TR800Web
12280-0755-01
Seite
8 / 8
www.ziehl.de
Inputs
Pt 100, Pt 1000
-
199…+860 °C, according EN 60751
KTY83, KTY84
-
55…+175 °C, -40…+150 °C
Thermocouples
Type B, E, J, K, L, N, R, S, T EN 60 584, DIN 43 710
Voltage- / Current input
0-10 V, 0/4-20 mA
Measuring of resistance
0,0 … 500,0 Ω , 0…30,00 kΩ
Input Y1-Y2
Reset, app. 18 VDC / 3,5 mA
Input S1 and S2
for contact or S0-interface
Network-connection
10/100 MBit
Auto
-
MDIX
RS 485 interface
Baud rate
4800, 9600, 19200 Baud
Parity
N, O, E (none, odd, even)
Wire length
1000 m at 19200 Baud
Test conditions
EN 61010-1
Rated impulse voltage
4000 V
Overvoltage category
Contamination level
III
2
Rated insulation voltage Ui
300 V
On-time
100 %
Galvanic insulation / Test-voltage
Ethernet
– sensors
DC 750 V
Us
– relays, sensors, Ethernet
DC 3820 V
Relays
– sensors, Ethernet
DC 3820 V
Sensors
– relays
DC 3820 V
No galvanic insulation
RS485
– sensors – reset input Y1/Y2 – S1 – S2
Environmental conditions
Ambient temperature range
Storage temperature range
Altitude
Climatic conditions
External wiring temperature range
-20 °C ... +65 °C
-
20 °C …+70 °C
Up to 2000 m
5
– 85 % rel. humidity, no condensation
-
5 °C …+70 °C
Housing
Design V8, switchgear mounting
Dimensions (W x H x D)
140 x 90 x 58 mm
Mounting height / w
idth
55 mm / 8 TE
Wire connection, one wire
each 1 x 1,5 mm
2
Stranded wire with insulated ferrules
each 1 x 1,0 mm
2
Stripping length
8 mm
Torque of screw
0,5 Nm (3,6 lb.in)
Protection class housing / terminal
IP 30 / IP 20
Fitting position
any
Installation
Snap mounting on mounting rail 35 mm according to EN
60 715 or with screws M 4
(2 additional bars, not included
in delivery)
Weight
app. 370 g
Subject to technical changes