Appendix SIPROTEC configuration
16.1 Configuration SIPROTEC Compact-Devices (only 7SK80)
Connection of sensors and configuration of RTD box TR1200IP for evaluation of Siemens
SIPROTEC Compact-device 7SK80 at Port A.
Settings for the Ethernet connection between SIPROTEC Compact-device and RTD box TR1200IP:
-Setting in SIPROTEC Compact-
device is „
Ziehl RTD UDP Protocol“
-Setting in RTD TR1200IP is
„Modbus UDP Protocol”
with
„On“
(Presetting = „On“) activated.
CAUTION! The EN100 module in the SIPROTEC 4 devices does not support this function.
The connection type
„6 RTD Ethernet“
or
„12 RTD Ethernet“
from the
RTDs set within „Function scope“
of the Compact-device.
Following settings have to be done in RTD box TR1200IP:
For „6 RTD Ethernet”
Connect Sensors 1…6
Configure Sensors 1...6 in menu item
8
SEN.
8
depending on the connection
(configure sensors that are not connected as "nc")
Configure Sensors 7…12 in menu item
8
SEN.
8
as "nc"
Set IP address in menu item
8
IP .
8
and UDP port in menu item
8
udp
8
The TR1200IP transmits the data of Sensors 1...6 on enquiry (see protocol description) with the
IP address under the set UDP port.
For “12 RTD Ethernet”
Connect Sensors 1…12
Configure Sensors 1...12 in menu item
8
SEN.
8
depending on the connection
Set IP address in menu item
8
IP .
8
and UDP port in menu item
8
udp
8
The TR1200IP transmits the data of Sensors 1...6 on enquiry (see protocol description) with the
IP address under the set UDP port. On enquiry with the same IP address under the set UDP port +1,
the TR1200IP
transmits the data of Sensors 7…12.
Find detailed application description in Internet, at following Link :
> Accessories > Temperature Detection > 7XV5662-8AD10 > Downloads
16.2 Configuration SIPROTEC 5-Devices
Settings for the Ethernet connection between SIPROTEC 5 and RTD box TR1200IP:
-Setting in SIPROTEC 5-
device is „
SUP-
Protocol“
(Slave Unit Protocol)
-Setting in RTD TR1200IP is
„Modbus TCP Protocol”
with
„On“
(Presetting = „On“) activated.
The
„Modbus“
TCP-Protocol can be activated with the function buttons under the menu
8
tcP
8
–
8
mod
8,
or
using the Web-Browser in the tab
„TCP/UDP Config“
with
„On“
activated.
The setting „RTD“ (RTD-Protocol) and „UDP Port“ have no influence here.
The Modbus TCP Port is fix set to 502 and cannot be changed.
The setting of the SIPROTEC 5-device can be found in manual (e.g. 7UT82)
in chapter 5.9 „function group type analog converter“.
In Internet under:
> SIPROTEC 5 > 7UT82 > Downloads
Attention!
The RTD box TR1200IP suppers only
10 MBit/s Ethernet
connections,
so no direct connection to
100 MBit-communication modul
is possible. In such a case you have to use
e.g. an autom. 10/100 MBit/s- Autosensing-Switch between TR1200IP and SIPROTEC 5.