Installation and Operation Manual
|
Jandy® Legacy™ Model LRZM Pool/Spa Heater by Zodiac®
WaRNiNG
united States
Do not install the heater with the top of the vent as-
sembly within 4 feet (1.22 m) horizontally and 4 feet
(1.22 m) vertically of any opening into a building.
canada
Do not install the heater with the top of the vent as-
sembly within 10 feet (3.05 m) of any opening into a
building.
aveRtiSSeMeNt
Lorsque vous installez l’appareil de chauffage,
assurez-vous que l’ouverture d’aération se trouve à
un minimum de 10 pieds (3,05 m) de toute ouver-
ture d’un bâtiment.
The top surface of the heater must be at least
three (3) feet (0.9 m) above any forced air inlet, or
intake ducts located within 10 feet (3.05m) horizon-
tally.
If the heater is installed under an overhang, there
must be a minimum clearance of five (5) feet (1.5 m)
above the top of the heater and the structure should not
overhang the heater more than 12 inches (0.30 m). The
area under the overhang must be open on three sides.
This prevents combustion gases from being diverted
into living areas through doors, windows, or gravity
inlets.
Ne pas installer ce chauffe-piscine sous une
aillie mesurant moins de 5 pi de hauteur. La partie
sous la saillie doit être ouverte sur 3 côtés.
If the heater is installed close to a structure,
protect it from rain water runoff with rain gutters on
the roof or other measures. Do not locate the heater
near irrigation sprinkler systems that could spray water
on it. Water from sprinklers may cause damage to
controls and electronic components.
Avoid locations where wind deflection off nearby
Figure 3. outdoor Heater installation
structures might cause downdraft conditions. Where
downdraft conditions exist, locate the heater at least
three (3) feet (0.91 m) from vertical surfaces (e.g.,
nearby buildings and walls). The addition of a vent cap
may be necessary.
In Florida, it is required that the heater be secure-
ly fastened to the equipment pad. Use a size
1/4" x 2-1/4" long galvanized or plated concrete
screws and washers at each of the four tabs located
at the base of the heater. Mounting the appliance in
this manner meets the applicable requirements of the
Florida Building Code.
Mounting screws are not provided with this
heater. After placing the heater on the equipment pad,
drill a hole in the concrete at each of the four tabs
on the feet of the heater. (The correct size drill bit
is usually provided with the concrete screws when
purchased). Place a screw in each of the holes and
fasten the heater to the equipment pad. See Figure 4.
Do not over torque the screws.
2.3.5
indoor and outdoor Shelter
installations
An outdoor shelter (Canada only) is an unoccu-
pied enclosure which does not communicate directly
with occupied areas. All indoor installations and
outdoor shelter installations require a factory approved
vent collar. The vent collar must be installed without
modification and in accordance with the instructions
provided by the manufacturer.
Une remise extérieure (au Canada seule-
ment) est un endroit inoccupé qui ne communique
pas directement avec les endroits occupés. Toutes
les installations intérieures et remises extérieures
exigent l’addition d’une cheminée approuvée par le
manufacturier. La cheminée doit être installée sans
aucune modification et selon les exigences fournies
par le manufacturier.
These codes, standards and Zodiac Pool Systems,
Inc. require that the heater be properly vented as
outlined in this manual. Proper ventilation of exhaust
1/4” X 2-1/4”
GALVANIZED OR PLATED
CONCRETE SCREWS
Figure 4. anchor Heater to equipment Pad