Quick Guide TR1200  

 

updated: 2017-11-09/Fu 

from Firmware: -03

 

 

TR1200 

12320-0752-04 

Page

 

1 / 8 

www.ziehl.de 

 
- Pt 100 thermostat with 12 sensor ports and Interface RS485 

 
 
Detailed operating manual see: 

http://www.ziehl.com/en/Products/detail/TR1200-39

 

 

Display and controls 

 
 
 
 
 
 
 
 
 
 
 

LED relay state 

(yellow)

 

 

OFF 

The relay  is released 

 

Illuminated 

The relay is picked up 

LED  sensors 

(yellow)

 

 

Illuminated 

Displays the sensor value belonging to the LED in the digital 
display 

 

 

flashes, 

8

Er1

8

or

8

Er2

8

 

Sensor error in the corresponding sensor circuit 

 

All illuminated 

Displays the value of the warmest sensor in the digital display 

Digital display 3 digits 

(red)

 

 

Display of sensor value 

 

Display of error codes e.g.  

8

Er9

8

  

Hindmost decimal point 

(red)

 

  

OFF 

Display mode 

  

Illuminated 

Menu mode 

 

flashes 

Parameter mode 

LED error 

(red)

 

 

OFF 

normal operation 

 

Illuminated with 

8

Er1

8

 , 

8

Er2

8

 , 

8

Er8

8

  or 

8

Er9

8

 

Sensor error, malfunction, invalid parameter 

Button  Up / Down 

(display mode, normal operation)

 

 

Press briefly 

Change into the menu mode (see Operating instructions Point 8.4) 

 

Press for > 2s 

Displays the stored MAX value (Up) / MIN value(Down) 

– press also 

button 

Set for ≥ 2s to erase the stored value 

Button Set / Reset 

(display mode, normal operation)

 

 

Press briefly 

Displays the value of next sensor (sensor LED illuminates) 

 

Press for > 2s 

Reset, back to display mode 

 

Press for > 10s 

Displays the software version (e.g. 

000)

 

LED RS485 Interface 

(yellow)

 

 

Rx flashes briefly 

Unit is receiving data via the RS485 interface 

 

Tx flashes briefly 

Unit is transmitting data via the RS485 interface 

 

Summary of Contents for TR1200

Page 1: ...l illuminated Displays the value of the warmest sensor in the digital display 3 Digital display 3 digits red Display of sensor value Display of error codes e g 8Er98 4 Hindmost decimal point red OFF D...

Page 2: ...L S 2 Sensor 2 3 L S 3 Sensor 3 3 L S 4 Sensor 4 3 L S 5 Sensor 5 3 L S 6 Sensor 6 3 L S 7 Sensor 7 nc S 8 Sensor 8 nc S 9 Sensor 9 nc S10 Sensor 10 nc S11 Sensor 11 nc S12 Sensor 12 nc rel Rel Relay...

Page 3: ...ct condition To keep this condition observe the security instructions with the headline Attention written in the instructions manual Ignoring of the security instructions may lead to death physical in...

Page 4: ...figuration RS485 connection Use RS485 Interface only with shielded wires Large cable lengths may shift the potential ground and the transmission can be disturbed Corrective measures can be galvanic se...

Page 5: ...cluded in delivery Connection according to connection plan or type plate 6 Commissioning 6 1 Control chart Unit Pressing buttons Up Down simultaneously sets the values to the smallest one Code Reset P...

Page 6: ...Sensors 1 12 83 L8 3 conductor connection 8 nc8 No sensor connected 8rel8 Relay function 8bus 8 Menu item for configuring the RS485 interface 8Prt 8 Protocol RS485 interface 84858 RS485 protocol 8Mod...

Page 7: ...chnique Terminals of sensor 1 6 are not compatible to terminals sensor 7 12 Parameter configuration not allowed Code lock active The Code lock can be activated as a protection against manipulation of...

Page 8: ...vice address in menu item 8bus 8 8adr8 to 818 12 RTD half duplex operation mode 1x TR 1200 works like 2x TR 600 The TR 1200 transmits the data from Sensors 1 6 on request with address 1 and from Senso...

Reviews: