IMPORTANT

To minimize risk of air lock, intake of DC pump must be set above intake of primary pump.

© Copyright 2019 Zoeller

®

 Co. All rights reserved.

OUTLET

PUMP

PRIMARY

1" MIN.

IMPORTANT: OFF LEVEL 

OF FLOAT ASSEMBLY 

MUST BE HIGHER THAN 

DC BACKUP PUMP

DC PUMP INSTALLED IN LINE WITH SUBMERSIBLE PUMP

BATTERY BOX

AQUANOT

® 

FIT CONTROLLER

OUTLET

CHARGER

HI-WATER 

REED SENSOR

OPERATIONAL FLOAT SWITCH

AQUANOT FIT CONTROLLER 

30 AMP FUSE

HI-WATER REED SWITCH

BATTERY BOX

DC PUMP

12 VOLT BATTERY 

SUPPLIED BY USER

WHITE LEAD TO POSITIVE

BLACK LEAD TO NEGATIVE

CLAMP

EXPLODED VIEW - DC PUMP

FIGURE 2

SK3185

Summary of Contents for 508-0014

Page 1: ...arning ca gov 1 Make sure there is a properly grounded 115 V receptacle available Do not use primary pump circuit The location must be within 6 1 8 m of the control box and battery The power supply for your DC control system plugsdirectlyintothe115Voutlet DO NOTUSEANEXTENSIONCORD 2 Make sure the 115 V electrical supply circuit is equipped with fuses or circuit breakers of proper capacity 3 DC emer...

Page 2: ...eset button for 3 seconds to reset the controller and clear any alarms or indicators 2 Plug the controller and the primary pump into the wall outlet a The primary pump will come on lower the water to the normal operating level and shut off b The battery light will be yellow when charging The charger is replacing the energy consumed during the test The green light will come on after the charger has...

Page 3: ...nstallation Wet cell batteries contain acid and proper precaution must be taken when handling Battery box will accommodate a maximum battery size of 13 1 2 34 3 cm Length x 7 17 8 cm Width x 9 1 2 49 5 cm Height AGM batteries also recommended Do not use gel batteries or automotive batteries Pump Construction Non corrodible plastic premium seals Performance 35 GPM at 10 113 LPM at 3 m at 12 6 volts...

Page 4: ...p or lid The float switch can be moved on the discharge pipe or the rubber stops can be adjusted as necessary Cut extra float rod length below lower float stop to prevent debris from interfering with float operation Install the high water switch with the on level set at least 1 2 5 cm above the on level of the operational float using the supplied clamp Move the switch up and down ensuring free mov...

Page 5: ...FF LEVEL OF FLOAT ASSEMBLY MUST BE HIGHERTHAN DC BACKUP PUMP DC PUMP INSTALLED IN LINE WITH SUBMERSIBLE PUMP BATTERY BOX AQUANOT FIT CONTROLLER OUTLET CHARGER HI WATER REED SENSOR OPERATIONAL FLOAT SWITCH AQUANOT FIT CONTROLLER 30 AMP FUSE HI WATER REED SWITCH BATTERY BOX DC PUMP 12 VOLT BATTERY SUPPLIED BY USER WHITE LEADTO POSITIVE BLACK LEADTO NEGATIVE CLAMP EXPLODED VIEW DC PUMP FIGURE 2 SK318...

Page 6: ...start the 24 hour timer for self testing AQUANOT FIT Solid Flashing Off System Ready No Faults Green AC off with no faults Green Battery Charged Green Low Battery Red No AC Power Charging Yellow Bad Battery Red DC pump Pump Ran Yellow Pump Running Yellow Pump Fault Red Float Status High Water Red Float Fault Red Z Control Connected Searching Broadcasting SSID or Dormant The LEDs will display infor...

Page 7: ...ion process Create a free account at zcontrolcloud com Locate the Fit s Device ID on the top sticker Connection Steps 1 Apply AC Power to the Fit The Z Control LED will blink and then turn off indicating the Fit is in AP Mode and is transmitting an SSID see Figure B If the LED is blinking and not in AP mode press the Z Control button for 12 seconds and let go The LED will now be off indicating the...

Page 8: ... choose the WiFi you want the Fit to use for internet connectivity Enter the password for the router you chose in the field indicated If the password is correct the Fit will connect to the router and start sending status updates to zcontrolcloud com You will see the Z Control LED go from blinking to solid This could take up to a minute or so If the LED does not turn solid then the password entered...

Page 9: ...oud com see Figure D Click the Edit button next to a location and choose Add New Device Follow the directions to add your Fit by either auto detect or entering the Device I D When successful a Fit product tile will appear in your account The Fit is capable of OTA or over the air firmware updates It s possible that the Fit could perform an update immediately if one is available at the Z Control Clo...

Page 10: ... CO is being produced a charging battery may be producing gaseous by products which are causing the CO detector to activate Contact the manufacturer and ask for recommendations to prevent the alarm activation There are millions of batteries manufactured each year so it is impossible to guarantee consistent quality A defective battery will never become fully charged and may damage the charging circ...

Page 11: ..._ _______________________________________________________________________________ _______________________________________________________________________________ _______________________________________________________________________________ _______________________________________________________________________________ ______________________________________________________________________________...

Page 12: ... 40256 0347 SHIPTO 3649 Cane Run Road Louisville KY 40211 1961 502 778 2731 1 800 928 PUMP FAX 502 774 3624 Visit our web site zoellerpumps com These are the original installation instructions Copyright 2019 Zoeller Co All rights reserved ...

Reviews: