Installation of the hot water boiler of series
“Pyrotherm”
Norms and requirements.
4.1. Basic requirements for installation of wood gasification hot water
boiler of series “Pyrotherm”:
•
The room, dedicated to mount the hot water boiler should be supplied
with fresh air supply duct, necessary for optimal combustion process as
well as room ventilation;
•
Installation of the hot water boiler in inhabitable premises, including
dwelling corridors, is not allowed;
•
The hot water boiler should be connected to the heating system by
authorized personal only;
•
Installation and service procedures of the hot water boiler should be
performed by authorized qualified and certified personal ONLY;
•
The wood gasification boiler of series “Pyrotherm” could be attached to a
heating system, equipped with opened or closed expansion vessel, which
should be designed for the water capacity of the entire heating system (its
capacity is calcutated at the step of heating system project development);
•
Both the entire heating system and the hot water boiler should be totally
filled with circulating fluid (water) and air-free before operating the
boiler;
•
Maintenance procedures of the boiler (as well as the heating system)
should be performed by trained adult persons, which have read the user
manual of the unit;
ATTENTION: at the transport of the boiler, take care to preserve the ceramic
element, mounted in the combustion chamber of the boiler not to be cracked or
damaged (secure the detail, or even transport it separately from the boiler);
Installation procedure of the hot water boiler requires engineering project
for the heating system, prepared according to the acting local norms and
recommendations as follows:
•
To the heating system - EN 303-5/2000 - „Heating boilers. Part 5 :
Heating boilers for solid fuels, hand and automatically fired, nominal
heat output of up to 300 kW. Terminology, requirements, testing and
marking”;