  • It is possible to connect a remote control module 

(1)

 

(with display) . 

To do this use terminals : 

    34-35 

(signals Tx-Rx)  

and 36-37 for 12 Vac supply of the interface A1 card.

 

 

Important :  

To connect the remote On/Off

(2) 

functions, fault and warning functions for filter start up, use cables with a section of at least 

1mm². Packing glands and cable inlets are available for passage of these cables into the unit. 
To connect the remote module

(1)

 (max. distance = 50 m) use a shielded cable of 4x0.75 mm² minimum 

(connected to the earth 

harness in the heat pump)

.  

 

(1)

 

module available as an 

optional extra

.    

(2) 

 

it is essential to use an independent cable for connection of this function (terminals 1 and 2). 

 

5. REGULATOR OPERATION 

 

5.1 Presentation 

 

The 

Euro 

α

 FK

 setting thermostat with digital display is supplied fitted in the appliance, electrically connected and pre-

set in the factory for swimming pool heating. 

 

Setting principle

: a control sensor placed at the water inlet side of the heat pump measures the temperature in the pool 

and compares it to the target temperature. If the water temperature becomes or is lower than the target temperature, the 
regulator unit authorises heating after a set time of 180 seconds, the Led   blinks and then remains on. 

 
 
 
 

 

 
 
 
 
 
 

 
 
 
 
 

 

5.2 Setting the target temperature 

 

Press and hold the 

Set

 key to display the target temperature, then press the key         to increase or         to decrease the 

temperature. Then release the key to return to  the display of the water temperature. 

 

 

                  

                                                  

 

 
 
 
 
 

Note:  

The maximum target temperature is limited to 

32°C

 in order to protect the swimming pool liner. This high target may, 

however, be modified by the installer, but at his own responsibility .

 

Heating mode 

Defrost cycle 

 (blinking = timer) 

Program temperature or set 

regulator parameters

 

On/Off 

(1)

, Stand-by 

(1)

 

 (red dot), Fault reset 

Increase value (UP) 

Decrease value (DOWN) 

Compressor operation  

(blinking = timer)

 

Filter pump control/heat pump on 

 

(if connected) 

 

Temperature display in  

°C or °F 

 

then 

Ô

 

       

then     

Ò

 

(1) 

Stop operation in  

Heating mode

Remarks :

  

- when a defrost cycle is in progress, it ends with maintaining ventilation except if the ambient temperature drops below +5°C or if filtration is stopped (J1 open). 

- in the case where the unit requests heating (Leds  

 and 

 on or  

  on and 

 blinking) led 

 remains on (contact 5-6 closed) for 120 s then switches off 

(contact 5-6 open). 

Summary of Contents for Edenpac 2

Page 1: ...gle fan 4 1 2 Edenpac with double fan 4 2 Hydraulic connections 10 4 3 Electric connection 11 5 Regulator operation 12 5 1 Presentation 12 5 2 Setting the target temperature 12 6 Starting up 13 6 1 Ch...

Page 2: ...2 Voltage Prior to any operation check that the voltage on the name plate of the appliance corresponds to the mains voltage provided on site 1 3 Water treatment In order to use our appliances under th...

Page 3: ...ANIUM condenser unit 8 Regulator sensor 9 LP pressure switch Cased SCROLL compressor 11 Arched flat fin unit cooler 12 Anti frost sensor 13 Fastening plates with silent blocks 14 Pool inlet water conn...

Page 4: ...e on photos but located at the back of the unit 1 2 3 4 6 5 7 8 9 11 13 1 Top and bottom panels with polypropylene grid 2 Motor fan unit 3 Access flap to digital regulator 3a Euro FK and pressure gaug...

Page 5: ...ions of the appliance with packaging in mm Weight of Edenpac 2 with packaging 98 kg Weight of Edenpac 3 with packaging 101 kg Weight of Edenpac 4 5 with packaging 110 kg 1275 480 870 To be transported...

Page 6: ...6 2 2 2 Edenpac 6...

Page 7: ...anner 13 1 ratchet spanner 1 pliers 2 straps for handling Choose the appliance installation site according to the following criteria the appliance must be installed outdoors the clearance around the a...

Page 8: ...re are not water jets In the contrary case respect a minimum distance of 3 5 metres Attention Do not lift the appliance by picking it up at the front and or the water inlet outlet points Use 2 lifting...

Page 9: ...crews 2 and 3 on the right side using a cross head screwdriver Slide the entire front panel forward and then down 4 1 2 Edenpac with double fan Turn the 2 clips 1a and 1b in the front turn clockwise u...

Page 10: ...ent facility see diagrams below Hydraulic circuit test pressure 3 bar Hydraulic circuit operating pressure 1 5 bar Edenpac 2 3 4 and 5 Average water flow 5 to 6 5 m3 h pressure drop 1 3 to 1 7 mCE 0 1...

Page 11: ...olarity 230V 50Hz between terminals 1 2 refer to the electrical wiring diagram below Possibility to connect an exterior fault indicator of 230V 50Hz between terminals 0 and 4 refer to the electrical w...

Page 12: ...f the water temperature becomes or is lower than the target temperature the regulator unit authorises heating after a set time of 180 seconds the Led blinks and then remains on 5 2 Setting the target...

Page 13: ...at the base of the unit may be due to normal condensation of the water vapour in the air or due to the defrost cycle in progress phenomenon visible if the additional condensation evacuation kit is not...

Page 14: ...d longer than or equal to 3 s a timer of 130 seconds min is activated before the unit starts again For information this time period may increase during a defrost cycle or if the compressor stop time i...

Page 15: ...ne hour Consult a PSA approved technician to check the sensor and operation of the defrost cycle Cut power supply or press the button if dtd starts blinking after stand by Ofr5 and switch the regulato...

Page 16: ...g operations must be carried out at least once a year Clean the evaporator at the back of the heat pump with a soft brush and gentle water spray Never use a high pressure cleaner for this operation Ch...

Page 17: ...17 9 ELECTRICAL DIAGRAMS 9 1 Electrical diagram of connection interface card To J11 and J12 To J6 and J14...

Page 18: ...18 9 2 Electrical diagram EdenPAC single phase IMPORTANT Elimination or shunting of one of the safety or remote control devices automatically cancels the GUARANTEE...

Page 19: ...19 9 3 Electrical diagram EdenPAC three phase IMPORTANT Elimination or shunting of one of the safety or remote control devices automatically cancels the GUARANTEE...

Page 20: ...or shunting of one of the safety or remote control devices automatically cancels the GUARANTEE With an aim to improving its products PSA reserves the right to modify the characteristics without prior...

Reviews: