COMMISSIONING SERVICING 

FILLING 

Check  all  connections  for  water  tightness  including  any  factory  made 
connections  such  as  the  immersion  heater  and  the  temperature  and 
pressure relief valve. The pressure in the expansion vessel should 
be checked to ensure it is 3 bar (45PSI). The valve is of the car tyre 
(Schrader) type. 

The hot tap furthest away from the AquaFlo should be opened 
before filling the system to let air out. The system should be flushed 
before use. The remaining taps should be opened in turn to expel air. 

DIRECT UNITS 

The system must be fully filled and flushed before switching on the 
power to the immersion heaters and allowing the unit to heat up. 
The immersion heater is supplied preset at 55°C. Turning fully to + 
sets to approx 65°C. 

INDIRECT UNITS 

Ensure the lever on the two port valve is set to the filling position and 
use  the  boiler  manufacturers  commissioning  instructions  to  fill  the 
primary  circuit.  When  full  release  the  lever.  Switch  the 
programmer  to  Domestic  Hot  water  (DHW)  and  allow  the  unit  to 
start  to  heat.  Adjust the dial of the dual thermostat to between 55°C 
and 65°C as required. 

STORAGE TEMPERATURE 

A  storage  temperature  of  60-65°C  is  normal  for  both  direct  and 
indirect  AquaFlos.  In  hard  water  areas  consideration  should  be 
given to reducing this to 55-60°C. In many healthcare applications 
the  guidance  on  Legionella  control  and  safe  water  delivery 
temperatures  will  require  storing  the  water  at  60-65°C, 
distributing at 50-55°C and using thermostatic mixing valves to control 
the final temperature. For details consult the NHS estates guidance 
on safe hot water temperatures. 

SAFETY VALVE CHECKS 

Any  water  coming  from  either  the  expansion  relief  valve  or  the 
temperature/pressure  relief  valve  during  heat  up  is  indicative  of  a 
problem which needs to be identified and rectified. The temperature 
relief and expansion relief valves should be fully opened, one at a 
time  then  both  together  allowing  as  much  water  as  possible  to  flow 
through the tundish. Check that your discharge pipework is free from 
debris  and  is  carrying  the  water  away  without  spillage  over  the 
tundish and release the valves and check that they reseat properly. 

 

 

 

 

 

 

 

GENERAL 

Servicing should only be carried out by competent installers and any 
spare  parts  used  must  be  purchased  from  Zip  Heaters.  NEVER 
bypass  any  safety  devices  or  operate  the  unit  without  them  fully 
operational. 

DRAINING 

Isolate  from  the  electrical  supply  to  prevent  the  immersion  heaters 
burning out. Isolate the unit from the cold mains. Attach a hose to 
the draining tap ensuring it reaches to a level below the unit. (This will 
ensure an efficient syphon is set up and the maximum amount of 
water is drained from the unit). Open the hot tap closest to the unit 
and open the draining tap.   

 

 

 

 

WARNING: WATER DRAINED OFF MAY BE VERY HOT! 
 
ANNUAL SERVICING 

A competent installer should carry out the following checks on an 
annual basis, ideally at the same time as the annual boiler service. 

1)  The expansion relief valve on the inlet control set should be eased 

open allowing water to flow for 5 seconds. The valve should then 
be  closed  making  sure  it  re-seats  correctly.  Repeat  this 
procedure  with  the  pressure/temperature  relief  valve.  Always 
ensure that the discharge pipework is allowing the water to drain 
away adequately. If not check for blockages etc. and clear. 

WARNING: THE WATER DISCHARGED MAY BE VERY HOT! 

2)  Ensure  that  any  immersion  heaters  that  are  fitted  are  working 

correctly and that they are controlling the water at a temperature 
of between 55°C and 65°C. 

3)  Make sure the pressure in the expansion vessel is charged to 3 

bar. Turn off the water supply to the unit and open a hot tap first. 
The valve on the expansion vessel is a Schrader (standard car 
tyre) type. Air or CO2 can be used to repressurise the expansion 
vessel. 

4)  Remove the head on the inlet control set by unscrewing, and 

clean the mesh filter within. 

YOUR WARRANTY MAY BE VOID WITHOUT PROOF OF 
ANNUAL SERVICING. 

Summary of Contents for AquaFlo II

Page 1: ...nance and User Instructions AquaFlo II Issue 3 December 2011 Please read these instructions carefully before commencing installation of the AquaFlo unvented water heater Please leave these instruction...

Page 2: ...ler holding their G3 unvented qualification The installation of this product is also notifiable under the national building regulations The electrical installation including earthing and cross bonding...

Page 3: ...ould be remembered that for every 1 meter that an outlet is above the AquaFlo the pressure will be reduced by 0 1 bar If siting outside the heated envelope of the dwelling such as in a garage or outbu...

Page 4: ...e necessary to incorporate an extra expansion vessel into the circuit to accommodate the increased system water volume in larger secondary circulation systems Where off peak electrical tariffs are bei...

Page 5: ...ervices supplying water for domestic use within buildings and their curtilages b Have a vertical section of pipe at least 300mm long below the tundish before any elbows or bends in the pipework c Be i...

Page 6: ...Black O Orange G Y Green Yellow Br Brown L Live N Neutral C Common SL Switched Live E Earth 3 Port mid position Cutout combined duostat 2 Port DHW C E 2 1 Br G Bl O G Y 1 2 3 Br G Bl O GY 1 2 3 C E 2...

Page 7: ...d be fully opened one at a time then both together allowing as much water as possible to flow through the tundish Check that your discharge pipework is free from debris and is carrying the water away...

Page 8: ...serviced annually All the components fitted to or supplied with the AquaFlo carry a 2 year warranty EXCLUSIONS THE WARRANTY DOES NOT COVER The effects of scale build up Any labour charges associated w...

Page 9: ...1 74 16 46 12 0 1 0 1 07 AF4120 118 915 30 148 105 16 46 16 0 1 0 1 23 AF4150 148 1102 38 186 132 18 55 17 2 1 0 1 41 AF4180 178 1290 42 220 160 18 55 20 4 1 0 1 53 AF4210 208 1478 45 253 188 18 55 22...

Page 10: ...t to alter data specifications and component parts without prior notice IMPORTANT No liability is accepted for incorrect use or installation of this product Zip Heaters UK Ltd 14 Bertie Ward Way Dereh...

Reviews: