background image

5

© Copyright 2016 Zoeller

®

 Co. All rights reserved.

 FOR YOUR PROTECTION, ALWAYS DISCONNECT PUMP FROM ITS POWER SOURCE BEFORE HANDLING.  Single phase 

pumps are supplied with a 3-prong grounded plug to help protect you against the possibility of electrical shock. DO NOT UNDER ANY CIRCUMSTANCES 

REMOVE THE GROUND PIN.  The 3-prong plug must  be inserted into a mating 3-prong grounded receptacle. If the installation does not have such 

a receptacle, it must be changed to the proper type, wired and grounded in accordance with the National Electrical Code and all applicable local codes and 

ordinances.  

 

All three phase pumps require motor starting devices with motor overload protection. See FM0514 for simplex installations or FM0486 for duplex 

installations. Three phase pumps must be installed in accordance with the National Electrical Code and all applicable local codes and ordinances. Pumps are 

not to be installed in locations classified as hazardous in accordance with National Electrical Code, ANSI/NFPA 70.

  “Risk of electrical shock”  Do not remove power supply cord and strain relief or connect conduit directly to the pump.
 Installation and checking of electrical circuits and hardware should be performed by a qualified licensed electrician.

Pump Wiring Instructions

Single Phase Installation

Models E404/E405 and I404/I405 are nonautomatic. To operate automati

-

cally a control panel or 20 amp control switch (P/N 10-0748) must be added 

to the power circuit. Follow the instructions provided with the panel or float 

switch to wire the system.

WD Model Installation

Models WD404/WD405 are fully automatic. A float switch is included and factory wired in the pump circuit to 

provide automatic operation once the float switch is secured properly to the outlet pipe. Use the diagram above to 

secure the float switch properly and obtain the proper tether to customize the on-off cycle to each application.

Three Phase Installation

WIRING DIAGRAM FOR MODELS

F404/F405 - 230V, 3 PH, 60 HZ

G404/G405 - 460V, 3 PH, 60 HZ

J404/J405 - 200/208V, 3 PH, 60 HZ

BA404/BA405 - 575V, 3 PH, 60 HZ

F4404/F4405 - 230V, 3 PH, 60 HZ

G4404/G4405 - 460V, 3 PH, 60 HZ

J4404/J4405 - 200/208V, 3 PH, 60 HZ

BA4404/BA4405 - 575V, 3 PH, 60 HZ

Three phase pumps are nonautomatic. To operate automatically, a control 

panel is required. Follow the instructions provided with the panel to wire the 

system.

Before installing a pump, check the pump rotation to insure that wiring has 

been connected properly to power source, and that the green lead of power 

cord (See wiring diagram), is connected to a valid ground, Momentarily en

-

ergize the pump, observing the directions of kick back due to starting torque. 

Rotation is correct if kick back is in the opposite direction of rotation arrow on 

the pump casing. If rotation is not correct, switching of any two power leads 

other than ground, should provide the proper rotation.

Determining Pumping Range

in Inches (1 inch - 2.5 cm)

min.

max.

Use only as a guide. Due to weight of 

cable, pumping range above horizontal 

is not equal to pumping range below 

horizontal. Ranges are based on testing in 

nonturbulent conditions.

 Range may vary 

due to water temperature and cord shape. 

As tether length increases, so does the 

variance of the pumping range.

Tether Length  5  10 15 20 22
Pumping Range  9  13.5  18  22  24

RUN

O.L.

MOTOR

(3)

BLUE

RED

WHITE

BLACK

GREEN

L1

L2

START

(1)

(2)

YELLOW

BLUE

RED

CAPACITOR

(WHITE)

(BLACK)

(BROWN)

WIRING DIAGRAM FOR MODELS

E404/E405 - 230V, 1 PH, 60 HZ

I404/I405 - 200/208V, 1 PH, 60 HZ

E4404/E4405 - 230V, 1 PH, 60 HZ

I4404/I4405 - 200/208V, 1 PH, 60 HZ

MOTOR

(3)

BLUE

RED

BLACK

GREEN

L1

L2

(1)

(2)

YELLOW

L3

WHITE

RED

60 HZ

START

RUN

BLUE

MOTOR

(WHITE)

RED

(BROWN)

O.L.

YELLOW

(BLACK)

SWITCH

FLOAT 

BLACK

BLACK

WHITE

CAPACITOR

BLUE

(1)

(2)

RED

RUN

WHITE

GREEN

L1

L2

(3)

WIRING DIAGRAM FOR MODELS

WD405 - 230V, 1 PH, 60 HZ

WH4405 - 200/208V, 1 PH, 60 HZ

011835

22" MAX.

5" MIN.

20 AMP SWITCH (WD & WH MODELS)

SK305D

002397

006848

Summary of Contents for 404/4404

Page 1: ...ructions 1 Limited Warranty 2 Service Checklist 2 Preinstallation Information 3 Pump Performance Data 4 Typical Dewatering Installation 4 Typical Sewage Installation 4 Pump Wiring Instructions 5 Operation 6 Maintenance 6 Replacement Parts 7 Safety Instructions TO AVOID SERIOUS OR FATAL PERSONAL INJURY OR MAJOR PROPERTY DAMAGE READ AND FOLLOW ALL SAFETY IN STRUCTIONS IN MANUAL AND ON PUMP THIS MANU...

Page 2: ...orkmanship under normal use and service when properly used and maintained for a period of one year from date of purchase by the end user or 18 months from date of original manu facture of the product whichever comes first Parts that fail within the warranty period one year from date of purchase by the end user or 18 months from the date of original manufacture of the product whichever comes first ...

Page 3: ...uses or circuit breakers of proper capacity A separate branch circuit is recommended sized according to the National Electrical Code for the current shown on the pump nameplate 5 FOR ADDED SAFETY Pumping and other electrical equipment must be connected to a 3 prong grounded receptacle with integral ground fault circuit interrupter GFCI 6 Risk of electric shock These pumps have not been investigate...

Page 4: ...l and State codes 11 If rail system is used discharge elbow must be firmly anchored to the bottom of basin No part of the pump can rest on the floor The cantilevered weight of the pump is required to seal the discharge connection Refer to Zoeller FM0793 for rail system installation Instructions 12 Basin must be clean and free of debris after installation SK1025 Typical Dewatering Installation All ...

Page 5: ... obtain the proper tether to customize the on off cycle to each application Three Phase Installation WIRING DIAGRAM FOR MODELS F404 F405 230V 3 PH 60 HZ G404 G405 460V 3 PH 60 HZ J404 J405 200 208V 3 PH 60 HZ BA404 BA405 575V 3 PH 60 HZ F4404 F4405 230V 3 PH 60 HZ G4404 G4405 460V 3 PH 60 HZ J4404 J4405 200 208V 3 PH 60 HZ BA4404 BA4405 575V 3 PH 60 HZ Three phase pumps are nonautomatic To operate...

Page 6: ...eady for operation Zoeller recommends completing a Start up Report FM0990 whenever a system is started for the first time or after a system has had a significant change take place i e pump replacement overhaul ect A copy of the Start up Report should remain with the system for future reference ADJUSTMENT PROCEDURE Pumps No adjustments are required other than assuring correct rotation Panels The th...

Page 7: ...7 Seal Cord Asm STRRLF 0 to 1 28 Clamp 6 Auto SS 0 to1 29 Cord Term Seal Control 0 to1 30 Seal Cord Asm Str Rlf Control Cord 0 to 1 31 Clamp Str Rlf 0 to 1 32 Screw 6 32 x 25 RHM Sl Tc Stlgr 1 to 4 33 Float Switch Term Seal 0 to 1 34 Seal Float Switch Cord Asm Strain Relief 0 to 1 35 Connector Wirenut 0 to 1 36 Screw 25 20 x 75 HHm SS 4 37 Screw 25 20 x 1 HHm SS 4 38 Screw 313 18 x 1 HH Cap SS 4 t...

Page 8: ...UND SCREW 18 20 21 24 22 23 26 17 14 15 38 16 14 18 38 15 19 10 26 32 25 34 33 35 DOUBLE SEAL ONLY 31 36 32 38 45 40 11 41 44 43 42 27 27 27 27 25 27 32 26 27 39 12 9 9 12 13 13 E MODEL I MODEL XE MODEL WD MODEL SENSOR CORDAGE J F G BA MODELS 12 14 GA J F G BA MODELS 16 18 GA SK1814 Copyright 2016 Zoeller Co All rights reserved ...