Chapter 6. Description of Operation of Protection Subsystem
6-41
M7IRDA2003I
7IRD-A/J/M: Distribution Protection & Control Terminal
© ZIV APLICACIONES Y TECNOLOGÍA, S.L.U. 2020
Table 6-3: Auxiliary Outputs
Num
Name
Description
Function
61
IR
Reclose Initiate (7IRD-A/J)
Collocate the Recloser in the
start time state (from a rest
situation of the Recloser).
62
SUTM_A
Phase A Time Overcurrent Mask Enabled Trip
Output
Unit Trips. Affected by their
corresponding trip mask.
63
SUTM_B
Phase B Time Overcurrent Mask Enabled Trip
Output
64
SUTM_C
Phase C Time Overcurrent Mask Enabled Trip
Output
65
SUTM_N
Ground Time Overcurrent Mask Enabled Trip
Output
66
SUIM_A
Phase A Inst. (7IRD-A/M) / Inst. 1 (7IRD-J)
Overcurrent Mask Enabled Trip Output
67
SUIM_B
Phase B Inst. (7IRD-A/M) / Inst. 1 (7IRD-J)
Overcurrent Mask Enabled Trip Output
68
SUIM_C
Phase C Inst. (7IRD-A/M) / Inst. 1 (7IRD-J)
Overcurrent Mask Enabled Trip Output
69
SUIM_N
Ground Inst. (7IRD-A/M) / Inst. 1 (7IRD-J)
Overcurrent Mask Enabled Trip Output
70
FASEM_A
Open Phase Mask Enabled Trip Output
71
RESIDUALM
Residual Current Mask Enabled Trip Output
74
BI
Recloser Lockout (7IRD-A/J)
Any of the internal blocks
described below.
75
SBI_NTR
Recloser Lockout Due to Lack of Rated Voltage
(7IRD-A/J)
The voltage reference input is
not active before the waiting
time of the reference voltage (if
the Recloser supervision by
reference voltage setting is
enabled).
76
SBI_DD
Recloser Lockout Due to Permanent Fault
(7IRD-A/J)
This signal is activated when all
the recloses take place and the
fault is still there.
77
SBI_FC
Recloser Lockout Due To Breaker Close Failure
(7IRD-A/J)
The breaker has not closed
during the time of the closure
failure (logic setting – time of
breaker closure failure).
78
SBI_FI
Recloser Lockout Due To Breaker Failure
(7IRD-A/J)
End of the starting time without
resetting of the fault and
breaker opening.
79
SBI_FL
Recloser Lockout Due To Switch-On-To-Fault
(7IRD-A/J)
If following a manual close or a
change of setting, there is a trip
before the security time has
elapsed after manual close.
80
SBI_IA
Recloser Lockout Due To Open Breaker Status
(7IRD-A/J)
Breaker opened without a fault
associated with the breaker
operation.
81
SBI_NCR
Recloser Lockout Due To Unsatisfied Reclosing
Conditions (7IRD-A/J)
Signal related to the Operation
Inhibition Input.
82
RCC_1
Reclose Attempt 1 (7IRD-A/J)
Signal the sequence in which
the Recloser is.
83
RCC_2
Reclose Attempt 2 (7IRD-A/J)
84
RCC_3
Reclose Attempt 3 (7IRD-A/J)
85
RCC_4
Reclose Attempt 4 (7IRD-A/J)