Annex B. DNP 3.0 Communications Protocol
B-9
M7IRDA2003I
7IRD-A/J/M: Distribution Protection & Control Terminal
© ZIV APLICACIONES Y TECNOLOGÍA, S.L.U. 2020
Metering Changes (Deadband Values)
The second option,
Deadband Values
, presents the possibility to adjust independently the
analogic metering bands (according to equipment and model). The setting represents the
percentage over the maximum value of the measure that will be taken as reference to test if
there is an analogical change to record.
If it is adjusted to 100%, analogical changes in this measure will not be recorded, which is then
understood as being in a deactivated state.
EDC Local-Telecomand
The third option presents the possibility to adjust the selection mode of the calculated digital
status (
EDC
) as
Local / Telecomand.
B.4.3
Information Access
The previous options are in the same position at information menu too. It’s important to
remember that at information menu the settings can be shown but they can’t be modified.