background image

 

TR111V 

12090-0703-02

 

Page

 

3 / 8 

www.ziehl.de 

  

Display and controls 

 

  Potentiometer 

%T

” for limit value 

  LED Power 

 

Potentiometer “

Hys

” Hysteresis 

  LED Relay on 

  Potentiometer Switching delay 

don/doff

” 

  Potentiometer 

T

” Selection of measuring-range

 

 
 
 
 
 
 
 
 

Detailed description 

As standard, the relay in the TR111V operates according to the closed-current-mode. If a temperature sensor 
is connected, the relay picks up (11-14 closed = ok). The relay releases in the case of a sensor error. If the 
temperature at the sensor exceeds the adjusted value, the relay releases. The state of the relay is signalled 
by a LED: relay picked up = LED on. At operating-current-mode the function of the relay is inverted. It picks 
up at over-temperature (11-12 closed = ok). 

 

Remark 

Sensors have to be connected with shielded cable. We recommend to connect it to ground on the sensor-
side. 
 

Application and short description 

Temperature-Relays TR111V can be used as limit-switches or 2-point controllers with high repeat accuracy. 
3 measuring-ranges, adjustable hysteresis and switching delay and the choice between operating- and 
closed-current principle of the relay make it a very universal device. Protection from over-temperature in 
processes, plants and machines. Monitoring of temperatures in bearings. Controlling of temperatures in 
processes and plants.

 

 
 

Overview of functions 

 

Measuring input 1x Pt 100 (RTD) / 3-wire 

 

3 or 4 measuring-ranges selectable 

 

1 limit adjustable 0...100 % 

 

switching delay adjustable 0,1...10 s 

 

Output-relay 1 changeover-contact (co) 

 

Operating- or closed-current-principle 

 

Switching off at sensor-short-circuit or break 

 

LEDs for display state of relay 

 

Housing for mounting in switchgear cabinets or fuseboxes, 35 mm wide 

 

Mounting heigt 55 mm 

 

Universal supply-voltage AC/DC 24-240 V 

 
 

 

Summary of Contents for TR111V

Page 1: ...0 info ziehl de www ziehl de Temperature Relays and MINIKA Mains Monitoring Digital Panelmeters MINIPAN Switching Relays and Controls Measuring Transducers Grid and Plant Protection Operating Manual TR111V updated 2017 11 06 sm TR111V 12090 0703 02 Page 1 8 www ziehl de Pt100 Temperature Relay ...

Page 2: ...s 1 Display and controls 3 2 Detailed description 3 3 Application and short description 3 4 Overview of functions 3 5 Connecting diagram 4 6 Function diagram 4 7 Important Information 5 8 Installation 5 9 Error search 5 10 Technical data 6 11 Housing Type V2 8 ...

Page 3: ...d cable We recommend to connect it to ground on the sensor side 3 Application and short description Temperature Relays TR111V can be used as limit switches or 2 point controllers with high repeat accuracy 3 measuring ranges adjustable hysteresis and switching delay and the choice between operating and closed current principle of the relay make it a very universal device Protection from over temper...

Page 4: ...TR111V 12090 0703 02 Page 4 8 www ziehl de 5 Connecting diagram 1 closed current mode 2 operating current mode 3 3 wire 4 2 wire Bridge from T2 T3 6 Function diagram ...

Page 5: ...They must observe the contents of the instructions manual the information which are written on the equipment and the relevant security instructions for the setting up and the use of electrical units The equipment are built according to EN and checked and leave the plant according to security in perfect condition If in any case the information in the instructions manual is not sufficient please con...

Page 6: ...ording to EN60751 Sensor voltage 5 V Sensor current 2 5 mA Short circuit 15 Ω Type of connection 3 wire max resistance 3x 25 Ω Limti value Measuring ranges 3 or 4 ranges selectable 3 measuring ranges 10 40 C 0 100 C 0 200 C Repeat error app 1 K 4 measuring ranges 0 100 C 100 200 C 200 300 C 300 400 C Repeat error app 1 6 K Error of setting 5 K Temperature dependence 0 05 K Hysteresis Adjustable ap...

Page 7: ...68 2 6 2 13 2 Hz 1 mm 13 2 100 Hz 1 g 2 25 Hz 1 6 mm 25 150 Hz 5 g Housing Design V2 Mounting height 55 mm Dimension H x W x D 90 x 35 x 58 mm Line connection solid wire 1 x 0 34 2 5 mm AWG 22 12 Strand wire with insulated ferrules 1 x 0 1 1 5 mm AWG 27 14 Stripping length torque 8 mm 0 5 Nm Protection class housing terminals IP 30 IP20 Attachment mounting 35 mm standard rail according to EN60715 ...

Page 8: ...l base 3 Riegel bar for snap mounting 4 Plombenlasche latch for sealing 5 Frontplatteneinsatz front panel 6 Kennzeichen für unten position downward 7 Riegel bei Wandbefestigung mit Schrauben Riegelbohrung ø 4 2 mm For fixing to wall with screws ø 4 2 mm 48 58 45 3 61 8 16 5 90 Option 98 116 35 3 4 1 2 5 7 6 ...

Reviews: