plug the controller and the primary pump into the wall outlet a The primary pump will come on lower the water to the normal operating level and shut off b The battery light will be yellow when charging The charger is replacing the energy consumed during the test The green light will come on after the charger has...

Page 3: ...nstallation Wet cell batteries contain acid and proper precaution must be taken when handling Battery box will accommodate a maximum battery size of 13 1 2 34 3 cm Length x 7 17 8 cm Width x 9 1 2 49 5 cm Height AGM batteries also recommended Do not use gel batteries or automotive batteries Pump Construction Non corrodible plastic premium seals Performance 35 GPM at 10 113 LPM at 3 m at 12 6 volts...

Page 4: ...p or lid The float switch can be moved on the discharge pipe or the rubber stops can be adjusted as necessary Cut extra float rod length below lower float stop to prevent debris from interfering with float operation Install the high water switch with the on level set at least 1 2 5 cm above the on level of the operational float using the supplied clamp Move the switch up and down ensuring free mov...

Page 5: ...FF LEVEL OF FLOAT ASSEMBLY MUST BE HIGHERTHAN DC BACKUP PUMP DC PUMP INSTALLED IN LINE WITH SUBMERSIBLE PUMP BATTERY BOX AQUANOT FIT CONTROLLER OUTLET CHARGER HI WATER REED SENSOR OPERATIONAL FLOAT SWITCH AQUANOT FIT CONTROLLER 30 AMP FUSE HI WATER REED SWITCH BATTERY BOX DC PUMP 12 VOLT BATTERY SUPPLIED BY USER WHITE LEADTO POSITIVE BLACK LEADTO NEGATIVE CLAMP EXPLODED VIEW DC PUMP FIGURE 2 SK318...

Page 6: ...start the 24 hour timer for self testing AQUANOT FIT Solid Flashing Off System Ready No Faults Green AC off with no faults Green Battery Charged Green Low Battery Red No AC Power Charging Yellow Bad Battery Red DC pump Pump Ran Yellow Pump Running Yellow Pump Fault Red Float Status High Water Red Float Fault Red Z Control Connected Searching Broadcasting SSID or Dormant The LEDs will display infor...

Page 7: ...ion process Create a free account at zcontrolcloud com Locate the Fit s Device ID on the top sticker Connection Steps 1 Apply AC Power to the Fit The Z Control LED will blink and then turn off indicating the Fit is in AP Mode and is transmitting an SSID see Figure B If the LED is blinking and not in AP mode press the Z Control button for 12 seconds and let go The LED will now be off indicating the...

Page 8: ... choose the WiFi you want the Fit to use for internet connectivity Enter the password for the router you chose in the field indicated If the password is correct the Fit will connect to the router and start sending status updates to zcontrolcloud com You will see the Z Control LED go from blinking to solid This could take up to a minute or so If the LED does not turn solid then the password entered...

Page 9: ...oud com see Figure D Click the Edit button next to a location and choose Add New Device Follow the directions to add your Fit by either auto detect or entering the Device I D When successful a Fit product tile will appear in your account The Fit is capable of OTA or over the air firmware updates It s possible that the Fit could perform an update immediately if one is available at the Z Control Clo...

Page 10: ... CO is being produced a charging battery may be producing gaseous by products which are causing the CO detector to activate Contact the manufacturer and ask for recommendations to prevent the alarm activation There are millions of batteries manufactured each year so it is impossible to guarantee consistent quality A defective battery will never become fully charged and may damage the charging circ...

Page 11: ..._ _______________________________________________________________________________ _______________________________________________________________________________ _______________________________________________________________________________ _______________________________________________________________________________ ______________________________________________________________________________...

Page 12: ... 40256 0347 SHIPTO 3649 Cane Run Road Louisville KY 40211 1961 502 778 2731 1 800 928 PUMP FAX 502 774 3624 Visit our web site zoellerpumps com These are the original installation instructions Copyright 2019 Zoeller Co All rights reserved ...

Reviews: