Page 18
ENGLISH
Jandy® Legacy™ Model LRZM Pool/Spa Heater by Zodiac®
|
Installation and Operation Manual
Note
Do not reverse the position of the bypass.
13. Thread on the 10 bolts and washers and hand
tighten.
14. Place the return header over the bolts and gasket-
ed tubes on the right side of the tube assembly.
Align the bolt and tube holes in the header with
the bolts and tubes in the header bar and slide the
assembly together.
15. Thread on the 10 bolts and washers and hand
tighten.
16. Use a torque wrench to tighten the bolts on each
header to four (4) foot-pounds. The bolts must be
tightened in the sequence indicated in Figure 11.
cautioN
Failure to tighten the header as indicated in step 16
may cause the header to leak or become perma-
nently damaged from warping.
atteNtioN
Si le tuyau collecteur n’est pas serré conformément
aux directives des l'étape 16, il risque d’avoir des
fuites ou de s’endommager de façon permanente.
17. Remove the 3/4 inch button plug located in the
left side panel below the inlet/outlet header and
replace with the 3/4 inch wire grommet from the
right side panel below the return header. The high
limit leads were routed through this grommet
prior to removal in step 5. Install the 3/4 inch
plug in the opening where the 3/4 inch wire
grommet was removed.
18. Install the longer syphon loop tube (part number
R0483601) to the pressure switch and locate
the the pressure switch in the front area of the
cabinet.
19. Reconnect the white wire on the pressure switch
(PS) and the white wire on the Fireman's switch
terminal.
1. For an existing installation, drain the heater by
removing the two drain plugs on the inlet/outlet
header and the drain plug on the return header.
2. Remove the heater front panel (door).
3. Remove the I/O header side cover plates, top and
bottom. See Figure 10.
4. Remove the return header side cover plates, top
and bottom. See Figure 10.
5. Tag and disconnect the white wire on the
pressure switch (PS) and the white wire on the
Fireman's switch terminal which leads to the high
limit switch.
6. Remove the water temperature sensor nut from
the inlet/outlet header and remove the sensor.
7. Tag and disconnect the black and white wires
from the water pressure switch.
cautioN
In order to prevent property damage or injury, en-
sure that the wiring is handled and routed carefully
so as not to cause any damage to it. Additionally, be
careful not to create any kinks in the water pressure
switch copper tubing when handling the header.
atteNtioN
Afin d'empêcher des dégâts matériels ou des bles-
sures, assurez-vous que le câblage est manipulé
et installé soigneusement de manière à ne pas
l’endommager. De plus, vous devez faire attention
à ne créer aucune imperfection dans la conduite en
cuivre de l’interrupteur de pression d'eau en ma-
nipulant la tête.
8. For an existing installation, remove the coupling
nuts from the header and disconnect the water
supply from the heater.
9. Remove the 10 bolts and washers from the inlet/
outlet header and remove the header from the
tube assembly.
10. Remove the 10 bolts and washers from the return
header and remove the header from the tube
assembly.
11. For an existing installation, remove the tube
gaskets and clean the header's mating surface of
any corrosion or debris. Replace the tube gaskets
with new ones. Do not use any metal tools on the
header surface. Scratches may compromise the
seal integrity.
12. Place the inlet/outlet header over the bolts and
gasketed tubes on the left side of the tube assem-
bly. Align the bolt and tube holes in the header
with the bolts and tubes in the header bar and
slide the assembly together. Refer to Figure 9.
4
6
5
10
1
8
7 3
2
9
Figure 11. Header Bolt tightening Sequence