ZIEHL TR1200IP Operating Manual Download Page 6

 

TR1200IP 

12390-0706-05

 

Page

 

6 / 23 

www.ziehl.de 

  

Important notice 

 

DANGER! 

 

 

Hazardous voltage! 

 

Will cause death or serious injury. Turn off and lock out all power 

 

supplying this device before working on this device. 

 

The  flawless  and  safe  operation  of  a  device  requires  that  it  is  shipped  and  stored  appropriately, 
professionally installed and put into operation and operated according to its intended use. 
Only people who are familiar with the installation, commissioning and operation and who have qualifications 
corresponding to their job are permitted to work on the device. They must comply with the contents of the 
operating instructions, the notices attached to the device and the relevant safety regulations for constructing 
and operating electrical plants. 
The  devices  are  built  and  certified  in  accordance  with  DIN/EN/IEC  and  leave  the  factory  in  a  safe  and 
technically flawless condition. To maintain this state you must comply with the safety regulations indicated 
with "Caution" in the operating instructions.  
If the information in the operating instructions is insufficient at any time, please contact us directly or 
contact the representation responsible for you. 
Instead of the industrial norms and stipulations stated in the operating instructions and applicable in Europe, 
you must comply with the valid and applicable regulations in the country of utilization if the device is used 
outside of the area of application. 

 

 

 

 

Caution! If the operating current execution is programmed for all relays,

 

 

    

a failure of the control voltage or the device will not be detected. 

 

 

 

When using as a monitoring device, the operator must ensure that this error is 

 

 

 

detected through periodic performance tests. We recommend programming and 

 

 

 

correspondingly evaluating at least one relay in closed-circuit current execution. 

 

Caution!  Sensor connections 

It is only permitted to connect to or disconnect from sensor  

connections terminals or to plug them in or unplug them with the power supply switched off.  
The pin connections of Sensors 1…6 (below) are not compatible with Sensors 7…12  
(above). If a 3-conductor sensor connected below is to be connected above, both external  
connections must be swapped. The sensors are connected to terminals 1T1 

– 1T2 – 1T3,  

2T1 - 

… - 12T3. The plug-in contacts have special contact material and must only be used  

for connecting the sensors. 

 

Ethernet connection:  

Use the Ethernet connection solely with a shielded patch cable, category 5. The maximum  
cable length is 20m. When using longer cable lengths, the earth potential can shift, causing  
transmission interference. Corrective measures by using media converters can be taken  
which can optically transmit the electrical signal across further distances and, e.g., create the  
connection to an optical switch. 

 

Comply with the maximum permissible temperature when installing in a switch cabinet. Ensure sufficient 
clearance to other devices or heat sources. If cooling is inhibited, e.g., through close proximity to devices 
with increased surface temperature or interference with the cooling-air current, the permissible ambient 
temperature is decreased. 

 
 

 

 

Caution! 

 

 

 

Before applying mains voltage to the device, make sure that the control voltage Us 

 

 

 

complies with the mains voltage connected to the device! 

Summary of Contents for TR1200IP

Page 1: ...2023 11 14 Sc from Firmware 11 For more information and help about this product please scan the QR Code or choose the following link TR1200IP Operating manual Quick guide Datasheet Connection diagram...

Page 2: ...guration mode last decimal point flashes 10 10 7 2 wire cable compensation 10 10 8 Configuring sensors 11 10 9 Configuring the relay 11 10 10 Configuring the Ethernet interface 11 10 11 Simulation 13...

Page 3: ...e digital display FLASHES 8Er18 or 8Er28 Sensor error in the corresponding sensor circuit MORE THAN ONE ON Temperature value of the warmest sensor is displayed in the digital display 3 3 digit digital...

Page 4: ...ensor 7 8 nc8 S Sensor 8 nc8 S 9 Sensor 9 8 nc8 S10 Sensor 10 8 nc8 S11 Sensor 11 8 nc8 S12 Sensor 12 8 nc8 Rel rel Relay function 8 r8 IP IP1 1st block IP address 81928 IP2 2nd block IP address 81688...

Page 5: ...or sensor short circuits are also transmitted via the protocol to the connected evaluation unit 5 Summary of the functions 3 digit digital display for the temperature of up to max 12 measuring points...

Page 6: ...control voltage or the device will not be detected When using as a monitoring device the operator must ensure that this error is detected through periodic performance tests We recommend programming an...

Page 7: ...Mounting The device can be mounted Distribution board or switch cabinet on 35 mm rails according to EN 60715 9 Detailed description 9 1 Description of the connections Connection Function A1 and A2 Su...

Page 8: ...su1 1 Bloc 255 su2 2 Bloc 0 255 su3 3 Bloc 0 255 su4 4 Bloc 0 255 Gat GA1 1 Bloc 0 255 GA2 2 Bloc 0 255 GA3 3 Bloc 0 255 Ga4 4 Bloc 0 255 UDP UD1 1 Bloc 0 655 UD2 2 Bloc 00 35 tcp rtd protocol On off...

Page 9: ...IP18 8IP48 IP address blocks 8IP18 8IP28 IP address blocks set to next Block1 Block2 Block3 Block4 8 08 82558 Subnetwork mask 8Sub 8 Menu item for setting the subnetwork mask subdivided into 4 blocks...

Page 10: ...hanges the value of the parameter If no key is pressed for 2s the display starts alternating again If no key is pressed for 30s simulation mode 15 min one automatically returns to the display mode the...

Page 11: ...nal current flash alternately Use the Up and Down keys to select the relay function Press the Set key exits the configuration mode Display 8rel 8 Relay function 10 10 Configuring the Ethernet interfac...

Page 12: ...st block 0 flash alternately Set the 1st block of the gateway using the Up and Down keys Press the Set key Display 8ga28 808 gateway 2nd block 0 flash alternately Set the 2nd block of the gateway usin...

Page 13: ...f this value is actually being measured Error messages are only indicated with the LEDs and not in the display The set values are simulated until the menu item 8si 8 is left with the Up or Down button...

Page 14: ...ternately Use the Up and Down keys to set the saved pin code factory setting is 85048 Press the Set key Set the desired code lock using the Up and Down keys o 8off 8 off all parameters can be changed...

Page 15: ...nfiguring the gateway 8ga18 8ga48 Blocks 1 to 4 to set the gateway 8udp 8 Menu item to configure the RTD protocol and the setting of the UDP port 8rtd8 ZIEHL RTD protocol 8ud18 8ud28 Blocks 1 to 2 to...

Page 16: ...Er88 appears in the display Internal device error The unit needs to be returned 8Er98 appears in the display Parameter error Do a factory reset False values or sensor error for Sensors 7 12 Sensors 7...

Page 17: ...s at AC 250 V 6 A Temperature measurement Measurement time sensor 0 25 3s dependent on the number of sensors Measurement time sensor 0 25 30s for measurement cycle of one sensor Measurement range 199...

Page 18: ...ons Ambient temperature range 20 C 65 C Storage temperature range 20 C 70 C Altitude Up to 2000 m Climatic conditions 5 85 rel humidity no condensation External wiring temperature range 5 C 70 C Vibra...

Page 19: ...4 Mounting type V8 Dimensions in mm 1 Cover 2 Base 3 Bar for snap mounting 4 Latch for sealing 5 Front panel 6 Identification for down position downward 7 Bar for wall mounting with screws Bar drill h...

Page 20: ...the Internet at www ziehl com TR1200IP ZIEHL RTD protocol 15 2 Modbus TCP protocol The modbus protocol can be switched off in the menu item 8tcp 8 8mod8 The modbus TCP Port is permanently set to 502 a...

Page 21: ...TR1200IP 12390 0706 05 Page 21 23 www ziehl de 15 4 IEC 61850 GOOSE protocol devices with part no T224078 only GOOSE application descriptions see http www ziehl com en AllProducts detail TR1200IP 40...

Page 22: ...he connection Set IP address in menu item 8IP 8 and UDP port in menu item 8udp8 The TR1200IP transmits the data of Sensors 1 6 on enquiry see protocol description with the IP address under the set UDP...

Page 23: ...splayed and the sensor LEDs S1 6 illuminate in succession As soon as the firmware has been transmitted the TR1200IP reprograms itself During this process the sensor LEDs S1 6 flicker rapidly Do not sw...