TR800Web
12280-0755-01
Seite
2 / 8
www.ziehl.de
14
IP address slide switch
Towards Ethernet jack:
IP address 10.10.10.10
Towards reset button:
IP address User (set via web browser)
15
Webserver reset button
Internal webserver restarts when pressed (duration ca. 1 minute)
16
LED (yellow) input state S1 and S2
On: input Sx active
2
Installation
The unit can be installed as follows:
Installation in switchgear cabinet on 35 mm mounting rail according to EN 60715
With screws M4 for installation on walls or panel. (additional latch not included in delivery)
Connection according to connection plan or type plate.
3
Important Information’s
DANGER!
Hazardous voltage!
Will cause death or serious injury. Turn off and lock out all power
supplying this device before working on this device.
Observe the maximum temperature permissible when installing in switching cabinet. Make sure
sufficient space to other equipment or heat sources. If the cooling becomes more difficult e.g.
through close proximity of apparatus with elevated surface temperature or hindrance of the
cooling air, the tolerable environmental temperature is diminishing.
A circuit-breaker or switch must be situated within easy reach of the
unit and fused. Installation excess current protection should be
≤ 10 A.
Before switching on make sure that the operational voltage Us of the
type- plate and the mains voltage are the same.
ATTENTION! When all relays are programmed in operation current mode (= pick up
at alarm), a loss of the supply voltage or an instrument failure can remain
unidentified.
When the relay is applied as control instrument, the operator must ensure, that
this error is recognized by regular examinations.
We recommend to program and accordingly evaluate at least one relay in the
closed-circuit current mode
!
!
!