2.2 Wiring Table
Note
:
The diameter of connection wire depend on rated power of
UPS
In the below table, for single phase model, “L” represents line wire, for
three phase model, “L” represents the wire of L1,L2,L3 and the diameter
of three phase is the same.
Model
EX6K
EX6KL
EX10K
EX10KL
EX3110KL EX3115KL EX3120KL
In
pu
t
G
10AWG
6
m
㎡
10AWG
6
m
㎡
8AWG
10
m
㎡
8AWG
10
m
㎡
8AWG
10
m
㎡
6AWG
25
m
㎡
6AWG
25
m
㎡
N
10AWG
6
m
㎡
10AWG
6
m
㎡
8AWG
10
m
㎡
8AWG
10
m
㎡
8AWG
10
m
㎡
6AWG
25
m
㎡
6AWG
25
m
㎡
L
10AWG
6
m
㎡
10AWG
6
m
㎡
8AWG
10
m
㎡
8AWG
10
m
㎡
8AWG
10
m
㎡
6AWG
25
m
㎡
6AWG
25
m
㎡
Ba
tt
er
y
+
10AWG
6
m
㎡
10AWG
6
m
㎡
8AWG
10
m
㎡
8AWG
10
m
㎡
8AWG
10
m
㎡
6AWG
25
m
㎡
6AWG
25
m
㎡
-
10AWG
6
m
㎡
10AWG
6
m
㎡
8AWG
10
m
㎡
8AWG
10
m
㎡
8AWG
10
m
㎡
6AWG
25
m
㎡
6AWG
25
m
㎡
G
10AWG
6
m
㎡
10AWG
6
m
㎡
8AWG
10
m
㎡
8AWG
10
m
㎡
8AWG
10
m
㎡
6AWG
25
m
㎡
6AWG
25
m
㎡
Ou
tp
ut
L
10AWG
6
m
㎡
10AWG
6
m
㎡
8AWG
10
m
㎡
8AWG
10
m
㎡
8AWG
10
m
㎡
6AWG
25
m
㎡
6AWG
25
m
㎡
N
10AWG
6
m
㎡
10AWG
6
m
㎡
8AWG
10
m
㎡
8AWG
10
m
㎡
8AWG
10
m
㎡
6AWG
25
m
㎡
6AWG
25
m
㎡
G
10AWG
6
m
㎡
10AWG
6
m
㎡
8AWG
10
m
㎡
8AWG
10
m
㎡
8AWG
10
m
㎡
6AWG
25
m
㎡
6AWG
25
m
㎡
2.3 UPS Connection
Dangerous: The rated current of mains breaker installed by user must bigger than
input current of UPS, or the mains breaker may be damaged.(About maximum input
Summary of Contents for EX series
Page 1: ...EX SERIES EX6K L EX10K L EX3110K L EX3115K L EX3120K L USER MANUAL...
Page 8: ...4 1 2 Front View 1 3 Rear View EX6KL EX10KL EX6K EX10K EX3110KL EX3115KL EX3120KL EX10K EX6K...
Page 9: ...5 EX6KL EX10KL EX3110KL EX3115KL EX3120KL...
Page 20: ...16...
Page 21: ...17...
Page 25: ...21...
Page 33: ...29 4 2 Operate mode 1 AC mode AC Mode 2 Battery Mode Battery Mode...
Page 34: ...30 3 Standby Mode Standby Mode 4 Bypass Mode Bypass Mode...