TS200 Series Tripod Turnstile
User Manual
P a g e
|
10
Note:
The third party access control system lock relay trigger time should be 1 second or less than 1
second.
Connection Diagram of the Access Controller
Figure 4-2
Note:
The lock relay duration of access controller device needs to be set to 1s. Forbidden using
electrically charged objects to connect to the port of Opening Signal Input, otherwise will damage
the control board.
DIP K1 Switch Configuration
Figure 4-3
Pin
1
2
3
4
5
6
7
8
Function Setting
Opening Duration Direction Indicator Continue Passing Function Alarm
Default
1
1
1
0
1
0
0
0
0=ON
1=OFF
4.3.1
Setting the Turnstile Opening Duration
Opening duration refers to the period of time from opening to closing once the turnstile receives an
opening signal. In the DIP switch, number 1, 2, and 3 are used for duration settings. It can be set to
different values from 5s to 60s according to the following chart.