background image

ZGR SWIT NG 

 

 

Operation manual 

www.zigor.com 

22 

 

7.1  Battery maintenance  

 

 

 

It is not necessary to discharge the battery completely, as this could involve the unnecessary risk of disconnecting 
the load. After these intentional discharges, leave the 

SWIT NG connected for at least 6 hours in order to recharge 

the battery.  In the case of spontaneous, long and frequent mains power failures that cause the battery to 
discharge a great deal, it is not necessary to carry out the aforementioned maintenance charging operations. 

 

Placing the batteries correctly so that all their elements can be easily reached facilitates maintenance. 
Maintenance consists of checking the following aspects: 

 

Cleanliness: The elements, their connections and supports must be kept clean and dry. It is 
recommended to protect the terminals and metal connections with diluted vaseline. Do not use cleaning 
products containing solvents and/or harmful substances for cleaning elements with plastic containers. 

 

Connections and terminals: Check the tightness of nuts on the poles of elements as well as the 

tightness of the electrical connection with at regular intervals of approximately 12 months. 

 

Checking voltages: Check the voltages of elements in order to detect any possible anomalies in these. 

 

Refilling elements with electrolyte (only when appropriate): The electrolyte level must never be under 

the minimum safety mark. The electrolyte level must be made up with distilled water. Filling with 
electrolyte must only be done when it is necessary to replace the original. Never exceed the maximum 
level indicated on the elements. Should electrolyte fall on the elements or their accessories during the 
refilling operation, the affected parts must be cleaned thoroughly and then dried. 

 

Checking the density of the electrolyte (only when appropriate): The density does not vary according 

to the load status; nevertheless it decreases during the service life of the battery. The standard density of 
the electrolyte depends on the manufacturer. 

 

Do not smoke, light a fire or generate sparks near batteries during recharging as there is a risk of fire and/or 
explosion. 

For cleaning, do not use synthetic material clothes or sponges. Keep batteries clean and dry at all times. Protect 
them against dirt, dust, metal shavings, etc. 

Checking battery voltages: You are recommended to check the voltages on each element of the battery, both in 

Efficient maintenance lengthens the service life of batteries and ensures that the unit operates correctly.

 

 

WARNING 

In order to ensure that the active material of the internal plates that form part of the battery maintain their 
accumulative properties in the most suitable manner, it is recommended to discharge the 

ZGR SWIT NG 

battery once a year. To do this, just leave it operating under load conditions or without a load by disconnecting 

this from the mains for an appropriate amount of time. 

 

WARNING 

If the 

ZGR SWIT NG  is to be disconnected for a month or more, you must disconnect the battery circuit 

breaker to prevent consumption in the 

ZGR SWIT NG’s electronic systems. 

 

WARNING 

 

Electrolyte is highly corrosive. In the case of any contact with the skin, remove stained clothing and wash with 
abundant water those parts of the skin affected. The case of any problem, see a doctor. The case of any 

contact with one's eyes, rinse with a great deal of water for 10 to 15 minutes and see an ophthalmologist.

 

 

Summary of Contents for ZGR SWIT NG

Page 1: ...Manual de Operaci n Operation Manual ZGR SWIT NG Rectificador Cargador conmutado Switching Rectifier Charger www zigor com...

Page 2: ......

Page 3: ...5 5 Procedimientos de operaci n 18 5 1 Procedimiento de puesta en marcha del ZGR SWIT NG 18 6 RESOLUCI N DE PROBLEMAS 19 6 1 Aver as del ZGR SWIT NG 19 6 2 Repuestos recomendados 20 7 MANTENIMIENTO 21...

Page 4: ...sponsabilidad de ZIGOR es necesario que el operador elabore y publique instrucciones o advertencias de seguridad el personal afectado tiene que comprender y confirmar el contenido de las mismas Uso co...

Page 5: ...resistente a fluidos corrosivos cidos o alcalinos seg n tipo de bater as y predispuesto de acuerdo con las normas locales Si el electrolito entra en contacto con la piel la zona afectada debe ser lava...

Page 6: ...el marco general v lido en toda la Uni n Europea para la retirada y reutilizaci n de los residuos de los AEE Para deshacerse de este producto y asegurar su adecuada gesti n siga la Legislaci n y norm...

Page 7: ...mpruebe si el material entregado corresponde con el resguardo de entrega Esto se realizar consultando la etiqueta del fabricante que se encuentra en la parte posterior o lateral del equipo El riesgo d...

Page 8: ...o en condiciones de ausencia de suministro el ctrico La tendencia es a la alimentaci n distribuida por lo que se demanda sistemas de peque a potencia ZGR SWIT NG localizados en la proximidad del equip...

Page 9: ...s para conseguir una adquisici n de energ a de la red con alto factor de potencia 2 2 Principales caracter sticas Alto rendimiento Amplia gama de soluciones personalizadas de 500 a 1000W en 24 48 110...

Page 10: ...en producir perturbaciones en los equipos electr nicos y en la red Detr s del filtro EMI de entrada nos encontramos con un sistema de precarga Este sistema evita corrientes de pico elevadas en el arra...

Page 11: ...cto Tomando como referencia una temperatura de 20 C a una temperatura ambiente por encima de 20 C corresponde una menor tensi n de salida T amb 20 C menor V Salida en caso contrario sube teniendo como...

Page 12: ...escarga de la bater a Se puede considerar como un aviso de seguridad se enciende cuando la tensi n de bater a se aproxime al valor de la parada final de descarga Una vez llegado al valor de parada fin...

Page 13: ...as y o ZGR SWIT NG En caso de no observar estas recomendaciones se perder n las condiciones de garant a Coloque todo el conjunto en el lugar de funcionamiento como se indica en el siguiente apartado C...

Page 14: ...ara soportar su peso Este debe quedar inm vil y estable En caso de que el ZGR SWIT NG y las bater as vayan en el mismo cofre desplace primeramente el armario de bater as vac o sin las bater as y coloq...

Page 15: ...ficamente un Interruptor Diferencial en la l nea de red anterior al equipo Adem s de elemento de seguridad nos proporciona una forma de desenergizar la red en los procesos de instalaci n y mantenimien...

Page 16: ...iza la carga de bater a bornas de al lado Para ello usted tiene que tener presente que no se debe superar la corriente m xima que entrega el ZGR SWIT NG mirar la tabla superior A mayor corriente de co...

Page 17: ...ada a la corriente m xima de utilizaci n En el caso de suministrar bater as de Plomo recordar la necesidad de efectuar recargas peri dicas como m nimo cada 6 meses en caso de almacenamiento Como prueb...

Page 18: ...que este comience a funcionar 1 Compruebe que el led de se alizaci n de alimentaci n OK permanece encendido verde 2 Presione el pulsador de encendido hasta la posici n ON 3 Compruebe que el led de se...

Page 19: ...omprobar posibles humedades en el entorno Si persiste avisar a ZIGOR M x tensi n de salida Led rojo encendido La Vcc se sit a por encima del margen establecido en f brica dependiendo de los modelos Av...

Page 20: ...erg a proveniente de sobretensiones en la red M dulos T rmica un termostato vigila la temperatura del circuito de potencia Limitaci n de corriente de salida al 100 de la corriente nominal depende de c...

Page 21: ...amiento LEDs indicando un correcto funcionamiento Valores dentro de m rgenes Ning n evento activo o Control del hist rico de eventos en busca de fallos espor dicos o repetitivos Semestralmente o Verif...

Page 22: ...ca de seguridad m nima Solo se debe completar el nivel del electrolito con agua destilada El rellenado con electrolito solo se debe realizar cuando haya que sustituir el original Nunca sobrepasar el n...

Page 23: ...E brevemente para resetear la alarma MUY IMPORTANTE Antes de presionar el bot n aseg rese con un aparato de medida que la tensi n y polaridad en los bornes BAT y BAT del cargador son las adecuadas En...

Page 24: ...de la carga 8 Variaci n del 5 al 95 de la carga 5 Variaci n del 5 al 95 de la carga 5 Tiempo 3 ms Tiempo 5 ms Tiempo 5 ms Variaci n del 95 al 5 de la carga 7 Variaci n del 95 al 5 de la carga 4 Variac...

Page 25: ...utilizada es este caso ha sido Prescripciones generales y prescripciones de seguridad Normativa UNE EN 50178 1998 Directiva europea de Compatibilidad Electromagn tica 89 336 CEE y posteriores enmiend...

Page 26: ...s a las condiciones de instalaci n Cuando el cliente no demuestre fehacientemente la realizaci n sistem tica de las labores de mantenimiento peri dicas descritas en el Manual de Operaci n del equipo D...

Page 27: ...5 5 Operating instructions 18 5 1 Start up procedure for the ZGR SWIT NG 18 6 TROUBLESHOOTING 19 6 1 Malfunctions of ZGR SWIT NG 19 6 2 Recommended spare parts 20 7 MAINTENANCE 21 7 1 Battery maintena...

Page 28: ...derstand and confirm their content Use the unit for the purpose for which it was designed The system supplied must be used only for the purpose for which it was designed Any other use is strictly forb...

Page 29: ...hysically damaged they must be placed in a container in resistant to corrosive liquids acids or alkaline according to the type of battery and prepared in accordance with local regulations If the elect...

Page 30: ...012 19 EU WEEE regarding used electrical and electronic equipment Waste electrical and electronic equipment WEEE RD 110 2015 The Directive provides the general framework valid throughout the European...

Page 31: ...loss or damage of Products shall transfer to the Customer from the moment ZIGOR places these at his disposal in the place indicated by the Customer From then on the customer will have 24 hours to make...

Page 32: ...WIT NG situated near the equipment these supply Normal supply sources are not designed to manage battery charges and specialised economic solutions are required In view of the wide variety of applicat...

Page 33: ...mized solutions from 500 to 1000 W in 24 48 110 125V Integrated battery disconnector Reduced harmonic distortion Low input current distortion Battery temperature compensation Easy installation front w...

Page 34: ...y cause disturbances in the economic equipment and in the mains network After the input EMI filter we find a pre charge system This system avoids high peak currents when the equipment is starting up i...

Page 35: ...Taking a temperature of 20 C as reference a lower output voltage corresponds to an atmospheric temperature of above 20 C Atm temp 20 C lower output V in the opposite case it rises the maximum output v...

Page 36: ...idered to be a safety warning It turns on when the battery voltage comes near the end of discharge stop value Once the end of discharge stop value is reached the battery cut off will shut off the load...

Page 37: ...these recommendations not be followed the terms of the warranty will not be applicable Place the complete unit in the place where it is to operate as indicated in the following section Checking the ba...

Page 38: ...he empty battery cabinet without batteries and place these once the cabinet is in position The place chosen must guarantee Easy connections Sufficient space to work with the ZGR SWIT NG system without...

Page 39: ...Differential Switch on the mains line upstream of the unit In addition to being a safety element this provides us with a way of disconnecting the mains supply during maintenance and installation work...

Page 40: ...hile the battery is being charged terminals on side To do this you must remember that the maximum current provided by the ZGR SWIT NG must not be exceeded see table above The higher the consumption cu...

Page 41: ...he cross section of the cable must be appropriate for the maximum load current If lead batteries are supplied remember to recharge periodically at least every six months if stored The final battery co...

Page 42: ...order to turn on the ZGR SWIT NG and start operating 1 Check that the OK supply LED remains on green 2 Press the On Off button to the On position 3 Check that LED 1 rectifier charger turns on green a...

Page 43: ...n established in the factory depending on the model Notify ZIGOR Next end of discharge red LED on The battery is almost completely discharged Wait for the mains supply to return Supply OK green LED of...

Page 44: ...absorb the energy from mains overvoltages Modules Thermal a thermostat checks the temperature of the power circuit Output current limitation at 100 of the nominal current depends on each model Interna...

Page 45: ...argins No active event o Control of the event history in search of sporadic or repetitive failures 6 monthly o Check on the correct ventilation of the location o Cleaning of the equipment s air inlet...

Page 46: ...uld electrolyte fall on the elements or their accessories during the refilling operation the affected parts must be cleaned thoroughly and then dried Checking the density of the electrolyte only when...

Page 47: ...ZGR SWIT NG Operation manual www zigor com 23 charging and discharging in order to detect possible malfunctions...

Page 48: ...h the system completely stopped ZIGOR cannot be held responsible for damages caused to the battery charger or equipment powered by this as well as to personnel in case of not following this recommenda...

Page 49: ...se 5 to 95 variation in charge 8 5 to 95 variation in charge 5 5 to 95 variation in charge 5 Time 3 ms Time 5 ms Time 5 ms 95 to 5 variation in charge 7 95 to 5 variation in charge 4 95 to 5 variation...

Page 50: ...dments The standard used in this case was General regulations and safety regulations Standard UNE EN 50178 1998 European Electromagnetic Compatibility directive 89 336 CEE and subsequent amendments Ha...

Page 51: ...ng annual referring to the Installation Conditions When the customer not clearly proves the systematic realization of regular maintenance operations described in the Operating Manual Equipment deterio...

Page 52: ...zigor com Consulte nuestra web para contactar con la red de delegaciones comerciales Refer to our website in order to contact the commercial branches network Veuillez consulter notre page web pour con...

Reviews: