Type: TMS 400

22.12.1999

Subject to technical modifications.

EA - Nr.:

9710.1

Technical data

………………………………………

Type - Plate
Order number
Supply voltage U

/ frequency 

Power consumption

………………………………………

Tolerance voltage Us

AC 0.9 ... 1.1 Us

Tolerance frequency Us

48 ... 62 Hz

Sensor connection

     

Sensor

thermocouple (see type plate)

Limit value

     

Adjustment accuracy

approx. 1 % of span

Repeat accuracy

approx. 0,2 % of span

Hysteresis

 2 % of span

Switching state

standard: closed - circuit current principle

option: operating current principle

Relay standard

true > set value = relay released

LED Display

relay released = LED off

Relay output   

1 relay,1 x CO-contact

Switching voltage

max. AC 415 V

Switching current

max. 6 A

Switching power consumption

max. 1100 VA

Rated operational current

2,5 A 400 V AC 15
4 A

250 V AC 15

3 A

24 V

DC 13

Testing conditions

    

VDE 0660 / VDE 0160

Rated insulation voltage Ui
according to VDE 0110

AC 415 V

Isolation

VDE 110 / Gr. C

Transformer

VDE 0550

Test voltage between supply voltage,
relay output and sensor side

2.5 kV

On period

100 %

max. ambient temperature

-20 ... +55 °C

Climatic category

F (according to DIN 40 040)

Housing:

design S-12, plug-in housing

Dimensions (H x W x D)

82 x 42 x 121 mm

Line connection

12-pole, max. 2 x 1.5 mm

2

 each

Protection Housing

IP 30

Protection contacts

IP 20

Panel inclination

any

Mounting

snapable on 35 mm standard rail according to DIN
or assembly with screws M 4

Summary of Contents for TMS 400

Page 1: ...ats of the TMS series are electronic two position controllers Modern circuitry well proved components as well as function and routine tests ensure high repeat accuracy and a long service life Function As standard the TMS 400 thermostats operate according to the closed circuit current principle If a temperature sensor is connected the installed relay picks up The relay always switches off in the ca...

Page 2: ...ased LED off Relay output 1 relay 1 x CO contact Switching voltage max AC 415 V Switching current max 6 A Switching power consumption max 1100 VA Rated operational current 2 5 A 400 VAC 15 4 A 250 V AC 15 3 A 24 V DC 13 Testing conditions VDE 0660 VDE 0160 Rated insulation voltage Ui according to VDE 0110 AC 415 V Isolation VDE 110 Gr C Transformer VDE 0550 Test voltage between supply voltage rela...

Page 3: ... recommended mininum clearance 2 cm Wiring directly to plug base Connect wires as per wiring scheme Plug in electronics and fix with knurled screw Attention Do not plug in device alive nor detach it from socket Before switching on make sure that the operational voltage Us of the lateral type plate and the mains voltage are the same Put into operation the thermostat as follows Connect thermocouple ...

Page 4: ...Wiring scheme 1 2 4 5 6 7 8 9 10 11 12 3 analog output option TMS 400 K1 Us Design S12 5 104 5 82 36 23 5 AA AA AA 38 34 80 61 5 17 5 7 5 41 5 17 41 10 82 1 1 2 3 4 5 7 6 8 9 10 11 12 11 5 16 5 2 3 1 14 27 5 116 AA AA 41 5 Base 1 2 3 Cable bushing Mounting bore hole Unlatching only with rail mounting 2 6 Jacks for coding pins 1 ...

Reviews: