EA - Nr.:

9710.1

Installation - Putting into operation

The plug base can be mounted

35 mm mounting rail according to DIN 50 002

M4 screws

When installing the device into the switch-gear cabinet, please observe the

max. admissible temperature. Care for both sufficient  clearance to other

devices or sources of heat or enough forced draught. Generally

recommended mininum clearance: 2 cm.

Wiring directly to plug base

Connect wires as per wiring scheme

Plug in electronics and fix with knurled screw

Attention!

Do not plug in device alive nor detach it from socket.

Before switching on make sure that the operational voltage Us of the

lateral type plate and the mains voltage are the same.

Put into operation the thermostat as follows

Connect thermocouple.

Switch on mains voltage

At correct state, the LED lights up ( tempeature lower than the set limit ), contacts 7,8

closed. ( Relay picked up ).

Set limit with screwdriver to desired value

Relay releases when set temperature is exceeded, the relevant LED is switched off.

Summary of Contents for TMS 400

Page 1: ...ats of the TMS series are electronic two position controllers Modern circuitry well proved components as well as function and routine tests ensure high repeat accuracy and a long service life Function As standard the TMS 400 thermostats operate according to the closed circuit current principle If a temperature sensor is connected the installed relay picks up The relay always switches off in the ca...

Page 2: ...ased LED off Relay output 1 relay 1 x CO contact Switching voltage max AC 415 V Switching current max 6 A Switching power consumption max 1100 VA Rated operational current 2 5 A 400 VAC 15 4 A 250 V AC 15 3 A 24 V DC 13 Testing conditions VDE 0660 VDE 0160 Rated insulation voltage Ui according to VDE 0110 AC 415 V Isolation VDE 110 Gr C Transformer VDE 0550 Test voltage between supply voltage rela...

Page 3: ... recommended mininum clearance 2 cm Wiring directly to plug base Connect wires as per wiring scheme Plug in electronics and fix with knurled screw Attention Do not plug in device alive nor detach it from socket Before switching on make sure that the operational voltage Us of the lateral type plate and the mains voltage are the same Put into operation the thermostat as follows Connect thermocouple ...

Page 4: ...Wiring scheme 1 2 4 5 6 7 8 9 10 11 12 3 analog output option TMS 400 K1 Us Design S12 5 104 5 82 36 23 5 AA AA AA 38 34 80 61 5 17 5 7 5 41 5 17 41 10 82 1 1 2 3 4 5 7 6 8 9 10 11 12 11 5 16 5 2 3 1 14 27 5 116 AA AA 41 5 Base 1 2 3 Cable bushing Mounting bore hole Unlatching only with rail mounting 2 6 Jacks for coding pins 1 ...

Reviews: