TS200 Series Tripod Turnstile

User Manual

P a g e

|

10

Note:

The third party access control system lock relay trigger time should be 1 second or less than 1

second.

Connection Diagram of the Access Controller

Figure 4-2

Note:

The lock relay duration of access controller device needs to be set to 1s. Forbidden using

electrically charged objects to connect to the port of Opening Signal Input, otherwise will damage
the control board.

DIP K1 Switch Configuration

Figure 4-3

Pin

1

2

3

4

5

6

7

8

Function Setting

Opening Duration Direction Indicator Continue Passing Function Alarm

Default

1

1

1

0

1

0

0

0

0=ON

1=OFF

4.3.1

Setting the Turnstile Opening Duration

Opening duration refers to the period of time from opening to closing once the turnstile receives an
opening signal. In the DIP switch, number 1, 2, and 3 are used for duration settings. It can be set to
different values from 5s to 60s according to the following chart.

Summary of Contents for TS200 Series

Page 1: ...ZKTECO CO LTD All rights reserved Thank you for choosing our product Please read the instructions carefully before operation Follow these instructions to ensure that the product is functioning properly The images shown in this manual are for illustrative purposes only ...

Page 2: ...l P a g e 1 About the Manual This manual introduces the operations of TS200 Series Tripod Turnstile product All figures displayed are for illustration purposes only Figures in this manual may not be exactly consistent with the actual products ...

Page 3: ...key names for devices For example press OK Window names menu items data table and field names are inside square brackets For example pop up the New User window Multi level menus are separated by forwarding slashes For example File Create Folder Symbols Convention Description This implies about the notice or pays attention to in the manual The general information which helps in performing the opera...

Page 4: ...IAGRAM 9 FUNCTION DESCRIPTION OF THE TURNSTILE CONTROL BOARD 9 CONNECTION DIAGRAM OF THE ACCESS CONTROLLER 10 DIP K1 SWITCH CONFIGURATION 10 4 3 1 SETTING THE TURNSTILE OPENING DURATION 10 4 3 2 DIRECTION INDICATOR 11 4 3 3 CONTINUE PASSING FUNCTION 11 4 3 4 ALARM FUNCTION OPTIONAL 11 5 EQUIPMENT PRECAUTIONS AND MAINTENANCE 12 PRECAUTIONS 12 MAINTENANCE 13 6 TROUBLESHOOTING 14 ATTACHMENT 1 FACTORY...

Page 5: ...ifications Input Voltage AC 100 120V 200 240V 50Hz 60Hz Arm Length mm 500 Operating Environment Indoor and Outdoor shelter Dimension mm Figure 1 L 1200 W 280 H 980 Operating Temperature 28ºC 60ºC Package Size mm L 1275 W 370 H 1063 Operating Humidity 5 85 Flow Rate Max 30 passages minute Input Control Signal Dry contact Rated Power 18 W Figure 1 ...

Page 6: ...gure 2 1 Power on Test before Installation 1 Please make sure that the power requirements are strictly met to avoid permanent damages to the unit Input voltage AC 100 120V 200 240V Note The tripod turnstile must be connected to the ground earth 2 Power on and wait 30s for the tripod turnstile to finish the self check program 3 Lift the arms manually as shown in Figure 2 2 4 Check whether the tripo...

Page 7: ...3 1 Figure 3 1 Notes 1 When installing the tripod turnstile against the wall please reserve a distance of at least 100 mm in order to open the cover for future adjustment and maintenance 2 The spare space from the end of the arm shall not be greater than 80 mm see Figure 3 1 3 You are also recommended to set a warning line for card swiping see Figure 3 2 The warning line prompts users to swipe car...

Page 8: ...ing as shown in Figure 3 3 Units of all data is millimeter Power supply and communication wire should go through the inlet Cable protection covers are suggested to use if it is surface mounted Warning The tripod turnstile must be connected to the ground earth there is wiring interface near the power switch Figure 3 3 ...

Page 9: ...d use a horizontal ruler to test the levelness of the mounting plate If the mounting plate is not levelled adjust it with the gaskets provided Note that all the four expansion bolts must be installed properly as shown in Figure 3 4 Figure 3 4 3 Install the turnstile on the mounting plate and tighten the screws Apply screw securing glue before using and putting gaskets on the screws to adjust the d...

Page 10: ...ion of the Turnstile Control Board If you are using standard device that without RFID or Fingerprint reader you need to connect access control system to the main board please check the content in this chapter carefully Turnstile control board s diagram as shown in Figure 4 1 Figure 4 1 ...

Page 11: ... port of Opening Signal Input otherwise will damage the control board DIP K1 Switch Configuration Figure 4 3 Pin 1 2 3 4 5 6 7 8 Function Setting Opening Duration Direction Indicator Continue Passing Function Alarm Default 1 1 1 0 1 0 0 0 0 ON 1 OFF 4 3 1 Setting the Turnstile Opening Duration Opening duration refers to the period of time from opening to closing once the turnstile receives an open...

Page 12: ...ion With the Continue Passing function the turnstile could remember at most 20 swipes of one card at one time and allows up to 20 people to pass so they don t have to swipe card each time This function can be enabled or disabled with number 6 in the DIP switch The descriptions of the bit settings are as follows In the DIP switch number 6 is used to enabled or disabled the Continue Passing Function...

Page 13: ...ables are connected properly this equipment can be immersed under water at a depth of 250 mm but it must not be powered on when it is immersed in water 3 It is highly recommended to set a warning card swiping line to remind passers by to correctly swipe cards at a reasonable distance from the device to prevent passers by from being squeezed 4 It is recommended to place a warning sign at a conspicu...

Page 14: ...mmended placing warning signs at conspicuous positions for alerting every passersby to pass carefully and in good order Reasonable maintenance consciousness helps to guarantee long term usage of the tripod turnstile Regular maintenance Cleaning and protection liquid dedicated for stainless steel are recommended to wipe the outer shell of the equipment regularly The tripod turnstile used outdoors o...

Page 15: ...cessful authentication It may be caused by lack of permission or a circuit problem 1 Check whether the user has the permission to pass 2 Use a multimeter to check whether the NO and COM ports of the access control system have a relay signal output 3 Short circuit the ports K1 GND and K2 GND if the turnstile is successfully opened the controller is not normal In this case please refer to Attachment...

Page 16: ...cation TCP IP 192 168 1 201 5 Turnstile Opening Duration 5s 6 Passing Direction Indicator Passing is allowed in both directions 7 Continue Passing Function Disabled 8 Alarm Function Disabled Note The Lock Driving Duration is 5 seconds by default Please set it to 1 second Do not connect an electrically charged objects to any ports of Opening Signal Input otherwise it will damage the control board ...

Page 17: ... g e 16 Attachment 2 Connection Diagram of Control Board and Access Control Panel Warning This is a class A product In a domestic environment this product may cause radio interference so that the user may have to take adequate additional measures ...

Reviews: